Profinet Cables: Connect - AUMA SA-UW Operation Instructions Manual

Multi-turn actuators, for continuous underwater use with actuator controls ac 01.2 non-intrusive
Table of Contents

Advertisement

SA 07.2-UW
SA 16.2-UW / SAR 07.2-UW
AC 01.2 Non-Intrusive Profinet
5.3.5.

Profinet cables: connect

SAR 16.2-UW Control unit: electronic (MWG)
Figure 23: Profinet connection board with connection terminals
n 1
Profinet cable from previous device
n+1
Profinet cable to next device
(For line topology or redundant ring/MRP - Media Redundancy Protocol)
Profinet connection is made individually by means of a safe Ethernet-capable
insulation displacement connection. The colour coding of connection terminals are
matching the Ethernet cable according to Profinet (white/blue/yellow/orange).
Table 15: Connecting data
Connection capacity (solid wire)
Connection capacity (stranded)
1.
Remove cable sheathing and clamp shield under strain relief.
2.
Connect cables to connection terminals. For this, use a small screwdriver to lift
or push down the levers.
Table 16:
Connection terminal assignment
Signal
TD +
TD
RD +
RD
Option:
0.2 mm²
0.34 mm² / AWG 24
0.2 mm²
0.34 mm² / AWG 24
Function
Transmit Data +
Transmit Data
Receive Data +
Receive Data
Electrical connection
AWG 22
AWG 22
Colour of wire insulation
Yellow
Orange
White
Blue