11.4. BALANCE REFRIGERANT OF THE 2-WAY, 3-WAY VALVE

(Lack of refrigerant in the refrigeration cycle)
Procedure:
1. Confirm that both the 2-way and 3-way valve are set to
the open position.
2. Connect the charge set to the 3-way valve's service
port.
· Leave the valve on the charge set closed.
· Connect the charge hose with the push-pin to the
service port.
3. Connect the charge set´s centre hose to refrigerant
reclaiming equipment.
· Purge the air from charge hose.
4. Open the valve (Low side) on the charge set and
discharge the refrigerant until the gauge indicates 0.05
MPa (0.5 kg/cm G) to 0.1 MPa (1 kg/cm G).
· If there is no air in the refrigeration cycle (the pressure
when the air conditioner is not running is higher than 0.1
MPa (1 kg/cm G), discharge the refrigerant until the
gauge indicates 0.05 MPa (0.5 kg/cm G) to 0.1 MPa (1
kg/cm G). If this is the case, it will not be necessary to
apply an evacuation.
· Discharge the refrigerant gradually; if it is discharged
too suddenly, the refrigeration
discharged.
5. Turn on refrigerant reclaiming equipment.
oil will also be
41
CS-VC70KE / CU-VC70KE / CS-VC90KE / CU-VC90KE / CS-VC120KE / CU-VC120KE