Corrective action

10.
Corrective action
10.1.

Faults during commissioning

Table 26:
Faults during operation/commissioning
Fault
In spite of correct setting of mechan-
ical limit switching, actuator operates
into the valve or actuator end position.
10.2.

Fault indications and warning indications

Table 27:
Faults and warnings via status indications in the display
Indication on display
S0001
S0005
Warnings
S0006
Not ready REMOTE
S0007
Fault
S0008
Out of specification
S0009
Function check
S0010
Maintenance required
S0011
Failure
52
SA 16.2-UW / SAR 07.2-UW
Description/cause
The overrun was not considered when setting the
limit switching.
The overrun is generated by the inertia of both the
actuator and the valve and the delay time of the
actuator controls.
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The display remains white.
Collective signals include further indications. They can be displayed via the
Details push button. The display remains white.
Description/cause
Instead of the valve position, a status text is dis-
played.
Collective signal 02:
Indicates the number of active warnings.
Collective signal 04:
Indicates the number of active signals.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
Collective signal 07:
Indication according to NAMUR recommendation
NE 107
Actuator is operated outside the normal operation
conditions.
Collective signal 08:
Indication according to NAMUR recommendation
NE 107
The actuator is being worked on; output signals are
temporarily invalid.
Collective signal 09:
Indication according to NAMUR recommendation
NE 107
Recommendation to perform maintenance.
Collective signal 10:
Indication according to NAMUR recommendation
NE 107
Actuator function failure, output signals are invalid
SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Remedy
Determine overrun: Overrun = travel covered
from switching off until complete standstill.
Set limit switching again considering the over-
run. (Turn actuator in the opposite direction
away from the end position by the amount of
overrun)
Remedy
For a description of the status texts, refer to Manual
(Operation and setting).
For indicated value > 0: Press push button
tails.
For details, refer to <Warnings and Out of specific-
ation> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Not ready REMOTE and
Function check> table.
For indicated value > 0: Press push button
to display a list of detailed indications.
For details, refer to <Faults and Failure> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Warnings and Out of specific-
ation> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Not ready REMOTE and
Function check> table.
For indicated value > 0: Press push button
to display a list of detailed indications.
For indicated value > 0: Press push button
to display a list of detailed indications.
For details, refer to <Faults and Failure> table.
De-
De-
Details
De-
De-
Details
Details