1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
Page 4
WARNING Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant connection inside a building or dwelling or room must be made by brazing or welding. Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a building or dwelling or room.
Page 5
CAUTION Do not touch the sharp aluminium fin, sharp parts may cause injury. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture. Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
2. Precaution for Using R32 Refrigerant The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
Page 7
CAUTION 2-5. No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
Page 8
CAUTION Leak detection methods Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
Page 9
CAUTION Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
3. Specification Model CS-Z20TKR CS-Z25TKR Indoor POS (EAN) 5025232871452 5025232871469 Model CU-Z20TKR CU-Z25TKR Outdoor POS (EAN) 5025232871643 5025232871650 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid.
Page 11
Model CS-Z20TKR CS-Z25TKR Indoor POS (EAN) 5025232871452 5025232871469 Model CU-Z20TKR CU-Z25TKR Outdoor POS (EAN) 5025232871643 5025232871650 Type Cross-flow Fan Cross-flow Fan Material ASG20K1 ASG20K1 Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles) Input Power 44.9 44.9 Output Power...
Page 12
Model CS-Z20TKR CS-Z25TKR Indoor POS (EAN) 5025232871452 5025232871469 Model CU-Z20TKR CU-Z25TKR Outdoor POS (EAN) 5025232871643 5025232871650 Height mm (inch) 295 (11-5/8) / 542 (21-11/32) 295 (11-5/8) / 542 (21-11/32) (I/D / O/D) Width Unit mm (inch) 919 (36-3/16) / 780 (30-23/32)
Page 13
Model CS-Z35TKR CS-Z42TKR Indoor POS (EAN) 5025232871476 5025232871483 Model CU-Z35TKR CU-Z42TKR Outdoor POS (EAN) 5025232871667 5025232871674 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. 0.90 3.50 4.00 0.90...
Page 14
Model CS-Z35TKR CS-Z42TKR Indoor POS (EAN) 5025232871476 5025232871483 Model CU-Z35TKR CU-Z42TKR Outdoor POS (EAN) 5025232871667 5025232871674 Type Cross-flow Fan Cross-flow Fan Material ASG20K1 ASG20K1 Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles) Input Power 44.9 44.9 Output Power Cool Heat Cool...
Page 16
Model CS-Z50TKR CS-Z60TKR Indoor POS (EAN) 5025232871490 5025232871506 Model CU-Z50TKR CU-Z60TKR Outdoor POS (EAN) 5025232871681 5025232871698 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. 0.90 5.00 6.00 0.90...
Page 17
Model CS-Z50TKR CS-Z60TKR Indoor POS (EAN) 5025232871490 5025232871506 Model CU-Z50TKR CU-Z60TKR Outdoor POS (EAN) 5025232871681 5025232871698 Type Cross-flow Fan Cross-flow Fan Material ASG33 ASG33 Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles) Input Power Output Power Cool Heat Cool Heat Cool...
Page 19
Model CS-Z71TKR CS-Z80TKR Indoor POS (EAN) 5025232871513 5025232871520 Model CU-Z71TKR CU-Z80TKR Outdoor POS (EAN) 5025232871704 5025232871711 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. 1.70 7.10 8.10 1.70...
Page 20
Model CS-Z71TKR CS-Z80TKR Indoor POS (EAN) 5025232871513 5025232871520 Model CU-Z71TKR CU-Z80TKR Outdoor POS (EAN) 5025232871704 5025232871711 Type Cross-flow Fan Cross-flow Fan Material ASG33 ASG33 Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles) Input Power Output Power Cool Heat Cool Heat Cool...
4. Features Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control Air Purifying System with nanoe-G Deactivates and removes bacterial, viruses and mould Environment Protection Non-ozone depletion substances refrigerant (R32) ...
5. Location of Controls and Components Indoor Unit Front panel Aluminium fin Auto OFF/ON button Use when remote control is misplaced or a malfunction occurs. Horizontal airflow direction louver Do not adjust by hand. Human activity sensor Sunlight Sensor and Vertical airflow direction louver Remote Control Receiver Do not adjust by hand.
6. Dimensions Indoor Unit 6.1.1 CS-Z20TKR CS-Z25TKR CS-Z35TKR CS-Z42TKR <Top View> <Side View> <Front View> <Side View> Air intake direction 2 ±0.5 2 ±0.5 Left piping Air outlet Right piping hole direction hole <Remote Control> <Bottom View> Gas side <Rear View>...
Page 25
6.1.2 CS-Z50TKR CS-Z60TKR CS-Z71TKR CS-Z80TKR <Top View> <Side View> <Front View> <Side View> Air intake 1120 direction Left piping Air outlet Right piping hole direction hole <Remote Control> <Bottom View> Liquid side <Rear View> Gas side (41-61) <Remote Control Holder> Relative position between the indoor unit and the installation plate <Front View>...
Outdoor Unit 6.2.1 CU-Z20TKR CU-Z25TKR CU-Z35TKR <Top View> Space necessary for installation 67.6 104.7 104.9 60.5 10 cm 10 cm 100 cm Anchor Bolt Pitch 320 x 570 2-way valve at Liquid side <Side View> (High Pressure) <Side View> <Front View> 3-way valve at Gas side (Low Pressure)
Page 27
6.2.3 CU-Z80TKR <Top View> Space necessary for installation 27.5 100mm 100mm 1000mm Anchor Bolt Pitch 360.5 × 613 <Side View> <Side View> <Front View> 3-way valve at Gas side (Low Pressure) 2-way valve at Liquid side Unit : mm (High Pressure) <Chassis>...
9. Wiring Connection Diagram Indoor Unit HAJEM-A CN-CNT (WHT) (WHT) AUTO SW TERMINAL AC306 (SW01) BOARD FUSE301 (BLK) T3.15A L250V OUTDOOR AC303 (WHT) UNIT UP DOWN NOISE FILTER LOUVER MOTOR AC304 (RED) CIRCUIT (OUTER) TEMP. FUSE LEFT RIGHT 102°C (3A) LOUVER MOTOR G301 (GRN) UP DOWN...
Outdoor Unit 9.2.1 CU-Z20TKR CU-Z25TKR CU-Z35TKR YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL...
Page 34
9.2.2 CU-Z42TKR CU-Z50TKR CU-Z60TKR CU-Z71TKR YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL...
Page 35
9.2.3 CU-Z80TKR REACTOR YELLOW (YLW) TO INDOOR UNIT SINGLE PHASE POWER SUPPLY REMARKS : BLUE : BROWN BLUE TERMINAL TERMINAL : ORANGE : BLACK (BLU) (RED) BOARD BOARD : YELLOW : WHITE CONNECTOR (TRADEMARK) : GRAY : RED WHITE YLW/GRN COMP.
12. Installation Instruction 12.1 Select the Best Location (5/4) = (m / (2.5 × (LFL) × h 12.1.1 Indoor Unit = Required minimum room area, in m Do not install the unit in excessive oil fume area = Refrigerant charge amount in appliance, in kg such as kitchen, workshop and etc.
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall Wall More than 1 More than 1 More Indoor unit 2 screw than 2 Installation 266 mm plate 1 266 mm...
Page 49
12.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping Wall Insert the piping sleeve to the hole. Indoor Outdoor Fix the bushing to the sleeve. Cut the sleeve until it extrudes about 15 mm 15 mm from the wall.
Page 50
12.2.3 Indoor Unit Installation ● Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. ● Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
Page 51
Replace the drain hose Rear view for left piping installation Connection cable Piping Drain hose More than 950 mm (3/4 ~ 1.75HP) or Connection cable Drain hose more than 1150 mm Drain cap Adjust the piping slightly (2.0 ~ 3.0HP) Drain hose downwards.
Page 52
Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the diagram below. Terminal Board Tape Earth Wire longer than others AC wires Connection cable for safety Terminals on the indoor unit Indoor & outdoor reason Connection cable Colour of wires...
12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 54
12.3.3 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging.
Page 55
12.3.4 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Applicable for : CU-Z20***, CU-Z25***, CU-Z35***, Cable connection to the power supply through CU-Z42***, CU-Z50***, CU-Z60***, Isolating Devices (Disconnecting means). CU-Z71*** Connect approved type polychloroprene sheathed power supply cord 3 x 1.5...
Page 56
Terminal Board Earth wire longer than others AC wires for safety reason Holder DRED Indoor & Power (Demand outdoor response supply Connection enabling cord Applicable for : CU-Z80*** cable devices) Remote Isolating Devices Indoor unit Agent WARNING This equipment must be properly earthed. Note: ...
Page 57
12.3.7 Evaluation of the Performance Operate the unit at cooling/heating operation mode for fifteen minutes or more. Measure the temperature of the intake and discharge air. Ensure the difference between the intake temperature and the discharge is more than 8°C during Cooling operation or more than 14°C during Heating operation.
12.4 Wired Remote Controller Installation Manual 12.4.1 Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation. Electrical work must be installed by a licensed electrician. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Page 59
12.4.2 Attached Accessories Name Diagram Remark Remote controller Remote controller cable Length (9.9 m) Screw Installing the remote controller to an outlet box (M4 machine pitched – 30 mm) (embedded cable) Screw Installing the remote controller to the wall (M4 self tapping – 14 mm) (exposed cable) Remote controller cable holder Holder for remote controller cable at control board...
Page 60
Embed an outlet box (JIS C 8336) into the wall. Outlet box may be purchased separately. Medium-sized square outlet box (obtain locally) Part No. DS3744 (Panasonic Co., Ltd.) or equivalent. Secure the remote controller lower case to the outlet box with the two accessory screws 3. Make sure that the lower case is flat against the wall at this time, with no bending.
Page 61
B. If Remote Controller Cable is Exposed Install the remote controller lower case to the wall with the two accessory screws 4. Fasten the screws properly until screw head is lower than the rib and reach the base of remote controller lower case to ensure they do not damage the PCB inside the remote controller 1.
Page 62
12.4.5 Connecting the Remote Controller Cable to Indoor Unit CAUTION Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause the electrical shock. Open front grille complete Front grille complete (Please refer HOW TO TAKE OUT FRONT GRILLE).
13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
Page 64
2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
Page 66
3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
Page 67
7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
Page 68
11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
Page 72
13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
Page 73
13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
Page 74
13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
Page 76
2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
Page 77
13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
Page 78
13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
Page 79
13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
Page 80
(Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
Page 82
1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
14. Operation and Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 84
14.1.5 Automatic Operation This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature. During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
14.2 Indoor Fan Motor Operation 14.2.1 Basic Rotation Speed (rpm) A. Basic Rotation Speed (rpm) i. Manual Fan Speed [Cooling, Dry, Fan] Fan motor’s number of rotation is determined according to remote control setting. Remote control ○ ○ ○ ○...
14.4 Airflow Direction There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes). Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Page 87
Side View (Inner Vane) Reference point 128º (Z20/25/35/42TK) 148º (Z50/60/71/80TK) Step 1 Stopper Step 2 Step 3 Closed Position Step 4 Step 5 Side View (Outer Vane) Closed Stopper Position 156º (Z20/25/35/42TK) 101º (Z50/60/71/80TK) Reference point Step 1 Step 2 Step 3 Step 4 Step 5...
0° Top View A: swing 43°C 40°C B: fix front Indoor Heat Exchanger Temperature Figure 1 Figure 2 Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the positions of the vane are as Figure 2 above. Pattern Airflow Direction Patterns at Remote Control...
Mild Dry button is pressed. ECONAVI button is pressed. iAUTO-X button is pressed. When quiet operation is stopped, operation is shifted to normal operation with previous setting. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. ...
14.10 Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.
Page 91
Indicator When nanoe-G starts, nanoe-G indicator ON. Remote Control Receiving Sound Normal Operation nanoe-G Operation : Beep nanoe-G Operation Normal Operation : Beep Stop nanoe-G individual Operation : Beep nanoe-G individual Operation Stop : Long Beep ...
Troubleshooting method Press nanoe-G button or OFF/ON button to stop the operation and check the nanoe-G connector at PCB. After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks. The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops. Error reset method ...
Enable or disable selection iCOMFiAUTO-XHEATCOOLDRYFAN SHOWER DIRECT Remote control normal mode Press SW continuously for 5s Press SW’s to choose function 7 Control Disable Transmit check code “Enable or Disable” code Control Enable Power failure During in-filter operation, if power failure occurs, after power resumes in-filter deactivation operation will not resume.
Page 94
14.14.1 Human Activity Sensor Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide comfort environment while maintain the energy saving level.
Page 95
14.14.1.1 Signal Detection 120° Human Activity sensor will turns on according to infrared sensors signal detection. Signal detection Possible detected human position area Sensor 1 Sensor 2 A & B B & C A & C A, B & C –...
Page 96
14.14.1.7 Setting Position Judgment According to installation position when there is only one activity area detected, the horizontal airflow direction louver position is fixed according to chart below: Horizontal airflow direction louver position Target area Left installation Center installation Right installation ...
Page 97
14.14.1.9 Rhythmic Temperature Wave Operation To further maximize the energy saving during ECONAVI operates at low activity level. Start condition The unit is operates in Cool or Dry mode under ECONAVI operation, and Human activity sensor detects low activity level continuously for 60 minutes, and ...
Page 98
14.14.1.10 ECONAVI Demo Mode To enable ECO DEMO mode, during unit is OFF (power standby): Remote control normal mode Press continously for 5s iAUTO-X Transmit ECO demo code and after 30 seconds return to normal mode. TEMP TEMP iAUTO-X Transmit sunlight sensor check code and after 30 seconds return to normal mode.
Page 99
14.14.1.12 Human Activity Sensor Check Mode To enable Human Activity sensor abnormality check mode, during ECONAVI operation ON: Remote control normal mode Press continously for 5s iAUTO-X Transmit ECO demo code and after 30 seconds return to normal mode. TEMP TEMP iAUTO-X...
Page 100
14.14.2.2 Judge Sunlight Intensity Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight intensity database. The sunlight sensor sensitivity could be adjusted: Remote control normal mode Press & release TEMP Press to choose No.2 Sensitivity Level 1: Less sensitive to sunlight intensity iAUTO-X...
Page 101
14.14.2.5 Sunlight Sensor Check Mode To enable sunlight sensor check mode, during unit is OFF (power standby): Remote control normal mode Press continously for 5s iAUTO-X Transmit ECO demo code and after 30 seconds return to normal mode. TEMP TEMP iAUTO-X Transmit sunlight sensor check code...
14.15 HA Terminal (HAJEM-A) Enable digital connection from indoor unit to external devices. Control items: Start/stop input. Start/stop signal output. 200~300msec ON/OFF input (Pin 1-2) Monitor output (Pin 1-2) Unit condition Condition 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal. (1 pulse signal: shortage status 200~300msec) 3-4 (Static output): 5V output during the unit ON.
14.17 Pump down Operation by CN-S A convenience method to activate pump down operation. Control start condition: During power standby condition, short CN-S continuously between 1 second and 10 seconds. Control stop condition: 480 seconds after pump down operation starts. CN-S is shorted again during pump down operation.
15. Protection Control 15.1 Protection Control for All Operations 15.1.1 Restart Control (Time Delay Safety Control) The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
Page 105
15.1.4 Compressor Overheating Prevention Control Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
15.2 Protection Control for Cooling & Soft Dry Operation 15.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
15.2.6 Odor Cut Control To reduce the odor released from the unit. Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable. Control content ...
Page 108
15.3.3 Overload Protection Control The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below. If the heat exchanger temperature exceeds 60°C, compressor will stop. 60°C Frequency Reduce 55°C 52°C Frequency Limited 49°C 46°C Free Indoor Heat...
16. Servicing Mode 16.1 Auto OFF/ON Button Auto OFF/ON Auto OFF/ON Auto OFF/ON Button pressed Button pressed Button pressed 5 sec 5 sec Auto Operation Test Run Operation Stop Test Run Operation Stop (Forced Cooling Operation) (Forced Heating Operation) Beep Beep x 2 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed.
REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
Page 111
16.2.6 Special Setting mode LCD display area: Special setting display area (highlighted in color) Function Options (If any) Cannot enter this special setting mode under the following conditions: 1 Operation ON. 2 Under [Real/ON/OFF] time setting mode. To enter zone 1 area: Normal display Enter Zone1 mode...
Page 112
Function & Options list: Note: The functions described in the table may not be applicable to the model and may subject to change without further notice. Function Options Remark Name Remote control number selection A, B, C, D Solar radiation sensitivity level adjustment 1, 2, 3, 4, 5 [iAUTO-X/iAUTO/iCOMF, Cool &...
17. Troubleshooting Guide 17.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas pressure Outlet air temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
Page 114
17.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
17.2 Breakdown Self Diagnosis Function 17.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LED abnormality code signal to the main unit.
17.3 Error Code Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
Page 117
Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality Expansion valve and lead wire and connector ...
17.4 Self-diagnosis Method 17.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB.
Page 119
17.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. ...
Page 120
17.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 121
17.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor.
Page 122
17.4.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused Lack of gas. Broken CT (current transformer).
Page 123
17.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Malfunction Caused ...
Page 124
17.4.7 H23 (Indoor Pipe Temperature Sensor 1 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 1 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 125
17.4.8 H24 (Indoor Pipe Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 2 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 126
17.4.9 H25 (nanoe-G Air Purifying System Abnormal) Malfunction Decision Conditions During standby of cooling and heating operation, nanoe-G breakdown occurs and air conditioner stops operation. Malfunction Caused Faulty indoor main PCB. Faulty indoor nanoe-G power module. Troubleshooting When abnormality indication starts again For safety reason and to prevent component breakdown, always switch off the power...
Page 127
17.4.10 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 128
17.4.11 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 129
17.4.12 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 130
17.4.13 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective.
Page 131
17.4.14 H59 (Human Activity Sensor Abnormality) Malfunction Decision Conditions Feedback signal of human activity sensor. Malfunction Caused Feedback signal is fixed at 0 VDC or 5 VDC continuously for 25 seconds during ECONAVI or AUTO COMFORT operation. Feedback signal is detected during ECONAVI or AUTO COMFORT off.
Page 132
17.4.15 H70 (Light Sensor Abnormality) Malfunction Decision Conditions Feedback signal of light sensor. Malfunction Caused Feedback value is 0 VDC continuously. Troubleshooting When abnormality indication starts again. For safety reason and to prevent Check the connector connection: component breakdown, always switch Turn off the power.
Page 133
17.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) 17.4.16.1 CU-Z20/25/35/42/50/60/71TKR Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. ...
Page 134
17.4.16.2 CU-Z80TKR Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor.
Page 135
17.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
Page 136
17.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C). Malfunction Caused ...
Page 137
17.4.19 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
Page 138
17.4.20 F90 (Power Factor Correction Protection) Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification. Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
Page 139
17.4.21 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused Lack of gas. 3-way valve close. Troubleshooting When F91 indication happens. For safety reason and to prevent component breakdown, always switch off the power before remove and...
Page 140
17.4.22 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect. Faulty Outdoor PCB. Faulty compressor. Troubleshooting When F93 indication happens.
Page 141
17.4.23 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
Page 142
17.4.24 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
Page 143
17.4.25 F97 (Compress Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (103°C) is detected by the compressor tank temperature sensor. Malfunction Caused Faulty compressor tank temperature sensor 2/3 way valve closed ...
Page 144
17.4.26 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Page 145
17.4.27 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused DC current peak due to compressor failure. ...
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1 CS-Z20TKR CS-Z25TKR CS-Z35TKR CS-Z42TKR 18.1.1...
Page 147
18.1.1.3 To Remove Electronic Controller 3 Hooks (Top, left and right hand side) Remove control board cover by releasing 3 hooks. Figure 2 Detach the terminal wire (Black), terminal wire (Red) and earth wire screws. Pull out the 10. Detach all connectors as labelled from the electronic electronic controller.
Page 148
18.1.1.4 To Remove Discharge Grille Remove the screw and pull out the HVU unit. HVU unit Figure 5 12. Pull out and remove the drain hose from the discharge grille. 13. Then pull the discharge grille downward gently to dismantle it. Figure 6 18.1.1.5 To Remove Control Board...
Page 149
18.1.1.6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 8 17. Remove the bearing by pulling it gently. 16. Remove the screw from the evaporator. Figure 9...
Page 150
Evaporator 18. Push the holdfast to the left and lift up the evaporator. 20. Fan motor can be removed after Cross flow fan the removal of the cross flow fan. Reminder: To reinstall the fan motor, adjust the fan motor connector to 90° towards you before fixing control board.
Page 151
18.1.1.7 To Assemble the Front Grille Receiver PCB CAUTION Do not directly fix the front grille complete, to avoid hitting the Receiver PCB. Figure 12 Gently assemble the right side of the front grille first then fix the left side. Figure 13...
Page 152
18.1.1.8 To Assemble the Intake Grille Hook Intake Grille Align the intake grille hooks into the slot. Hook Place in the hook to the slot. Then slightly bend the intake grille and push in the hooks into the slot. Figure 14...
WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.2 CS-Z50TKR CS-Z60TKR CS-Z71TKR CS-Z80TKR 18.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures...
Page 154
18.2.1.3 To Remove Electronic Controller 3 Hooks (left and right hand side) Remove control board cover by releasing 4 hooks. Figure 2 Detach the terminal wire (Black), terminal wire (Red) and earth wire screws. Pull out the 10. Detach all connectors as labelled from the electronic electronic controller.
Page 155
18.2.1.4 To Remove Discharge Grille Remove the screw and pull out the HVU unit. HVU unit Figure 5 12. Pull out and remove the drain hose from the discharge grille. 13. Then pull the discharge grille downward gently to dismantle it. Figure 6 18.2.1.5 To Remove Control Board...
Page 156
18.2.1.6 To Remove Cross Flow Fan and Indoor Fan Motor 15. Remove the screw that holding the cross flow fan and fan motor axis. Figure 8 17. Remove the bearing by pulling it gently. 16. Remove the screw from the evaporator. Figure 9...
Page 157
Evaporator 18. Push the holdfast to the left and lift up the evaporator. 20. Fan motor can be removed after Cross flow fan the removal of the cross flow fan. Reminder: To reinstall the fan motor, adjust the fan motor connector to 90° towards you before fixing control board.
Page 158
18.2.1.7 To Assemble the Front Grille Receiver PCB CAUTION Do not directly fix the front grille complete, to avoid hitting the Receiver PCB. Figure 12 Gently assemble the right side of the front grille first then fix the left side. Figure 13...
Page 159
18.2.1.8 To Assemble the Intake Grille Hook Intake Grille Align the intake grille hooks into the slot. Hook Place in the hook to the slot. Then slightly bend the intake grille and push in the hooks into the slot. Figure 14...
18.3 Outdoor Electronic Controller Removal Procedure 18.3.1 CU-Z20TKR CU-Z25TKR CU-Z35TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
Page 161
18.3.2 CU-Z42TKR CU-Z50TKR CU-Z60TKR CU-Z71TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws...
Page 162
18.3.3 CU-Z80TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 4 screws of the Top Panel. Remove the Control Board. Fig. 4 Remove the 8 screws of the Electronic Controller. Fig. 1 Remove the 10 screws of the Front Panel. Fig.
21. Exploded View and Replacement Parts List 21.1 Indoor Unit 21.1.1 CS-Z20TKR CS-Z25TKR CS-Z35TKR CS-Z42TKR CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 188
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z20TKR CS-Z25TKR REMARK CHASSIS COMPLETE ACXD50C00200 ← FAN MOTOR L6CBYYYL0171 ← CROSS-FLOW FAN COMPLETE CWH02C1076 ← BEARING ASSY CWH64K1006 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C10820 ACXB30C11150 FLARE NUT (LIQUID) CWT251048 ←...
Page 189
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z20TKR CS-Z25TKR REMARK INSTALLATION PLATE CWH361147 ← BAG COMPLETE - INSTALLATION SCREW CWH82C1705 ← CONTROL BOARD TOP COVER ACXH13-00190 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
Page 190
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z35TKR CS-Z42TKR REMARK CHASSIS COMPLETE ACXD50C00200 ← FAN MOTOR L6CBYYYL0171 ← CROSS-FLOW FAN COMPLETE CWH02C1076 ← BEARING ASSY CWH64K1006 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C01160 ACXB30C01170 FLARE NUT (LIQUID) CWT251048 ←...
Page 191
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z35TKR CS-Z42TKR REMARK INSTALLATION PLATE CWH361147 ← BAG COMPLETE - INSTALLATION SCREW CWH82C1705 ← CONTROL BOARD TOP COVER ACXH13-00190 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 192
21.1.2 CS-Z50TKR CS-Z60TKR CS-Z71TKR CS-Z80TKR CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 193
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z50TKR CS-Z60TKR REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0193 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C10710 ← FLARE NUT (LIQUID) CWT251030 ←...
Page 194
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z50TKR CS-Z60TKR REMARK INSTALLATION PLATE ACXH36-00080 ← BAG COMPLETE - INSTALLATION SCREW CWH82C1705 ← CONTROL BOARD TOP COVER ACXH13-00430 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 195
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z71TKR CS-Z80TKR REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0194 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C10720 ACXB30C01700 FLARE NUT (LIQUID) CWT251030 ←...
Page 196
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z71TKR CS-Z80TKR REMARK INSTALLATION PLATE ACXH36-00080 ← BAG COMPLETE - INSTALLATION SCREW CWH82C1705 ← CONTROL BOARD TOP COVER ACXH13-00430 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
21.2 Outdoor Unit 21.2.1 CU-Z20TKR CU-Z25TKR CU-Z35TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 198
REF. SAFETY PART NAME & DESCRIPTION QTY. CU-Z20TKR CU-Z25TKR CU-Z35TKR REMARK CHASSIS ASSY CWD52K1399 ← ← SOUND PROOF MATERIAL (COMP CWG302314 ← ← TOP) FAN MOTOR BRACKET CWD541157 ← ← SCREW - FAN MOTOR BRACKET CWH551217 ← ← FAN MOTOR L6CAYYYL0064 ←...
Page 199
REF. SAFETY PART NAME & DESCRIPTION QTY. CU-Z20TKR CU-Z25TKR CU-Z35TKR REMARK PANASONIC BADGE CWE373439 ← ← INVERTER BADGE CWE373441 ← ← OPERATING INSTRUCTION ACXF55-11420 ← ← INSTALLATION INSTRUCTION ACXF60-16890 ← ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
Page 200
21.2.2 CU-Z42TKR CU-Z50TKR CU-Z60TKR CU-Z71TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 201
CONTROL BOARD COVER - COMPLETE ACXH13C00170 ← CONTROL BOARD COVER CWH131470 ← TUBE ASS'Y (CAPPILARY TUBE) ACXT00C20450 DISCHARGE MUFFLER CWB121010 PANASONIC BADGE CWE373439 ← INVERTER BADGE CWE373441 ← SOUND PROOF MATERIAL (500 mm x 375 mm) CWG302636 ← SOUND PROOF MATERIAL (COMP TOP) CWG302630 ←...
Page 202
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z42TKR CU-Z50TKR REMARK BAG - COMPLETE CWG87C900 ← FLEXIBLE PIPE (L-TUBE) CWH5850080 ← PACKING CWB81012 ← OPERATING INSTRUCTION ACXF55-11420 ← INSTALLATION INSTRUCTION ACXF60-16890 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 204
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z60TKR CU-Z71TKR REMARK BAG - COMPLETE CWG87C900 ← FLEXIBLE PIPE (L-TUBE) CWH5850080 ← PACKING CWB81012 ← OPERATING INSTRUCTION ACXF55-11420 ← INSTALLATION INSTRUCTION ACXF60-16890 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 205
21.2.3 CU-Z80TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service part.
Page 206
CABINET SIDE PLATE CWE041317A CABINET FRONT PLATE CO. CWE06K1063 CABINET TOP PLATE CWE031083A CONTROL BOARD COVER CO. CWH13C1185 WIRE NET CWD041128A ACCESSORY CO. (DRAIN ELBOW) CWG87C900 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING - L.TUBE CWB81012 PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441...
Page 207
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z80TKR REMARK OPERATING INSTRUCTION ACXF55-11420 INSTALLATION INSTRUCTION ACXF60-16890 PLATE - C. B. COVER TERMINAL CWH131332 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock. Printed in Malaysia YY0717-0...