12 Electrical connection
12.1
Control units
12.1.1
CU-300
Encoder
Motor
PUSH
Motor
PULL
Lock Kick
OK
ALARM
Green
Red
DIP-switch
Push & Go
1
PAG
=
Safety mat
2
MAT
=
Stop on stall
3
SOS
=
Activation delay
4
AD
=
Inverse installation
5
INV
=
Arm system setting
6
AS1
=
7
AS2
Arm system setting
=
Note! Connect the motor cable to either PUSH or PULL depending on arm system.
12.1.2
Arm system selection
Factory set arm configuration is PUSH, if other is required:
Select arm configuration on the DIP-switches according to the table below.
Type of arm system
PUSH
PULL
PULL-220 (narrow door)
Reveal 0 - 65 mm
Sliding PUSH
Note! After changing any system selection a new LEARN must be carried out.
56
Synchronizing of double doors
Key hold open time
DIP-switch
ON
5 s
1
2 3 4 5 6 7
1.5 s
30 s
HOT / KHOT
7 s
12 s
4 s
5 s
CLSP
12 s
2,5 s
OPSP
External LED indicator = LED
Issue 2014-10-28
Hold open time
Closing torque
Program selector
+24V DC
= Lock-out for OPD (–)
LOUT
= Overhead presence detection
OPD
IIMP
= Inner impulse
GND
= Ground
OPD
= Overhead presence detection (incl. 24 V,
LOUT and Safety Impulse)
= Learn button
LRN
Power assist
LED
Closing speed
Opening speed
ON=1 OFF=0
AS 1
AS 2
DIP 6
DIP 7
0
0
1
0
0
1
1
1
PUSH
PULL
PULL
Sliding
PUSH
1007913-EI-9.0