3.4.1.2 End-pieces and lead-throughs
Once the flexible busbar has been routed, all free busbar ends must be safely
terminated and sealed as required to achieve an IP65 degree of protection.
To do this, use cable end pieces (RA-C1-END1) and bushings (RA-C1-DF) as
necessary.
Figure 49: Bushing RA-C1-DF for ribbon cable
With bushing RA-C1-DF the flexible busbar can be fed into distribution
module RA-C1-VM-7 or a control panel.
▶
Cut the busbar to the required length.
Figure 50: RA-C1-CUT hand ribbon cable cutter
→
For cutting to length we recommend tool RA-C1-CUT.
▶
Strip the flexible busbar to the required length:
•
For cable end piece to 19 mm,
•
With distributor module at 50 mm,
•
for control panel as required.
→
Tool RA-C1-AZ-4 is recommended for stripping 7 x 4 mm
ble bus bar.
If using a standard cable stripping knife, make sure not to cut
into the rubber jacket by more than 0.7 mm in order to avoid
damaging the conductor's insulation.
Figure 51: RA-C1-AZ-4
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
3 Installation
3.4 Power bus