How To Cut The Jumper On The Sync Cable For Double Doors; Double Door Installations - Assa Abloy Besam SW300 Installation And Service Manual

Swing door operator
Hide thumbs Also See for Besam SW300:
Table of Contents

Advertisement

12 Electrical connection
12.1.6

How to cut the jumper on the sync cable for double doors

Note! The connection/marking of the sync cable determines which of the operators is the MASTER
and SLAVE.
For an Astragal door;
• the Master door must open before the Slave door
• the Slave door must close before the Master door
Function
Opening
Synchronous
Synchronous
Asynchronous
Double egress
Astragal
Also see page 61.
12.1.7

Double door installations

There are four different types of double door installations:
• Rebated Has an overlapping master door, can be opened synchronously if it is not jamming
and must be closed asynchronously to avoid that the doors will jam or close in the wrong order.
• Jamming This door type needs to be opened and closed asynchronously to avoid that the
doors will jam with each other.
• Not jamming, not rebated This door type has doors that always can move independently of
each other and can be opened and closed synchronously.
• Double egress This door type has doors that opens in different directions which can be opened
and closed independently. This door type may have a different way of handling safety sensors
due to the difference in opening direction of the doors.
Also see page 61.
60
MASTER
SLAVE
Black
Door design
Closing
Astragal
Synchronous
Asynchronous
Asynchronous
Issue 2014-10-28
Red
Cut the jumper with color
Jamming
MASTER side
No
No
No cutting
Yes
No
Cut black
Yes
Yes
No cutting
Cut black
Jamming
SLAVE side
No cutting
No cutting
Cut red
Cut red
No jamming
1007913-EI-9.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Besam sw150

Table of Contents