Terminal Compartment (For Mains Connection): Close - AUMA SQ 05.2 Operation Instructions Manual

Part-turn actuators
Hide thumbs Also See for SQ 05.2:
Table of Contents

Advertisement

Electrical connection
5.2.3.

Terminal compartment (for mains connection): close

26
SQ 05.2
SQ 14.2 / SQR 05.2
Figure 19: Close mains terminal compartment
[1]
Connection housing
[2]
Screws for connection housing
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable gland (not included in delivery)
[7]
Blanking plug
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
Carefully fit socket carrier to avoid pinching the cables.
1.
Insert the socket carrier [5] into the connection housing [1] and fasten with
screws [4].
2.
Clean sealing faces of connection housing [1] and housing.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit connection housing [1] and fasten screws [2] evenly crosswise.
6.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU