Maintenance, troubleshooting
19.2.

Safety positions

Safety positions after failure of the electrical or pneumatic auxiliary power:
Operating mode
up
down
up
down
up
down
By default the control head is equipped with solenoid valves which operate in NC mode,
the model for double-acting actuators is equipped with 1 solenoid valve NC and 1 solenoid valve NO.
If process valves with several switching positions (e.g. double seat valves) are connected, the safety positions of
the individual actuators can be viewed according to the same logic as for a classical single seat valve.
Safety positions after failure of the bus communication:
AS interface:
If the Watchdog is activated (default), behavior is the same as a failure of the auxiliary electrical power, i.e. all
solenoid valve outputs are set to "0".
DeviceNet:
See chapter "12.12.1. Configuration of the safety position of solenoid valves if bus error".
Process valve design
single-acting
Control function A (NC)
• air opening
• spring closing
single-acting
Control function B (NO)
• air closing
• spring opening
double-acting
Control function I
• air opening
• air closing
Safety positions
after failure of the auxiliary power
electrical
down
up
not defined for both
solenoid valves NC, but
_____________________
defined for
Solenoid valve 1 NC +
Solenoid valve 2 NO
english
pneumatic
down
up
not defined
93