Carrier SmartVu Control Manual
Carrier SmartVu Control Manual

Carrier SmartVu Control Manual

For 19 series centrifugal chiller
Hide thumbs Also See for SmartVu Control:
Table of Contents

Advertisement

SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
TM
SmartVu
2.3
Dec 4, 2020
1 OF 168
Controls IOM
Control IOM
TM
Carrier® SmartVu
Control for 19 Series Centrifugal Chiller
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SmartVu Control and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier SmartVu Control

  • Page 1 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 1 OF 168 Controls IOM Control IOM Carrier® SmartVu Control for 19 Series Centrifugal Chiller...
  • Page 2 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 2 OF 168 Controls IOM Portions of control software (bash, diffutils, dosfstools, findutils, grep, gzip, readline, sed, tar, wget) are licensed under the GNU General Public License, version 3, © 2007 Free Software Foundation. You may obtain a copy of the license at https://www.gnu.org/licenses/gpl.html...
  • Page 3 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 3 OF 168 Controls IOM A portion of control software (OpenSSH) is Copyright (c) 1995 Tatu Ylonen <ylo@cs.hut.fi>, Espoo, Finland. All rights reserved. It is licensed under a BSD style license. You may obtain a copy of the license at https://github.com/openssh/openssh-portable/blob/master/LICENCE...
  • Page 4 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 4 OF 168 Controls IOM A portion of control software (bower) is Copyright (c) 2013-present Twitter and other contributors. It is licensed under a MIT X11 style license. You may obtain a copy of the license at https://github.com/bower/bower/blob/master/LICENSE...
  • Page 5: Table Of Contents

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 5 OF 168 Controls IOM Contents Contents..........................5 SAFETY CONSIDERATIONS..................10 1.1. General Description ....................10 1.2. Avoid Electrocution ....................10 GENERAL DESCRIPTION ....................11 2.1. General Description ....................11 2.2. Abbreviations Used ....................11 HARDWARE DESCRIPTION ..................12...
  • Page 6 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 6 OF 168 Controls IOM 4.7. Alarm Screen ......................44 4.8. Menu Screen ......................44 4.9. Setpoint Screen ....................45 4.10. Configuration Screen....................45 4.11. Time Schedule Screen ..................47 4.12. Trending screen ....................48 4.13.
  • Page 7 4.15.5. Motor Status ....................63 4.15.6. Envelope Control Status...................64 4.15.7. VFD Status ......................64 4.15.8. Startup Sequence ....................65 4.15.9. Purge System Status ..................65 4.15.10. Startup Sequence ..................66 19 SERIES CARRIER® SMARTVU CONTROL OPERATION ........67 5.1. Start/Stop Control ....................67 5.2. Chiller Run Status ....................67 5.3.
  • Page 8 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 8 OF 168 Controls IOM 5.13. Damper Vapor Source...................78 5.14. Demand Limit ......................78 5.15. Override Control ....................79 5.16. Recycle Control ....................83 5.17. Running Timers and Counters ................83 5.18. Water Pumps Control ...................84 5.19.
  • Page 9 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 9 OF 168 Controls IOM 5.35.1. Oil Stir Function ....................95 5.35.2. Power Request ....................95 5.35.3. Evaporator Approach Calculation ..............96 5.35.4. Evaporator Liquid Temperature Calculation ............96 5.35.5. Free Cooling ....................94 5.35.6.
  • Page 10: Safety Considerations

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 10 OF 168 Controls IOM 1. SAFETY CONSIDERATIONS 1.1. General Description Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the installation are not considered: operating pressures, presence of electrical components and voltages and the installation site (elevated plinths and built-up up structures).
  • Page 11: General Description

    2.1. General Description Carrier® SmartVu control is a control system for controlling Carrier 19 Series chiller which include both legacy and next generation centrifugal water-cooled chillers. The control system monitors and controls all operations of the chiller. The control system matches the cooling or heating capacity of the chiller to the cooling or heating load while providing state-of-the-art chiller protection.
  • Page 12: Hardware Description

    3. HARDWARE DESCRIPTION 3.1. General Description The 19 Series Carrier® SmartVu control system consists of one main control board (Carrier® SmartVu board), an ISM (Integrated Starter Module) for fixed speed chiller or freestanding VFD conf iguration and several IOBs and SIOB per system configuration requirements. All boards communicate via an internal LEN bus.
  • Page 13 PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 13 OF 168 Controls IOM Figure: 19 Series Carrier® SmartVu Control - View From Below Figure: 19 Series Carrier® SmartVu Control - View From Side Legend: J1: Reserved J5: Reserved J6: LEN connector,LEN/485 - IOB/SIOB, ISM, …...
  • Page 14 Connectivity J16: Ethert port 1 (default IP: 192.168.100.100, mask: 255.255.255.0) Carrier Proview (firmware upgrade) * Modbus/RTU and Modbus/TCP can only be enabled one instance at same time ** BACNET/IP and BACnet/mstp can only be enabled one instance at same time The main control board is supplied from a 24 VAC supply referred to earth.
  • Page 15: Ism (Integrated Starter Module)

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 15 OF 168 Controls IOM 3.1.2. ISM (Integrated Starter Module) ISM is motor control module for fixed speed or free standing VFD configuration, and it is supplied from an 115VAC supply referred to earth.
  • Page 16: Io Board

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 16 OF 168 Controls IOM 3.1.3. IO Board IO Board is Input/output Board, and it is supplied from a 24VAC supply ref erred to earth. For the IOB input / output description, please refer to section 3.5.
  • Page 17: Sensors

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 17 OF 168 Controls IOM 3.2. Sensors Pressure transducers: Pressure transducers are used to measure and control the pressures in the unit. These electronic sensors deliver 0 to 5 VDC. The transducers can be calibrated through the controller. The pressure transducers are connected to the IOBs.
  • Page 18 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 18 OF 168 Controls IOM Condenser entering This is an optional transducer, and it Optional for 19XR2~E/V/D, water pressure measures the pressure of condenser entering 19XR6/7 and 19DV...
  • Page 19 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 19 OF 168 Controls IOM High speed motor end measure the high speed motor end bearing Standard for 19XR6/7 bearing temperature temperature sensor High speed comp end measure the high speed compressor end...
  • Page 20: Controls Outputs

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 20 OF 168 Controls IOM 3.3. Controls Outputs Evaporator / Condenser water pump The controller can regulate an optional evaporator / condenser water pump. Inlet Guide Vane The Inlet Guide vane (IGV) is used to adjust the refrigerant vapor flow into compressor to change in the operating conditions of the machine.
  • Page 21 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 21 OF 168 Controls IOM...
  • Page 22 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 22 OF 168 Controls IOM 19XR6/7 I/O Mapping: For 19XR6/7 IOB1/2/3 is standard and IOB4 is optional. Board # Channel # Description Comments IOB1 Entering Chilled Water Temperature...
  • Page 23 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 23 OF 168 Controls IOM IOB1 user option , 0=chiller off, Chiller Status(Discrete) 1=chiller running IOB2 Motor Winding Temperature 1 IOB2 Motor Winding Temperature 2 IOB2 Motor Winding Temperature 3...
  • Page 24 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 24 OF 168 Controls IOM IOB3 [If guide vane1 Type is Analog] For analog type guide GV1 Pos Feedback vane [If guide vane1 Type is Digital] For digital type guide vane...
  • Page 25 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 25 OF 168 Controls IOM [If Water Pressure Option is PD TRM (transmitter)] Cond Water Pres Drop IOB4 [If Water Pressure Option is PD TRD (transducers)] User option...
  • Page 26 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 26 OF 168 Controls IOM AI10 FS VFD Load Current For free standing VFD IOB1 IOB1 AI11 Head Pressure Output 2 User option IOB1 Oil EXV Output IOB1...
  • Page 27 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 27 OF 168 Controls IOM [If economizer liquid bypass option is For vapor source valve enalbe] Liquid Bypass Valve Head Pressure Output User option IOB2 User option, dry contact, “Closed”...
  • Page 28 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 28 OF 168 Controls IOM Chiller Status(Discrete) User option IOB3 User option, 24VAC output, recommend Chiller Alert Relay IOB3 with external power supply Chilled Water Pump User option...
  • Page 29 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 29 OF 168 Controls IOM 19DV I/O mapping: For 19DV IOB1/2/3 is standard and IOB4 is optional. Board # Channel # Description Comments IOB1 Entering Chilled Water Temperature...
  • Page 30 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 30 OF 168 Controls IOM IOB2 Condenser Refrigerant Vapor Temperature Standard for DV5 IOB2 Used f or mA type EC Valve Feedback HGBP valve IOB2 IOB2 Pump Outlet Pressure...
  • Page 31 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 31 OF 168 Controls IOM IOB3 Head Pressure Output User option IOB3 Head Pressure Output 2 User option IOB3 Guide Vane 2 Output IOB3 IOB3 IOB3 User option, normal...
  • Page 32 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 32 OF 168 Controls IOM IOB4 AI11 IOB4 IOB4 IOB4 IOB4 IOB4 Power Request Feedback Marine option IOB4 Customer Alert User option IOB4 Free Cooling Start Switch User option...
  • Page 33 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 33 OF 168 Controls IOM IOB1 [If Evap Liquid Temp Opt is enable] Evap. Refrigerant Liquid Temperature IOB1 Comp Discharge Temperature IOB1 Condenser Pressure IOB1 Evaporator Pressure IOB1...
  • Page 34 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 34 OF 168 Controls IOM IOB2 AI10 Motor Winding Temperature 3 IOB2 AI11 IOB2 Used for Analog type Guide Vane1 Output guide vane actuator IOB2 Head Pressure Output 2...
  • Page 35 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 35 OF 168 Controls IOM IOB3 IOB3 IOB4 IOB4 [If Water Pressure Option is PD TRD (transducers)] Evap Enter Water Volts User option, if IOB4 IOB4 installed, same as...
  • Page 36: Connections At The Field Terminal Block

    The electrical characteristics of the transmission Cables shall be comprised of three conductors, (1.5 Pairs) two signals and one ground of 20 AWG or larger with 100% shield plus a tinned copper braid (65% coverage), embodied as one of the following types is recommended by Carrier: * Belden #8772 (for intra-building, 60 deg C)
  • Page 37 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 37 OF 168 Controls IOM be separated from other cables. Making the communication cable go through metal shield conduct is pref erred.
  • Page 38: User Interface Setting

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 38 OF 168 Controls IOM 4. USER INTERFACE SETTING 4.1. User Interface The user interf ace is a colorful 10.1” TFT touch screen. Navigation is either direct from the touch screen interf ace or by connecting to a web interface via the Ethenert IP port of the controller.
  • Page 39: Synoptic Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 39 OF 168 Controls IOM 4.3. Synoptic Screen Synoptic screen access button Main Menu access button User Login screen access button Unit Start/Stop access button Alarm menu access button...
  • Page 40: Language & Units Selection Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 40 OF 168 Controls IOM 4.4. Language & Units Selection Screen Cursor showing the activated language Unit of measurement selection: Metric/Imperial...
  • Page 41: Login Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 41 OF 168 Controls IOM 4.5. Login Screen Currently, the controller supports user login and service login. The def ault password for user login is “1111”, and it can be configured in local user login page.
  • Page 42: Chiller Start/Stop Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 42 OF 168 Controls IOM Log in Log off Enter the password 4.6. Chiller Start/Stop Screen The On/Of f screen allows users to select the unit operating mode.
  • Page 43: Chiller Stop

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 43 OF 168 Controls IOM 4.6.2. Chiller Stop To Stop the unit - press the following button:...
  • Page 44: Alarm Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 44 OF 168 Controls IOM Conf irm the unit shut-down or return to the previous screen. 4.7. Alarm Screen To access Alarm screen, press the following button: . More detailed contents please refer to chapter 6.
  • Page 45: Setpoint Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 45 OF 168 Controls IOM 4.9. Setpoint Screen 4.10. Configuration Screen...
  • Page 46 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 46 OF 168 Controls IOM Save Cancel Message Previous page Next page Below is an example to show how to force a point. Forcible point Forced value...
  • Page 47: Time Schedule Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 47 OF 168 Controls IOM The Auto button cancels the force action on the point. 4.11. Time Schedule Screen Detailed information please ref er to section 5.24.
  • Page 48: Trending Screen

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 48 OF 168 Controls IOM Selection of the applicable days for the time schedule Modification of the period start and end schedules Save Cancel Previous period Next period 4.12.
  • Page 49: 19Xr6/7/F Device Status Display Screens

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 49 OF 168 Controls IOM 4.13. 19XR6/7/F Device Status Display Screens The following screens are designed for end user to check the components status. 4.13.1. System Overview The following screen is the system overview screen (default screen), by clicking the component in this screen, user can enter the specific component screen, or clicking the bottom in home page.
  • Page 50: Condenser Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 50 OF 168 Controls IOM 4.13.2. Condenser Status...
  • Page 51: Evaporator Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 51 OF 168 Controls IOM 4.13.3. Evaporator Status 4.13.4. Compressor Status...
  • Page 52: Motor Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 52 OF 168 Controls IOM 4.13.5. Motor Status 4.13.6. Economizer Status The pressure difference shown in this screen is the pressure difference between economizer pressure and evaporator pressure.
  • Page 53: Transmission Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 53 OF 168 Controls IOM 4.13.7. Transmission Status 4.13.8. Envelope Control Status...
  • Page 54: Vfd Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 54 OF 168 Controls IOM 4.13.9. VFD Status 4.13.10.Startup Sequence The f ollowing screen shows the sequence of startup check items. Touch the mode title of main screen to...
  • Page 55: 19Xr2~5/C/D/E/V Device Status Display Screens

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 55 OF 168 Controls IOM 4.14. 19XR2~5/C/D/E/V Device Status Display Screens The following screens are designed for end user to check the components status. 4.14.1.System Overview The following screen is the system overview screen (default screen), by clicking the component in this screen, user can enter the specific component screen, or clicking the bottom in home page.
  • Page 56: Condenser Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 56 OF 168 Controls IOM 4.14.2.Condenser Status 4.14.3. Evaporator Status...
  • Page 57: Compressor Status - Single Stage

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 57 OF 168 Controls IOM 4.14.5. Compressor Status – Single Stage 4.14.6. Compressor Status – Dual Stage...
  • Page 58: Motor Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 58 OF 168 Controls IOM 4.14.7. Motor Status 4.14.8. Transmission Status 4.14.9. Transmission Status...
  • Page 59: Envelope Control Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 59 OF 168 Controls IOM 4.14.10. Envelope Control Status...
  • Page 60: Vfd Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 60 OF 168 Controls IOM 4.14.11.VFD Status 4.14.12.Startup Sequence The f ollowing screen is showing the startup sequence after user push the startup button. User can check where we are in the startup process.
  • Page 61: 19Dv Device Status Display Screens

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 61 OF 168 Controls IOM 4.15. 19DV Device Status Display Screens 4.15.1. System Overview The f ollowing screen is the system overview screen (default screen), by clicking the component in this...
  • Page 62: Condenser Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 62 OF 168 Controls IOM 4.15.2. Condenser Status 4.15.3. Evaporator Status...
  • Page 63: Compressor Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 63 OF 168 Controls IOM 4.15.4. Compressor Status 4.15.5. Motor Status...
  • Page 64: Envelope Control Status

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 64 OF 168 Controls IOM 4.15.6. Envelope Control Status 4.15.7. VFD Status...
  • Page 65: Startup Sequence

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 65 OF 168 Controls IOM 4.15.8. Startup Sequence 4.15.9. Purge System Status...
  • Page 66: Startup Sequence

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 66 OF 168 Controls IOM 4.15.10.Startup Sequence The f ollowing screen is showing the startup sequence after user push the startup button. User can check where we are in the startup process.
  • Page 67: Series Carrier® Smartvu

    – SmartVu Dec 4, 2020 67 OF 168 Controls IOM 5. 19 SERIES CARRIER® SMARTVU CONTROL OPERATION 5.1. Start/Stop Control This f unction determines the chiller STATSTOP command. There are 4 control modes (LOCAL, LOCAL SCHEDULE, REMOTE, NETWORK) can be selected. In a certain control mode, only appropriate control sources are valid to start or stop chiller.
  • Page 68: Chiller Start-Up Sequence

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 68 OF 168 Controls IOM "LOCKOUT Lockout in Controls Test is active " "RECYCLE Recycle shutdown completed on 12mA " low load in effect; non-fault condition "TRIPOUT" Shutdown completed due to alarm f ault condition.
  • Page 69: Startup

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 69 OF 168 Controls IOM COMP BEARING TEMP >= COMP BEARING ALERT- 10F Alarm COMP MOTOR WINDING TEMP >= MOTOR TEMP OVERRIDE - 10F Alarm COMP DISCHARGE TEMP >= COMP DISCHARGE ALERT- 10F Alarm EVAP_SAT <...
  • Page 70: Chiller Shutdown Sequence

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 70 OF 168 Controls IOM When chiller type is 19XR6/7, and oil pump kept OFF for over 50 hours. The oil prelube time will be 6 minutes instead of 40 seconds.
  • Page 71: Oil Lubrication Control

    19XR2~5/C/D/E/V/F currently. The terminal channel is located in IOB1 AO1, and it is a 4~20mA signal. During operation, Carrier® SmartVu control system will modulate the VFD speed to control the lubrication system oil pressure difference to between 25psi and 35psi.
  • Page 72: Refrigerant Lubrication Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 72 OF 168 Controls IOM 5.6. Refrigerant Lubrication Control For the 19DV system, refrigerant is used to lubricate and cool the compressor bearings. The ref rigerant lubrication system mainly includes refrigerant pumptwo control valves, evaporator and condenser filter, moisture removal desiccant, bearing filter, liquid level switch and additive reclaim system.
  • Page 73: Control Point

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 73 OF 168 Controls IOM 5.7.2. Control Point Capacity control is based on achieving and maintaining a CONTROL POINT temperature, which is the sum of the valid set point (from the SETPOINT screen) and a temperature reset value.
  • Page 74: Capacity Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 74 OF 168 Controls IOM 5.8. Capacity Control Capacity control shall provide chilled or condenser water temperature control by modulating the position of the inlet guide vane 1, and VFD speed for variable speed compressor based.
  • Page 75: Ramp Loading

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 75 OF 168 Controls IOM When chiller is running normally, the control will get input from capacity control to see whether to change VFD TARGET SPEED and how much to change.
  • Page 76: Surge Prevention Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 76 OF 168 Controls IOM A surge condition occurs when the lift becomes so high that the gas flow across the impeller reverses. This condition can eventually cause compressor damage. The envelope control algorithm notifies the operator that chiller operating conditions are marginal and to take action to help prevent compressor damage such as lowering entering condenser water temperature.
  • Page 77: Envelope Control Valve (Ec) Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 77 OF 168 Controls IOM If SURGE PROTECTION COUNTS exceed 20 within a SURGE TIME PERIOD and VFD speed has reached the maximum speed If IGV, VFD and EC are not able to be operated to do surge protection, when surge count is greater than 4.
  • Page 78: Damper Vapor Source

    5.14. Demand Limit The 19 Series Carrier® SmartVu controls provide a f eature for limiting AVERAGE LOAD CURRENT or Motor KILOWATTS by limiting capacity via guide vane control/VFD control. The limit applied is called ACTIVE DEMAND LIMIT, which is equal to a BASE DEMAND LIMIT value (set in the SETPOINT Screen, default value 100%), or be determined by AUTO DEMAND LIMIT INPUT (an optional 4-20 mA input, described below).
  • Page 79: Override Control

    - When the value of interest crosses the First Stage Set Point into the Override Region, the capacity are prevented from increasing further, and the status line on the 19 Series Carrier® SmartVu controller indicates the reason for the override. Normal capacity control operation is restored when the value crosses back over the First Stage Set Point, leaving the Override Region.
  • Page 80 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 80 OF 168 Controls IOM closed for a consecutive 20 seconds; for 19DV, Ignore low discharge superheat override during first 5 minutes af ter chiller startup completed.
  • Page 81 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 81 OF 168 Controls IOM Second Stage First Stage Override Override Configurable Capacity Override Capacity Inhibit Decrease Condition Range Value Termination Parameter > COND PRESS For low condenser High Condenser >...
  • Page 82 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 82 OF 168 Controls IOM PERCENT LINE PERCENT LINE PERCENT LINE CURRENT > CURRENT > CURRENT <= 100% 105% 100% or RECTIFIER (If 32VS VFD is High CURRENT...
  • Page 83: Recycle Control

    DELTA T f or 5 consecutive seconds. 5.17. Running Timers and Counters 19 Series Carrier® SmartVu control maintains three run time clocks: COMPRESSOR ONTIME, COMPRESSOR CONTINOUSE ONTIME and SERVICE ONTIME. COMPRESSOR ONTIME indicates the total lifetime compressor run hours. SERVICE ONTIME is a resettable timer that can be used to indicate the hours since the last service visit or any other event.
  • Page 84: Water Pumps Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 84 OF 168 Controls IOM the HMI. Both Ontime counters roll over to 0 at 500,000 hours. Manual changes to SERVICE ONTIME f rom the screen are permitted at any time.
  • Page 85: Quick Test

    19DV 72PSI condenser. Condenser Freeze Prevention — This control helps prevent condenser tube freeze-up by energizing the condenser pump relay. The 19 Series Carrier® SmartVu controls the pump and, by starting it, helps to prevent the water in the condenser from freezing.
  • Page 86: Analog Output

    5.21. Cooling Tower Control If “water pressure option” in CONF_OPT table is ENABLED, there will be another optional hydraulic control I/O board in the Carrier® SmartVu control system to allow Carrier® SmartVu control the water pumps and cooling tower fans (high speed and low speed).
  • Page 87: Head Pressure Control

    Head Pressure Control If the chiller system is equipped with head pressure control valve, and head pressure valve option in CONF_OPT table is ENABLED, then Carrier® SmartVu control system will control the opening of head pressure valve to maintain the pressure difference between condenser and evaporator. The output of this valve is 4-20mA type.
  • Page 88: Pressure Transducer Calibration

    12 records (1 minute) after. Each record is associated with a time stamp. These collections are saved as csv files. 20 files can be stored in total. The black box file can be uploaded with Carrier S-Proview. Once the upload is done, the original files saved in controller will be erased.
  • Page 89: Ism Calibration

    Once activate this function (in E-mail configuration menu) and set a valid E-mail address, and when any alarm occurs, Carrier® SmartVu will automatically send an E-mail to the mail address to inform the corresponding alarm information.
  • Page 90: Prognostic

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 90 OF 168 Controls IOM 5.30. Prognostic This prognostic function is designed for service trouble shooting. The prognostic function enables the service engineer to resolve the problem before they affected the operating efficiency and the chiller bottom life.
  • Page 91 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 91 OF 168 Controls IOM...
  • Page 92: Master Slave Control

    Oil EXV Control If the chiller system is equipped with Oil EXV control valve, and Oil EXV valve option in CONF_OPT table is ENABLED, then Carrier® SmartVu control system will control the opening of Oil EXV valve to maintain the oil supply temperature. The output of this valve is 4-20mA type.
  • Page 93: Water Pressure Difference Measurement

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 93 OF 168 Controls IOM Step 2: Set ”Option 2” -> ”Water Flow Measurement” as ”Flow Meter”, and the corresponding value of Water Flow at 4ma and 20ma.
  • Page 94: Free Cooling

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 94 OF 168 Controls IOM Step 2: Set ”Option 2” -> ”Water Pressure Option” as ”Pressure Drop”. Step 3: Set ”Option 2” -> ”Water Pressure Drop @20mA” the rated value of the transducer.
  • Page 95: Marine Option

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 95 OF 168 Controls IOM If the f ree cooling is activated the control shall take the following measure: If chiller is in not in OFF status, ignore the free cooling request (chiller will continue to run) until chiller shut down.
  • Page 96: Evaporator Approach Calculation

    5.36. Open Protocol Support Modbus/TCP on Carrier® SmartVu controller can be configured with the following steps: Step 1: Configuration Menu ->Network Configuration Step 2: Enable the Modbus/TCP, ethernet port 0 will be configured as Modbus/TCP or BACnet/IP...
  • Page 97 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 97 OF 168 Controls IOM Step 3: Controller will reboot automatically to save the configuration Note: Enable Modbus TCP, the Ethernet port will be used as Modbus / TCP interf ace, otherwise J8 port is Modbus / RTU;...
  • Page 98: Purge Control

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 98 OF 168 Controls IOM DEM_LIM Actual Demand Limit Analog Network 3018 EMSTOP Emergency Stop Switch Network 3020 HC_SEL Cooling/Heating Select Switch Network 3022 CHIL_OCC Network:Cmd Occupied Switch...
  • Page 99: Motor Rotation Check Option

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 99 OF 168 Controls IOM then set the ref rigerant level flag to ON. And if purge level in the purge tank is low, drainage solenoid valve should be closed.
  • Page 100: Liquid Bypass Control For 19Xrc

    Especially when pressure drop between upstream and downstream is lower than design point, or the chiller operating capacity over the limitation,the flow ability of a f ixed orifice will be de- rated. So if the chiller operates at a low lift, Carrier® SmartVu needs to limit the cooling capacity by inhibiting motor run at a high current or limiting input power to prevent liquid choke at high side orifice.
  • Page 101: Diagnostics - Troubleshooting

    This section provides the overview of actions to be taken in case any operating problems occur. 6.1. General The 19 Series Carrier® SmartVu control system has many fault tracing aid functions. The local interf ace and its various menus give access to all unit operating conditions.
  • Page 102: Alarm / Alert Codes

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 102 OF 168 Controls IOM 6.4. Alarm / Alert Codes 6.4.1. General Alarm Codes Alarm Description of the Reset type Action Possible cause code* alarm text taken by...
  • Page 103 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 103 OF 168 Controls IOM As above Alm-211 ALM-211 Sensor Fault As above Check sensor resistance. Check for proper wiring High Speed Comp - High Speed Comp End Bearing Temp Sensor and IOB End Bearing Temp connector.
  • Page 104 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 104 OF 168 Controls IOM Check for disconnected, grounded, or shorted wiring. Check for condensation in transducer connector. Alm-218 ALM-218 Sensor Fault As above As above Check Diffuser pressure transducer wiring.
  • Page 105 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 105 OF 168 Controls IOM Check compressor discharge temperature sensor wiring and accuracy to IOB connector. Check for excessive starts. Check COMP DISCHARGE ALERT setting. Check Evaporator Pressure, Evap Sat...
  • Page 106 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 106 OF 168 Controls IOM EVAP FLOW DELTA P CUTOUT, and WATER FLOW VERIFY TIME settings. Check load resistors, optional water flow switches or water flow delta P transducer calibration and wiring to IOB.
  • Page 107 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 107 OF 168 Controls IOM Check CONDENSER PRESSURE. Check Alm-257 ALM-257 Protective As above As above for high Condenser Water temperatures, Limit - High Condenser low water flow, fouled tubes. Check for...
  • Page 108 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 108 OF 168 Controls IOM Check diffuser schedule and guide vane schedule in SRD Configuration screen. Check for proper operation of diffuser and inlet guide vane actuators including inlet guide vane calibration.
  • Page 109 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 109 OF 168 Controls IOM Alm-277 ALM-277 Protective Manual Same as Carrier® SmartVu Power on reset Limit - UI Freeze above controller Reboot Alm-278 ALM-278 Protective Manual Same as...
  • Page 110 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 110 OF 168 Controls IOM Communication Failure Alm-300 ALM-300 Loss Automatic when Unit shuts Bus installation fault or defective slave Communication With the communication down. board comes back to...
  • Page 111 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 111 OF 168 Controls IOM As above As above Alm-354 Sensor Fault - Heat Tested when the compressor is on Reclaim Leaving Temp whatever the run status and the...
  • Page 112 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 112 OF 168 Controls IOM CURRENT IMBALANCE TIME. Check settings in ISM_CONF screen. Check ISM_HIST screen. Check current transformer wiring leading to ISM terminal block J4. Verify phase to phase and phase to ground line voltage.
  • Page 113 Check motor power leads for phase to phase or phase to ground shorts. Disconnect motor from starter and merger motor windings to ground and phase to phase. Call Carrier Service. The ISM has detected that the input power Alm-410...
  • Page 114 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 114 OF 168 Controls IOM OPTION in SETUP 2 screen. Check for wiring of current transformers to the J4 ISM terminals. Check if main circuit breaker has tripped. Check ISM_HIST screen.
  • Page 115 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 115 OF 168 Controls IOM high transient voltage conditions. VFD Circuit Board malfunction. Call Carrier Service Alm-431 ALM-431 VFD Fault - As above As above Temporary loss of VFD control voltage.
  • Page 116 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 116 OF 168 Controls IOM Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage. Alm-445 ALM-445 VFD Fault - As above...
  • Page 117 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 117 OF 168 Controls IOM As above Alm-512 VFD Fault - Short As above As above Circuit As above Alm-513 VFD Fault - Inrush As above As above...
  • Page 118: General Alert Codes

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 118 OF 168 Controls IOM 6.4.2. General Alert Codes ALARM Description of the Reset type Action Possible cause alarm text taken by code* the control Prestart alert Check STARTS IN 12 HOURS in Run times...
  • Page 119 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 119 OF 168 Controls IOM Temperature Reset sensor resistance or voltage drop. Check for proper wiring to CCM J4-13 & J4- Alt-121 As above CheckTemp Reset Configuration ALT-121 Sensor Alert -...
  • Page 120 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 120 OF 168 Controls IOM Alt-136 As above Check temp reset configurations ALT-136 Configuration As above Error - Temp Reset Alt-137 As above Check controlled water temp reset...
  • Page 121 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 121 OF 168 Controls IOM Alt-154 ALT-154 Process Alert - As above As above Check damper valve wiring and position Damper Valve Alert feedback inputs Alt-155 ALT-155 Process Alert -...
  • Page 122: Event States

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 122 OF 168 Controls IOM Alt-175 ALT-175 Master Slave Manual As above Check master control type Alert - ncorrect Master Control Type Alt-176 ALT-176 Master Slave Automatic As above...
  • Page 123 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 123 OF 168 Controls IOM Auto Restart Pending Condenser Flush in Progress Guide Vane 2 Calibration Envelope Control Valve Calibration Startup Inhibited - Loadshed in Effect Prestart Check in Progress...
  • Page 124 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 124 OF 168 Controls IOM Running - Guide Vane 2 Position Forced Operation - Refrigerant Lub Forced Running - Vapor Source Valve Forced Purge - Regeneration Forced Shutdown - Normal...
  • Page 125: Controller Ip Address Setting

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 125 OF 168 Controls IOM 7 CONTROLLER IP ADDRESS SETTING The user can go to the Ethernet configuration in the configuration menu to check and modify the IP...
  • Page 126 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 126 OF 168 Controls IOM Note: The IP addresses of J15 and J16 shall NOT be in the same sub network, for example , if J15 is conf igured as 169.254.1.1/255.255.0.0, then J16’s IP address can’t be configured as 169.254.x.x.
  • Page 127 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 127 OF 168 Controls IOM Click the Gateway/DNS Config in System Configuration page, will display the below page: Note: The Gateway 1 Destination/Mask of Gateway 1 IP and Gateway 2 IP can’t be set as 0.0.0.0/0 at the...
  • Page 128 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 128 OF 168 Controls IOM 8 WEB UI Access the SmartViewTM control by entering the IP address in the web browser. Set the IP address of the component: 169.254.1.1, then the address accessed by the web browser address bar is https://169.254.1.1...
  • Page 129: Screen Structure

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 129 OF 168 Controls IOM 9 SCREEN STRUCTURE...
  • Page 130: Detailed Menu Description

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 130 OF 168 Controls IOM 9.1. Detailed Menu Description Icon Displayed text* Description Access Associated table General Parameters GENUNIT Temperatures TEMP Pressures PRESSURE Inputs Status INPUTS Outputs Status...
  • Page 131 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 131 OF 168 Controls IOM Maintenance Menu USER MAINTAIN Trending Quick Calibration SERVICE QCK_CAL System USER SYSCONF Configuration *Depends on the selected language (English by default). GENUNIT - General Parameters...
  • Page 132 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 132 OF 168 Controls IOM °F AMPS_P Percent Current KW_P Motor Percent Kilowatts cal_capa Calculated Capacity DEM_LIM 10 to 100 Actual Demand Limit EMSTOP DSABLE_ENABLE DSABLE BMS Emergency Stop...
  • Page 133 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 133 OF 168 Controls IOM °C LCDW -17.78 Leaving Condenser Water °F °C HR_EWT -17.78 Heat Recl Entering Temp °F °C HR_LWT -17.78 Heat Recl Leaving Temp °F °C...
  • Page 134 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 134 OF 168 Controls IOM °F 0.00 Discharge Superheat °C MTRB_OIL -17.78 Thrust Bearing Oil Temp °F °C MTRB -17.78 Thrust Bearing Temp °F °C MTRB1 -17.78 Low Speed ME Brg Temp °F...
  • Page 135 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 135 OF 168 Controls IOM LIFT_A 0.00 Actual Lift LIFT_1 0.00 VDO High Lift Load Line LIFT_2 0.00 VDO Low Lift Load Line °C R_RESET -17.78 Remote Reset Temp °F...
  • Page 136 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 136 OF 168 Controls IOM PSIG OILP_DIS 0.00 Oil Supply Pressure PSIG OILP_SMP 0.00 Oil Sump Pressure PSIG OIL_PD 0.00 Oil Pump Delta P pd_off -34.48 to 20.69 0.00...
  • Page 137 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 137 OF 168 Controls IOM INPUTS - Inputs Status Name Range Default Unit Displayed text* STAR_AUX OPEN_CLOSE OPEN Compressor Start Contact RUN_AUX OPEN_CLOSE OPEN Compressor Run Contact DMP_FC...
  • Page 138 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 138 OF 168 Controls IOM AUTO_DEM Auto Demand Limit Input AUTO_RES Auto Water Temp Reset REF_LEAK Refrig Leakage Sensor VFD_IN VFD Speed Feedback GV1_MA GV1 Pos Feedback GV2_MA...
  • Page 139 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 139 OF 168 Controls IOM GV1_INC OFF_ON Guide Vane 1 Increase VFD_OUT VFD Speed Output mA OIL_HEAT OFF_ON Oil Heater Relay OIL_PUMP OFF_ON Oil Pump Relay CHST_OUT Chiller Status (Analog)
  • Page 140 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 140 OF 168 Controls IOM hdpv_tgt Head Pres Valve Tgt Pos HDPV_OUT Head Pres Output mA HDPV_OU2 Head Pres2 Output mA TFR_HIGH OFF_ON Tower Fan Relay High TFR_LOW...
  • Page 141 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 141 OF 168 Controls IOM COMP_PSV OFF_ON Purge Comp Valve PUMP_PSV OFF_ON Purge Pumpout Valve DRASVON OFF_ON Purge Drainage Valve REG_PSV OFF_ON Purge Regeneration Valve DIS_PSV OFF_ON Purge Discharge Valve...
  • Page 142 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 142 OF 168 Controls IOM cdw_off -68.95 to 68.95 0.00 Condenser Delta P Offset -10 to 10 cdw_pull 0.00 Cond Water Pulldown/Min CHWP OFF_ON Chilled Water Pump CHW_FLOW...
  • Page 143 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 143 OF 168 Controls IOM ctrlw_dt 0.00 Controlled Water DT cdw_fl_s 0 to 2 Cond Flow Status blank Failed or Not Started=0 blank Success=1, Verifying=2 chw_fl_s 0 to 2...
  • Page 144 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 144 OF 168 Controls IOM PGP_TM Total Pumpout Time pgp_tm_d Purge Pumpout in 24 Hrs pgp_tm_w Avg Daily Purge in 7 Day uptime Controller Uptime blank day - hour : minute...
  • Page 145 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 145 OF 168 Controls IOM condfrze NO_YES Condenser Frozen rcysh_cm NO_YES Recycle Shutdown Done nrysh_cm NO_YES NonRecycle Shutdown Done alm_act NO_YES In Alarm over_act NO_YES In Override pg_act...
  • Page 146: Configuration Menu

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 146 OF 168 Controls IOM 9.2. Configuration Menu Icon Displayed text* Description Access Associated table Factory FACTORY FACTORY Service Parameters SERVICE SERVICE1 Surge Correction SERVICE CFGSURGE Protective Limit...
  • Page 147 0 to 9 VFD/Starter Option blank Starter with ISM = 0 blank FS VFD with ISM = 1 blank Carrier 32VS VFD = 2 blank Rockwell LF2 VFD = 3 blank Eaton VFD = 4 blank Rockwell STD VFD = 5...
  • Page 148 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 148 OF 168 Controls IOM coun_cod 0 to 999 Country Code gv1_type 0 to 1 Guide Vane1 Type blank Digital=0, Analog=1 dmp_type 0 to 1 ECO DMP VLV Type...
  • Page 149 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 149 OF 168 Controls IOM tmramprt 0.56 to 5.56 1.67 Temp Ramp per Min 1 to 10 rcysh_dt 0.28 to 2.22 0.56 Recycle Shutdown Delta T 0.5 to 4 rcyst_dt 1.11 to 5.56...
  • Page 150 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 150 OF 168 Controls IOM blank 1m/4h=2, Comb. 0&1=3 *Depends on the selected language (English by default). CFGSURGE - Surge Correction Name Range Default Unit Displayed text* sgl_cfg...
  • Page 151 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 151 OF 168 Controls IOM 0.1 to 3 sgl_shfh -0.06 to 0 -0.01 Surge Line Shape Factor sgl_shfl 0 to 0.2 0.06 Sound Line Shape Factor sgl_dmin 1.2 to 5...
  • Page 152 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 152 OF 168 Controls IOM gvliftm1 19.50 DTS@GV Opening 1 35.1 gvstall2 15.5 GV Opening 2 gvliftm2 30.50 DTS@GV Opening 2 54.9 gv_db GV Jumpover Range gv_delay GV Jumpover Delay gv_sk_th 0.50...
  • Page 153 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 153 OF 168 Controls IOM cpcut_hi 1,861.65 to 1,896.13 Cond Press Cutout High 1,896.13 PSIG 270 to 275 ert_ovdt 1.11 to 2.78 1.67 Evap Override Delta T 2 to 5 °C...
  • Page 154 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 154 OF 168 Controls IOM °C dgt_alrt 51.67 to 93.33 93.33 Comp Discharge Alert 125 to 200 °F °C mt_over 65.56 to 93.33 93.33 Comp Motor Temp Override 150 to 200 °F...
  • Page 155 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 155 OF 168 Controls IOM cond_val 3.45 to 344.75 344.75 Cond Hi Flow DP Limit 0.5 to 50 cond_alm DSABLE_ENABLE DSABLE Cond Hi Flow Alarm °C inv_ov 37.78 to 204.44 93.33...
  • Page 156 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 156 OF 168 Controls IOM hdpv_opt DSABLE_ENABLE DSABLE HPR VLV Option hdp_0 0.00 to 586.08 172.38 HPR VLV Delta Pos 0% 0 to 85 hdp_100 0.00 to 586.08 344.75...
  • Page 157 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 157 OF 168 Controls IOM vssv_dly 0 to 10 Vapor Source SV Delay evap_t_o DSABLE_ENABLE ENABLE Evap Liquid Temp Opt evap_ref 0 to 1 Evap App Calc Selection...
  • Page 158 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 158 OF 168 Controls IOM 0 to 12000 chwf_bas 0.00 to 34,065.00 0.00 l/min Evap Flow Rate Baseline 0 to 9000 evpd_bas 0.00 to 137.90 0.00 Evap Pres Drop Baseline...
  • Page 159 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 159 OF 168 Controls IOM 0 to 8000 3000 Motor Nameplate RPM rlkw 0 to 5600 1500 Motor Nameplate KW skipfrq1 0 to 102 Skip Frequency 1 skipfrq2...
  • Page 160 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 160 OF 168 Controls IOM strt_dly 4 to 45 Start to Start Delay dem_sel 0 to 1 Demand Limit Type blank Base Demand=0, 4-20mA=1 rampslct 0 to 1...
  • Page 161 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 161 OF 168 Controls IOM dis_wt 0 to 40 PG Discharge Wait Time pgpumplm 20 to 200 Daily PG Pumpout Limit mot_pol 1 to 2 Motor Pole Pair...
  • Page 162 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 162 OF 168 Controls IOM vfdculm 0 to 99999 VFD Current Limit vfd_ldap DSABLE_ENABLE ENABLE VFD Load Current Input vfdc20ma 10 to 5000 VFD Load Current 20mA *Depends on the selected language (English by default).
  • Page 163: Quick Test Menu

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 163 OF 168 Controls IOM 9.3. Quick Test Menu QCK_TEST - Quick Test Name Range Default Unit Displayed text* QCK_TEST DSABLE_ENABLE DSABLE Quick Test Enable Q_OILH OFF_ON Oil Heater...
  • Page 164 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 164 OF 168 Controls IOM Q_DMPCL OFF_ON ECO DMP VLV Close Q_ALM OFF_ON Alarm Output Q_ALE OFF_ON Alert Output Q_CDWP OFF_ON Condenser Water Pump CDW_FLOW NO_YES Condenser Water Flow CDW_DT -22.22 to 136.11...
  • Page 165 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 165 OF 168 Controls IOM Q_EVAPSV OFF_ON Evap CV (DV Lube Sled) Q_OPRLUB OFF_ON Evap Drain CV Q_PRELUB OFF_ON Cond Drain CV Q_CDPSV OFF_ON Purge Cond SV Q_CMPSV...
  • Page 166 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 166 OF 168 Controls IOM GV1_CAL DSABLE_ENABLE DSABLE GV1 Calibration Enable GV1_STAT 0 to 2 GV1 Calibration Status blank No Calib Or Failure=0, blank Progress=1, Completed=2 GV1_OHM Guide Vane 1 Actual Ohms...
  • Page 167: Alarms Menu

    SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 167 OF 168 Controls IOM blank No Calib Or Failure=0, blank Progress=1, Completed=2 DMP_AMA ECO DMP VLV Actual mA DMP_MAXA ECO DMP VLV mA 100% DMP_MINA ECO DMP VLV mA 0%...
  • Page 168 SRDC-UG-2-14-000 REVISION DATE PAGE 19 Series Carrier® – SmartVu Dec 4, 2020 168 OF 168 Controls IOM alarm_5c Current Alarm 5 alarm_1 Jbus Current Alarm 1 alarm_2 Jbus Current Alarm 2 alarm_3 Jbus Current Alarm 3 alarm_4 Jbus Current Alarm 4...