Commissioning (basic settings)
9.4.
Test run
9.4.1.
Direction of rotation: check
9.4.2.
Limit switching: check
50
SA 16.2-UW / SAR 07.2-UW
Only perform test run only once all settings previously described have been
performed.
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
1.
Move actuator to intermediate position or to sufficient distance from end position.
2.
Unfasten threaded plug [1] and seal [2].
3.
Switch on actuator via local controls push button in direction OPEN and observe
the direction of rotation at the hollow shaft [3]:
Switch off before reaching the end position.
The direction of rotation is correct if the actuator runs in direction CLOSE
and the hollow shaft turns clockwise.
Figure 55: Hollow shaft for clockwise closing
[1]
Threaded plug
[2]
Seal
[3]
Hollow shaft
4.
Insert seal [2] and tightly fasten threaded plug [1].
Information: To ensure perfect tightness, make sure that the seal is correctly
inserted and the threaded plug securely and tightly fastened.
1.
Set selector switch to position Local control (LOCAL).
2.
Operate actuator using push buttons OPEN, STOP, CLOSE.
The limit switching is set correctly if (default indication):
-
the yellow indication light/LED1 is illuminated in end position CLOSED
-
the green indication light/LED5 is illuminated in end position OPEN
-
the indication lights go out after travelling into opposite direction.
The limit switching is set incorrectly if:
-
the actuator comes to a standstill before reaching the end position
-
one of the red indication lights/LEDs is illuminated (torque fault)
-
the status indication S0007 in the display signals a fault.