6
rpm
0 to 8000
7
rlkw
0 to 5600
8
skipfrq1
0 to 102
9
skipfrq2
0 to 102
10
skipfrq3
0 to 102
11
skipband
0 to 102
12
ramp_inc
5 to 60
13
ramp_dec
5 to 60
14
lvim_th
1 to 10
15
lvim_per
1 to 10
16
lcim_th
5 to 40
17
lcim_per
1 to 10
18
mcim_th
5 to 40
19
mcim_per
1 to 10
20
scycd_en
DSABLE_ENABLE
21
pwm_freq
0 to 1
22
blank
-
23
unit_byp
DSABLE_ENABLE
24
syst_byp
DSABLE_ENABLE
25
com_tout
0 to 255
26
res_def
NO_YES
*Depends on the selected language (English by default).
GENCONF - General
Name
Range
1
min_off
1 to 15
SRDC-UG-2-14-000
19 Series Carrier®
TM
SmartVu
Controls IOM
3000
rpm
1500
kW
30
Hz
30
Hz
30
Hz
0
Hz
30
sec
30
sec
10
%
10
sec
40
%
10
sec
40
%
10
sec
DSABLE
-
0
-
-
-
DSABLE
-
DSABLE
-
10
sec
NO
-
Default
Unit
3
min
REVISION
DATE
2.3
Dec 4, 2020
Motor Nameplate RPM
Motor Nameplate KW
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
Skip Frequency Band
Increase Ramp Time
Decrease Ramp Time
Line Voltage Imbalance%
Line Volt Imbalance Time
Line Current Imbalance%
Line Current Imbal Time
Motor Current Imbalance
Motor Current Imbal Time
Single Cycle Dropout
PWM Switch Frequency
2KHz=0, 4KHz=1
Unit Bypass Option
System Bypass Option
Communication Timeout
Restore Defaults
Displayed text*
Stop to Start Delay
PAGE
159 OF 168