Design Aid - Pentair SUDMO IntelliTop 2.0 Operating Instructions Manual

Control head
Table of Contents

Advertisement

24 V DC - Design
10.3.

Design aid

Power consumption of the electronics:
P
=
0.7 W
El
Power consumption of a valve during activation (200 ms):
P
=
0.9 W
Valve-ON
Power consumption of a valve after reduction:
P
=
0.6 W
Valve
Power consumption of an optical position report:
P
=
1.0 W
LED
Also, if several control head valves were to be opened simultaneously, the switch signal will be sent stag-
gered to the valves. Only one 0.9 W valve will ever be recorded.
Calculation examples:
Example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):
P
=
P
Total
El
3.8 W
=
0.7 W
or
I
=
I
Total
El
160 mA =
30 mA
Example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):
P
=
P
Total
El
3.5 W
=
0.7 W
or
I
=
I
Total
El
147 mA =
30 mA
When using an external initiator, its power requirement should be added.
or
or
or
or
+ 1 x P
+ 2 x P
Valve-ON
+ 1 x 0.9 W
+ 2 x 0.6 W
+ 1 x I
+ 2 x I
Valve-ON
Valve
+ 1 x 38 mA
+ 2 x 25 mA
+ 3 x P
+ 1 x P
Valve
+ 3 x 0.6 W
+ 1 x 1.0 W
+ 3 x I
+ 1 x I
Valve
LED
+ 3 x 25 mA
+ 1 x 42 mA
I
=
30 mA at 24 V
El
I
=
38 mA at 24 V
Valve-ON
I
=
25 mA at 24 V
Valve
I
=
42 mA at 24 V
LED
+ 1 x P
Valve
LED
+ 1 x 1.0 W
+ 1 x I
LED
+ 1 x 42 mA
LED
english
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2307193

Table of Contents