Network Topology Of A Devicenet System; Configuring The Devicenet Address / Baud Rate - Pentair SUDMO IntelliTop 2.0 Operating Instructions Manual

Control head
Table of Contents

Advertisement

DeviceNet Design
12.9.

Network topology of a DeviceNet system

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct. The circuit pre-
vents the occurrence of interference caused by signals reflected onto the data lines.
The trunk line must be terminated at both ends with resistors of 120 Ω and 1/4 W power loss (see "Fig. 25").
"Fig. 25" illustrates a line with one trunk line and several drop lines. Trunk lines and drop lines consist of identical
material.
V +
V –
CAN_H
CAN_L
Terminating
resistor
120 Ω
¼ W
Fig. 25:
Network topology

12.10. Configuring the DeviceNet address / baud rate

8 DIP switches are available for configuration:
• DIP switches 1 to 6
for the DeviceNet address
• DIP switches 7 to 8
for the baud rate
Fig. 26:
Position of the DIP switches
Drop lines
DeviceNet cable,
max. 6 m long
T1
Subscriber 1 (node 1)
english
Trunk line
DeviceNet cable
Tn
Subscriber n (node n)
Terminating
resistor
120 Ω
¼ W
61