10 Parameter list
10.4 Parameter groups for RASP

10.4.6 Parameter group 5 ("Communication")

Para-
Designation
meter
P5-01
RS485-0 Address
P5-02
COM Loss Timeout
P5-03
Action@Communication Loss
P5-04
FieldbusRampControl
P5-05
NETSendPZD3
P5-06
NETSendPZD4
P5-07
NETReceivePZD3
184
Table 39:
Parameter group 5 ("Communication")
Description
Unique address of the drive (keypad, OP bus)
With an active communication link, if a valid telegram is
not received by the drive within the period set with this
parameter, the drive will react as set in P5-03.
Device reaction after occuring of "Communication Loss".
Possibilities device dependent
0: Trip
1: Ramp to stop, then trip
2: Ramp to stop only (no trip)
3: Run at preset speed 2 (P2-01)
Fieldbus Ramp Control
0: OFF. Ramps are controlled from internal drives parame-
ters
1: ON. Ramps are controlled by the fieldbus.
Configuration of the 3rd process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place, e.g. 100 ≙
10.0 A
1: Output power in kW with 2 decimal places, e.g. 400 ≙
4.00 kW
2: Status of the digital inputs (DI). Bit 0 = Status DI1, Bit 1
= Status DI2 ...)
3: Heatsink temperature. 0 - 100 ≙ 0 - 100 °C
4: User register 1. Configuration with Function Block Editor
5: User register 2. Configuration with Function Block Editor
6: P0-59 value (Selection via P5-09)
Configuration of the 4th process data word PDO-4 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100 ≙ 10.0 A
1: Output power in kW with 2 decimal places,
e.g. 400 ≙ 4.00 kW
2: Status of the digital inputs (DI). Bit 0 = Status DI1, Bit 1
= Status DI2 ...)
3: Heatsink temperature. 0 - 100 ≙ 0 - 100 °C
4: User register 1. Configuration with Function Block Editor
5: User register 2. Configuration with Function Block Editor
6: P0-59 value (Selection via P5-09)
Configuration of the 3rd process data word PDI-3 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times with 2 decimal places
2: User register 3. Configuration with Function Block Editor.
3: User register 4. Configuration with Function Block Editor.
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
Unit
Min
Max
1
63
s
0
5.0
0
3
0
1
0
6
0
6
0
3
DS
1
2
0
0
0
1
1