12.3.1. Total line length and maximum line length according to
DeviceNet specification
The bus line is a 4-core cable with additional shielding which must conform to the DeviceNet specification. The cable
transmits both information (data) and energy (power supply for low-power actuators and sensors).
The maximum total line length (sum of trunk lines and drop lines) of a network depends on the baud rate.
Baud rate
125 kbaud
250 kbaud
500 kbaud
*
1
According to DeviceNet specification. If a different cable type is used, lower maximum values apply.
*
2
For cable designation and details - see DeviceNet specification

12.3.2. Drop line length

Baud rate
125 kbaud
250 kbaud
500 kbaud
56
3 discrete feedback signal of the position measuring system (positions S1 - S3)
1 discrete feedback signal of the external initiator (S4)
1 analog position signal in mm
supply via DeviceNet string (11 ... 25 V DC)
Switch level high signal ≥ 5 V
Switch level low signal ≤ 1.5 V
3 solenoid valves
max. output 5 W, if all valves are switched (3 x type 6524 with 0.6 W each)
Maximum total line length*
Thick Cable*
2
500 m
250 m
100 m
Length of the drop lines
Maximum length
6 m for all baud rates
english
1
Thin Cable*
2
100 m for all baud rates
Maximum total length of all drop lines in the
network
156 m
78 m
39 m
DeviceNet Design