Installation procedure:
Carefully insert the entire electronics module into the recess in the lower housing part.
Plug the electronics module carefully onto the contact pins for the position measuring system.
Refasten the electronics module with the Torx T10 screw (torque 0.4 Nm).
Reattach the electrical connections.
Check DIP switch positions (4-switch block for color coding, 8-switch block on DeviceNet electronics module
for address and Baud rate) and set the previously noted switch settings, if necessary.
If necessary, set AS interface address and jumper positions.
If required, make settings again, read out by PC software, using PC software.
Perform Teach-In procedure (see Chapter "16.1. Setting the position measuring system (Teach-In)").
Be sure to work carefully and cautiously, so that the electronics are not damaged.
Close the housing following the instructions in Chapter "8. Opening and Closing the Housing".
20.3.

Changing the valves

According to the design, 0 to 3 valve modules have been installed in the control head. The valves have been
designed with the flow restriction equipment for intake and exhaust air and must be installed as a valve module.
Note:
Disassemble/assemble the valves in upright position,
otherwise there is a risk that the non-return valve will fall out!
Fig. 36:
Valve module
Procedure:
Open the housing following the instructions in Chapter "8. Opening and Closing the Housing".
98
Valve module from above
english
Replacement of Components and Modules
Flow restriction screws
Torx screws (T10),
tightening torque:
1 Nm