SA 07.2-UW
Commissioning (basic settings)
9.3.

Limit switching: set

Select main menu
Select parameter
CLOSED or OPEN
User login
48
SA 16.2-UW / SAR 07.2-UW
Valve damage at valve/gearbox due to incorrect setting!
Allow for overrun when selecting limit seating.
Prior to setting the limit switching, set the torque switching to the lowest possible
value to avoid valve damage when approaching the end positions.
Customer settings M0041
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Set end pos.CLOSED?
4.
Up ▲ Down ▼:
Select via
▶ Set end pos.CLOSED? M0084
▶ Set end pos. OPEN? M0085
The black triangle ▶ indicates the current selection.
5.
Press
Ok.
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
-
Specialist (4) → continue with step 6
6.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
7.
Press Ok to confirm selected user.
Display indicates: Password 0***
8.
Enter password (→ enter password).
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
to parameter, or
and enter ID M0084.