Optimum start / stop control

Optimum start control max
Optimum stop control max

Raising the Reduced setpoint

Siemens Switzerland Ltd
HVAC Products
Line no.
HC1
HC2
HCP
790
1090
1390
791
1091
1391
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint is reached at the respective switching times.
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint minus 1/4 °C is reached at the respective switching times.
Optimum start / stop control is possible with or without room temperature sensor.
0
Xein
TRx
TRw
Xein
Switch-on time shifted forward in time
Xaus
Switch-off time shifted forward in time
ZSP
Time program
TRx
Actual value of the room temperature
TRw
Room temperature setpoint
Line no.
HC1
HC2
HCP
800
1100
1400
801
1101
1401
The function is used primarily in connection with heating systems with only little spare
capacity (e.g. low-energy houses). In such cases, the heating up time at low outside
temperatures would be too long. When the Reduced setpoint is raised, the rooms are
prevented from cooling down excessively, thus shortening the heating up time when
changing to the nominal setpoint.
TR
TRwA1
TRK
TRR
-15
User manual RVS61.843
6 The settings in detail
Operating line
Optimum start control max
Optimum stop control max
ZSP
Operating line
Reduced setp increase start
Reduced setp increase end
TRwA2
TRwA1 Reduced setpoint increase start
TRwA2 Reduced setpoint increase end
TRK
TRR
TAgem Composite outside temperature
-5
TAgem
Xaus
1/4 °C
Comfort setpoint
Reduced room temperature setpoint
CE1U2355en_02
23. November 2007
24
83/221