Table 1. A1410 and V5140 Quad Host Card Power and Cooling Requirements
Units Per Rack
Power Requirements
Max No
Chassis
Blades
kVa
1
10
2.514
2
20
5.028
3
30
7.542
4
40
10.056
5
50
12.570
6
60
15.084
7
70
17.598
1
10
2.467
2
20
4.934
3
30
7.401
4
40
9.868
5
50
12.336
6
60
14.803
7
70
17.270
1
10
2.435
2
20
4.871
3
30
7.307
4
40
9.742
5
50
12.178
6
60
14.614
7
70
17.049
1
10
2.426
2
20
4.852
3
30
7.279
4
40
9.705
5
50
12.132
6
60
14.558
7
70
16.984
NOTE: Power and current figures are per chassis. Each chassis has two IEC power inputs. Each input supplies power to five blade slots
in the chassis. For power and current figures per input, divide these numbers by 2.
When specifying uninterruptible power supplies (UPS), use the peak current draw to
determine the appropriate UPS.
•
2 chassis—5.5 kVA UPS
•
3 chassis—8 kVA UPS
•
5 chassis—13 kVA UPS
A1410 Blade and V5120 Dual Host Card Connected to I9420 User Port
The following table details power and thermal values for the specified configurations of:
•
A3100 chassis
•
A1410 PC blade with the following:
–
Current Draw
Peak Power
Watts (W)
Min
2514.21
17.50
5028.43
35.00
7542.64
52.50
10056.86
70.00
12571.07
87.50
15085.28
105.00
17599.50
122.50
2467.38
14.72
4934.76
29.44
7402.13
44.16
9869.51
58.88
12336.89
73.60
14804.27
88.32
17271.65
103.04
2435.78
8.32
4871.57
16.64
7307.35
24.96
9743.13
33.28
12178.92
41.60
14614.70
49.92
17050.48
58.24
2426.49
7.34
4852.98
14.68
7279.47
22.02
9705.96
29.36
12132.45
36.70
14558.93
44.04
16985.42
51.38
2.4 GHz Intel Core2 Quad Processor Q6600
Current (A)
Generated Heat (BTU/Hr)
Max
Peak
Min
100 Volts
23.80
25.14
5972.70
47.60
50.28
11945.39
71.40
75.42
17918.09
95.20
100.56
23890.78
119.00
125.70
29863.48
142.80
150.84
35836.18
166.60
175.98
41808.87
120 Volts
18.81
20.56
6028.67
37.62
41.12
12057.34
56.43
61.68
18086.01
75.24
82.24
24114.68
94.05
102.80
30143.34
112.86
123.36
36172.01
131.67
143.92
42200.68
208 Volts
10.70
11.71
5906.35
21.40
23.42
11812.70
32.10
35.13
17719.04
42.80
46.84
23625.39
53.50
58.55
29531.74
64.20
70.26
35438.09
74.90
81.97
41344.44
240 Volts
9.40
10.11
6012.29
18.80
20.22
12024.57
28.20
30.33
18036.86
37.60
40.44
24049.15
47.00
50.55
30061.43
56.40
60.66
36073.72
65.80
70.77
42086.01
Chassis and Blade Power Requirements
Thermal
Min
Max
Peak
(Tons)
8122.87
8580.20
0.498
16245.73
17160.41
0.995
24368.60
25740.61
1.493
32491.47
34320.82
1.991
40614.33
42901.02
2.489
48737.20
51481.23
2.986
56860.07
60061.43
3.484
7703.75
8420.48
0.502
15407.51
16840.96
1.005
23111.26
25261.43
1.507
30815.02
33681.91
2.010
38518.77
42102.39
2.512
46222.53
50522.87
3.014
53926.28
58943.34
3.517
7595.90
8312.90
0.492
15191.81
16625.80
0.984
22787.71
24938.70
1.477
30383.62
33251.60
1.969
37979.52
41564.51
2.461
45575.43
49877.41
2.953
53171.33
58190.31
3.445
7699.66
8281.23
0.501
15399.32
16562.46
1.002
23098.98
24843.69
1.503
30798.63
33124.91
2.004
38498.29
41406.14
2.505
46197.95
49687.37
3.006
53897.61
57968.60
3.507
Required
Cooling
Max
(Tons)
0.677
1.354
2.031
2.708
3.385
4.061
4.738
0.642
1.284
1.926
2.568
3.210
3.852
4.494
0.633
1.266
1.899
2.532
3.165
3.798
4.431
0.642
1.283
1.925
2.567
3.208
3.850
4.491