State Of Bus Status Led "Network - Pentair SUDMO IntelliTop 2.0 Operating Instructions Manual

Control head
Table of Contents

Advertisement

DeviceNet Design

12.13.2. State of bus status LED "Network"

LED
Device state
Off
No voltage / not
online
Green
Online, connection
to master exists
Flashes
Online, without
green
connection to
master
Flashes
Connection
red
time-out
Red
Critical fault
Explanation
• Device is not supplied with voltage
• Device has still not ended Duplicate
MAC ID Test (test lasts approx. 2 s)
• Device cannot end Duplicate MAC ID
Test.
• Normal operating state with estab-
lished connection to the master
• Normal operating state without estab-
lished connection to the master
• One or more I/O connections are in
Time-Out state
• Another device with the same MAC
ID address is in the circuit
• No bus connection due to communi-
cation problems
Troubleshooting
• Connect other devices, if the
device is the only network
subscriber,
• Replace device
• Check baud rate
• Check bus connection
• New connection establishment
by master to ensure that the
I/O data is transmitted cyclically.
• Check baud rate
• Please check address as pos-
sible troubleshooting
• If required, replace device
english
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2307193