DeviceNet Design

12.
DEVICENET DESIGN
12.1.

Definition

• The DeviceNet is a field bus system which is based on the CAN protocol (Controller Area Network). It enables
actuators and sensors (slaves) to be networked with higher-level controllers (master).
• The control head in the DeviceNet is a slave device according to the Predefined Master/Slave Connection Set
stipulated in the DeviceNet specification. Polled I/O, Bit Strobed I/O and Change of State (COS) are supported
as I/O connection variants.
• With DeviceNet it is necessary to differentiate between cyclical or event-driven high-priority process messages
(I/O Messages) and acyclical low-priority management messages (Explicit Messages).
• The protocol process conforms to the DeviceNet specification Release April 2010.
12.2.

Electrical connection option

Fig. 22:
Connection concept DeviceNet
12.3.

DeviceNet specification

EDS file
Icons
Baud rate
Address
Process data
INTELLITOP2.EDS
INTELLITOP2.ICO
125 kbit/s, 250 kbit/s, 500 kbit/s (can be adjusted using DIP switches 7, 8);
factory setting: 125 kbit/s
(see Chapter "12.10.2. Setting the baud rate")
0 ... 63 (via DIP switches 1 ... 6 adjustable);
factory setting: 63
(see Chapter "12.10.1. Settings of the DeviceNet address")
2 static input assemblies
(Input: from IntelliTop 2.0 to DeviceNet master/scanner)
1 static output assembly
Cable gland with multi-pole connection
(M12 plug according to IEC 61076-2-101, 5-pole)
Connection left:
Voltage, signals
Connection right:
external initiator
english