Torque Switching: Set - AUMA SA-UW Operation Instructions Manual

Multi-turn actuators, for continuous underwater use with actuator controls ac 01.2 non-intrusive
Table of Contents

Advertisement

SA 07.2-UW
Commissioning (basic settings)
User login
Change settings
9.2.

Torque switching: set

Select main menu
Select parameter
46
SA 16.2-UW / SAR 07.2-UW
6.
Press
Edit.
Display indicates: ▶ Specialist (4)
7.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press
Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle ▶.
10. Use
Up ▲ Down ▼ to select new setting.
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
11. Confirm selection via
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Trip torque CLOSE
SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Save.
Esc.
to parameter, or
and enter ID M0088.