3.6.4 Screened motor cable for RASP5.

3.6.4.1 General notes
The following information uses the example of a DESINA MOTORFLEX cable
with 4G1.0 2 x (2 x 0.75), to describe the steps required for the EMC connec-
tion of a mains cable to the RASP5.
Figure 67: EMC-compliant connection of the screened motor cable
a 360° contact fuse ≙ power
Stripping the motor cable ends (radial and longitudinal cut).
To strip the cable, set the blade so that the conductor insulation
and the screen braid remain undamaged.
Push the screen braid back to reveal the individual conductors.
The conductors B1 (= N) and B2(= L) for the external brake as well as T1
and T2 for the thermistor have a sheath and a separate screen braid.
These conductors must be stripped separately.
Then slide the outer screen braid of the motor cable back toward the
cable end far enough that conductors B1/B2 and T1/T2 are covered over
a large area and connected with each other.
Wrap insulating or textile tape or slide a rubber grommet around
the screen ends to prevent the screen braid from splicing.
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
U1, V1, W1, PE
B1/B2
T1/T2
3 Installation
3.6 Motor feeder
103