FusionCol8000-E240 Modular Indirect Evaporative Cooling System User Manual Issue Date 2021-01-30 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
Page 23
The condenser adopts the flow design with a low wind resistance. Exhaust ● A Huawei-developed high-speed fan is used, which features large air volume, high static pressure, high reliability, and a long service life. ● The fan is separated from the drive. The fan efficiency is improved by more than 8% compared with a common EC fan.
Page 24
● The variable-frequency drive power supply mode is used to implement soft startup of the water pump, improving the pump reliability. ● A Huawei-developed high-speed fan is used, which supply features large air volume, high static pressure, high reliability, and a long service life.
Page 26
The condenser adopts the flow design with a low wind resistance. Exhaust ● A Huawei-developed high-speed fan is used, which features large air volume, high static pressure, high reliability, and a long service life. ● The fan is separated from the drive. The fan efficiency is improved by more than 8% compared with a common EC fan.
Page 27
Supply fan ● A Huawei-developed high-speed fan is used, which features large air volume, high static pressure, high reliability, and a long service life. ● The fan is separated from the drive. The fan efficiency is improved by more than 8% compared with a common EC fan.
Page 29
Remote Users can monitor and manage one or more devices using the management remote management function provided by Huawei. Storage ● A large number of fault alarm records can be stored. Alarms can be managed by severity. A maximum of 500 historical alarms can be stored for each severity.
Page 32
Service Expert app. Obtain the initial startup password during deployment. View or obtain running information about the smart cooling product during inspection. Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module. To ensure security, remove the WiFi module immediately after use.
Page 34
(RCCB) that is insensitive to single-phase DC pulsation and transient impulse current. Note: If the requirements are not met, contact Huawei technical support for an optimized solution. Issue 01 (2021-01-30)
Do not stack whole FusionCol8000-E systems together. ● Check the FusionCol8000-E periodically. 3.2 Materials Materials to be prepared include materials delivered by Huawei, to be purchased by the customer, and to be prepared onsite. Table 3-1 Material description Item Description...
Figure 3-9 is missing. If any bonnet is missing, contact Huawei technical support. If no bonnet is missing, remove the valve bonnets, and press the valve plugs using the valve bonnets in turn. If gas flows out, the system is normal. If no gas flows out, contact Huawei technical support.
● Connect the COM/FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host. ● Customers can purchase Huawei's ECC and NetEco for the monitoring system. Figure 3-20 Connecting communications cables ----End 3.4.3.3 CAN Teamwork + FE Monitoring...
● Connect the COM/FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host. ● Customers can purchase Huawei's ECC and NetEco for the monitoring system. Issue 01 (2021-01-30)
Do not stack whole FusionCol8000-E systems together. ● Check the FusionCol8000-E periodically. 4.2 Materials Materials to be prepared include materials delivered by Huawei, to be purchased by the customer, and to be prepared onsite. Table 4-1 Material description Item Description...
Figure 4-8 is missing. If any bonnet is missing, contact Huawei technical support. If no bonnet is missing, remove the valve bonnets, and press the valve plugs using the valve bonnets in turn. If gas flows out, the system is normal. If no gas flows out, contact Huawei technical support.
● Connect the COM/FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host. ● Customers can purchase Huawei's ECC and NetEco for the monitoring system. Figure 4-21 Connecting communications cables ----End 4.4.3.3 CAN Teamwork + FE Monitoring...
● Connect the COM/FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host. ● Customers can purchase Huawei's ECC and NetEco for the monitoring system. Issue 01 (2021-01-30)
Page 102
Confirm with Huawei technical support before modifying parameters which cannot be modified by user operator. Otherwise, Huawei will not be liable for any consequences of the modification performed by the user. ● Only certified professionals are allowed to modify advanced parameters of smart cooling products.
No, no password is required for startup or shutdown verification. Prerequisites Download the Service Expert app from HUAWEI AppGallery. The app can only run on Android currently. You must apply for the permission to use the app after downloading it.
During operation, comply with the safety symbols on the device and all the safety instructions in this document. The safety precautions provided in this document do not cover all the safety precautions. Huawei shall not be liable for any consequence caused by the violation of the safety operation regulations and design, production, and usage standards.
FusionCol8000-E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance ● Exercise caution during professional maintenance. For details, contact Huawei technical support. ● When replacing a component, do not lean the component against the cabinet. 8.2 Routine Maintenance Smart Cooling Product Running ●...
----End 8.4.13.2 R410A Refrigerant CA UTION Do not use refrigerant of poor quality. Huawei will not be liable for any device damage caused by using refrigerant of poor quality. Verify that the refrigerant is authentic in the following ways: Dial the refrigerant vendor's hotline to confirm the refrigerant authenticity.
During the commissioning of the smart cooling product, ensure that no combustion-supporting materials (such as air or additive) enter the smart cooling product system. Huawei is not liable for any risks and losses caused due to violation. 8.4.13.4.1 Refrigerant Charge Amount Requirements...
8 System Maintenance NO TICE If the R410A refrigerant is provided by Huawei, put the refrigerant cylinder upside down when charging the refrigerant. If the refrigerant is not provided by Huawei, check with the refrigerant provider whether the cylinder has a siphon. If the cylinder has a siphon, stand the cylinder when charging refrigerant.