Instructions for Installation, O peration and Maintenance of Cutler-Hammer IQ DP-4000 Electrical Distribution System Monitor TD 1 7548A Cutler-Hammer Effective October 1997...
Page 2
TD1 7548A IQ DP-4000 USING THE MANUAL This manual covers the installation, setup, operation, maintenance, and troubleshooting of the IQ DP-4000. It gives step-by-step instructions for programming the IQ DP-4000 to meet your specific application requirements. If you are installing the IQ DP-4000 for the first time, you should read and become familiar with the following sections of the manual: Introduction Hardware Description...
TD1 7548A IQ DP-4000 INFORMATION SAFETY PRECAUTIONS LIABILITY SAFETY PRELIMINARY COMM ENTS Safety Precaution PRECAUTIONS All safety codes, safety standards, and/or regulations This Technical Document covers all aspects of m ust be strictly observed in the installation, operation, installation, operation, and unit-level maintenance of the and maintenance of this device.
Page 4
IQ DP-4000 SECTION 1 - INTRODUCTION TD 1 7548A Voltage may be directly monitored on 3-phase AC lines within a range of 1 20 to 600 VAC nominal without 1 .1 INTRODUCTION external potential transformers and within a range above The IQ DP-4000 is a microprocessor-based monitoring 600VAC to 5 1 0 with external potential transformers...
Page 5
21 07A55G03 IQ mounting flange IQFLANGE 5743B02G01 Commun ication module IPONI 8793C3 6 G0 1 I Q DP-4000 Auxil i ary Power Supply IQDPAUXPS 5743B37G01 IQ DP-4000 Configuration Utility See the Cutler-Hammer website at www.cutlerhammer.eaton.com Table 1.8 Parts and Accessories...
Page 6
IQ DP-4000 SECTION 2 - HARDWARE DESCRIPTION TD1 7548A Setpoint Switches, located on the rear right side of the chassis, allow you to tailor each IQ DP-4000 INTRODUCTION model for your specific applications. For a complete The IQ DP-4000 is designed for mounting through a description of each Setpoint Switch setting see cutout in a panel (usually a cabinet face or door).
Page 7
IQ DP-4000 TD1 7548A SECTION 2 - HARDWARE DESCRIPTION Figure 2.2 Rear Access Area of Chassis REMOVE ALL VOLTAGE FROM THE IQ DP-4000 A fuse, external to the power module, is located on BEFORE REMOVING AN D/OR REPLACIN G the rear right of the chassis. This fuse is a 1 /4 amp FUSES.
Page 8
IQ DP-4000 SECTION 2 - HARDWARE DESCRIPTION TD1 7548A The discrete input can be configured to be either a Series I l l Microsoft™ Windows-compatible reset input or a sync pulse input. The input is application featuring user-friendly, menu-driven screens activated by a contact closure across terminal block with easy set-up and operation.
Page 9
IQ DP-4000 SECTION 2 - HARDWARE DESCRIPTION TD1 7548A power module) 0.02 VA Overvoltage. An overvoltage is detected when the • amplitude of the AC line voltage exceeds 1 05, 1 1 0, CT Burden 0.003 VA 1 1 5, 1 20, 1 25, 1 30, 1 35, or 1 40% of the nominal Frequency 50/60 Hz line voltage.
Page 10
IQ DP-4000 SECTION 2 - HARDWARE DESCRIPTION TD1 7548A 2.2.3 Metering Specifications Table 2.C shows the metering specifications for the IQ D P-4000. Displayed through Local Display IMPACC +1- 0.3 % +1- 0.3 % +1- 1 digit AC Amperes Phases A, 8,C +1- 0.3 % +1- 1 digit +1- 0.3 %...
Page 11
IQ DP-4000 SECTION 3- OPERATOR PANEL TD1 7548A at the same time, the INCOM network address for your unit appears in the Display W indow. It monitors 3 .1 INTRODUCTION the following items: This section describes the operator panel of the IQ DP- 4000.
Page 12
IQ DP-4000 SECTION 3- OPERATOR PANEL TD1 7548A Metered. The Metered pushbutton displays Stepup and Stepdown. Holding the Stepup • • the metered values for all the parameters and Stepdown pushbuttons will display the on the Operator Panel. I NCOM address(only if the PONI module is attached and communication has been %THO.
Page 13
IQ DP-4000 SECTION 3- OPERATOR PANEL TD1 7548A Note: The following examples assume that the unit is Reactive Power using the mathematic sign convention. QUADRANT 2 QUADRANT 1 Watts, Vars and/or Power Factor. The selected • LEOs blink when viewing reverse power flow, lagging (negative) Power Factor, and negative Vars.
Page 14
IQ DP-4000 SECTION 3- OPERATOR PAN EL TD1 7548A POWER FLOW- Alarm Cause Operator Panel Description LINE Code Designation LOAD CURRENT TRANSFORMER External Remote device Figure 3.4 Induction Motor Load initiates alarm LINE LINE Overvoltage Undervoltage BREAKER A BREAKER 8 Phase Unbalance An alarm condition...
Page 15
IQ DP-4000 SECTION 4 - I NSTALLATION A N D STARTUP TD1 7548A are not threaded, but do not use a tap because this removes excess plastic from the holes, which leaves INTRODUCTION less threaded material for securing the IQ DP-4000 to This section provides the information for installing the IQ the mounting panel.
Page 16
IQ DP-4000 TD1 7548A SECTION 4 - INSTALLATION AND STARTUP power module using either the 36 in. (9 1 .4 em) or the 45 in. (1 1 4.25 em) Extension Cable Option 'W1th CoMMunico.tion Moclule 5.400 The separated power module can physically •...
Page 17
IQ DP-4000 SECTION 4 - INSTALLATION AND STARTUP TD1 7548A 3. You can use NO and NC contacts from the Relays to ENSURE THAT THE I N COMING AC POWER AND ALL control external devices. These contacts are rated at 'FOREIGN' POWER SOURCES ARE TURNED OFF 1 0 amps for 1 20/240 VAC or 30 VDC.
Page 18
IQ DP-4000 SECTION 4 - INSTALLATION AND STARTUP TD1 7548A PHASE WIRE (ABOVE VOLTS) & EXTERNAL VOLTAGE TRANSFORMERS CURRENT TRANSFORMERS ;\j l FUSE OPEN DELTA · � VT CONNECTION (100-350 (96- 264 CONTROL POWER � OP�4000 2cb jo 4 NEcJ'RAL TERM.
Page 19
IQ DP-4000 SECTION 4 - I N STALLATION A N D STARTUP TD17548A (ABOVE VOLTS) PHASE WIRE 2 CT's WITH 10 DP-4000 EXTERNAL VOLTAGE TRANSFORMERS & CURRENT TRANSFORMERS L1 NE LOAD � IQ DP-4000 CIIB NEUTRAL TERM. SEPARATE SOURCE POWER SUPPLY MODULE Figure 4.7 3-Phase, 3-Wire (above 600 volts) Wiring Diagram (Separate Source, 2 CTs) (UP TO VOLIS)
Page 20
IQ DP-4000 SECTION 4 - INSTALLATION A N D STARTUP TD17548A PH A SE WIRE (ABOVE VOLTS) EXTERNAL VOLTAGE TRANSFORMERS & CURRENT T LINE LOAD FUSE (100-350 VDC) (96-264 VAC) CONTROL POWER IQ uP-4000 HIC riB �lA NEUTRAL TERM. POWER SUPPLY SEPARATE SOURCE MODULE Figure 4.9 3-Phase, 4-Wire (above 600 volts) Wiring Diagram (Separate Source)
Page 21
IQ DP-4000 SECTION 4 - I N STALLATION AND STARTUP TD1 7548A PHASE WIRE (ABOVE 600 VOLTS) EXTERNAL VOLTAGE TRANSFORMERS & CURRENT TRANSFORMERS �� =�===================: 1 ,- = = - - = L O A FUSE OPEN DELTA VT CONNECTION DP - 4000 ci2C H2B NEUTRAL...
Page 22
IQ DP-4000 SECTION 4 - INSTALLATION A N D STARTUP TD1 7548A WIRE PHASE 3 (ABOVE 600 VOLTS) CT's WITH IQ DP-4000 & EXTERNAL VOLTAGE TRA!'.<ScORMERS CURRENT TRANSFORMERS LOAD FUSE OPEN D ELTA VT CONNECTION DP-4000 fll C c!l 8 r'2C NC:UTRAL TERrk...
Page 23
IQ DP-4000 TD1 7548A SECTION 4 - INSTALLATION AND STARTUP 3 PHASE WIRE (ABOVE VOLTS) & EX TERNAL VOLTAGE TRANSFORMERS CURRENT TR.4NSFORMERS LOAD FUSE CONNECTION � � 10 DP-4000 � Hl B NEUTRAL TERM. SELF-POWERED POWER SUPPLY MODULE Figure 4 . 1 5 3-Phase, 4-Wire (above 600 volts) Wiring Diagram 4 .
Page 24
IQ DP-4000 TD1 7548A SECTION 5 - PROGRAMMING THE IQ DP-4000 functions that may be set. The left column lists the 1 5 Select Switches and the top row lists the Setpoint INTRODUCTION Switches. Appendix B contains a blank Master Setpoint This section identifies all of the programmable functions Record Sheet for you to use to record your setpoint of the IQ...
5. 1 3 and is available from the Cutler- Hammer web site at DP-4000/DP-2 Mode 5. 1 4 www.cutlerhammer.eaton.com Table 5 . 8 General System Functions AwARNING BE CAREFUL WHEN R E PROGRAM M I N G T H E IQ DP-...
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A Press the Save button briefly to see if the LED's permanently stored device's long-term light properly. The corresponding LED will light if the memory. switch is turned on. 1 0. Place the Select Switch to the 0 position. When the Setpoint Switches for that Select Switch are all in the proper location, press and hold the 5.3 SYSTEM CON FIGURATION SETPOINT...
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A A system with a CBA sequence has phase C leading Switch SW1 Nos. 3 , 4, 5, and 6 specify the nominal AC line voltage. Set the switches according to Table 5 . F. phase B by 1 20 degrees, and phase B leading phase A Follow the table's line-to-line column when the wiring by 1 20 degrees.
IQ DP-4000 TD1 7548A SECTION 5 - PROGRAMM I N G THE IQ DP-4000 5 . 9. 1 Power Demand, Fixed/ Sliding 5 . 9 . 3 Current Demand Time Interval The IQ DP-4000 is programmed for the power related Switch SW4 Nos.
IQ DP-4000 SECTION 5 - PROGRAMM I N G THE IQ DP-4000 TD1 7548A Paragraphs 5. 1 2. 1 3. 1 and 5.1 2.1 3.2. See Table 5.1 for 5.1 1 VAR/POWER FACTOR SIGN CONVENTION setting the alarm modes for the relays. SETPOINT This setpoint selects the sign convention (+ or -) for the Var and the Power Factor values.
Page 30
IQ DP-4000 TD1 7548A SECTION 5 - PROGRAMMING THE IQ DP-4000 5. 1 2. 2 Latched/Unlatched ( Auto-reset ) Alarm Setpoint Alarm 1 Alarm 2 Position This setpoint allows the IQ DP-4000 to operate in one of two ways - the latched mode or the unlatched mode. OFF disables Activate on See Table 5.J for setting this option.
Page 31
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A phase rotation of the metered voltages to the selected The timer resets when the condition is below the alarm phase sequence of the system (see Section 5.8) , and threshold.
Page 32
IQ DP-4000 TD1 7548A SECTION 5 - PROGRAMMING THE IQ DP-4000 If the sampled voltage is greater than the overvoltage and comparing that voltage to a percentage of the detection level for longer than the alarm delay (see nominal AC line voltage. Section 5.
Page 33
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A •= OFF D = ON Table 5. W Reset Threshold Settings 5. 12. 15. 1 Overvoltage Reset Threshold determine threshold level reset overvoltage, find the voltage when an overvoltage alarm will occur.
Page 34
IQ DP-4000 TD1 7548A SECTION 5 - PROGRAMMING THE IQ DP-4000 Reset Threshold Overvoltage Detection Level (Volts) Reset Threshold 0 to 1 00% Reset Threshold Nominal Line-to-Line Voltage (Volts) Reset Threshold 1 00% ·••• .. . Figure 5. 1 Overvoltage Detection and Reset Levels 504V 528V - RST% x (528V - 480V) Example 1...
Page 35
IQ DP-4000 SECTION 5 - PROGRA M M I N G THE IQ DP-4000 TD1 7548A . , u"��la � Ef · . � ���{ · · · · · • / · · · · · •·•·• Nominal Line-to-Line Voltage (Volts) Reset Threshold Reset Threshold - 0 to 100% Reset Threshold...
Page 36
IQ DP-4000 SECTION 5 - PROGRA MMING THE IQ DP-4000 TD1 7548A Reset Threshold Maximum Deviation Between Phases Nominal Voltage x (0-40%) Reset Threshold - 0 to 1 00% Reset Threshold Reset Threshold 1 00% Maximum Deviation Between Phases Figure 5.3 Voltage Phase Unbalance Detection and Reset Levels Example 1 A system has the following settings: Nominal AC Line Voltage...
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A If the discrete input is set up as a reset input, a dry contact closure across the terminal blocks of the discrete ··· 5.1 3 IMPACC PROGRAMMABLE SETPOINT input will attem pt to reset an active alarm . (This is You can allow programming of the IQ DP-4000 using identical to using the Reset pushbutton when resetting an IMPACC with this setpoint.
Page 38
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A T able Pulse Initiator Parameter Selection Settings 5. 15. 3.2 Load Shed Settings, Range Selection Two ranges are associated with the load shed feature: a Load Shed range and a Restore Load range. Both ranges are set as a percentage of the nominal values for the system.
Page 39
IQ DP-4000 SECTION 5 - PROGRAMMING THE IQ DP-4000 TD1 7548A • = OFF D = ON Switch Settings Ran ges Load Shed , Select SW E Switch %of nominal No. 1 No. 2 No. 3 No. 4 No. 5 No.
Page 40
IQ DP-4000 SECTION 5 - PROGRAM MING THE IQ DP-4000 TD1 7548A •= OFF D = ON Ranges Switch Settings Select Load Shed, SW E SW E SW D SW D Sw itch % of nom inal No. 6 No. 7 No.
IQ DP-4000 SECTION 5 - PROGRA M MING THE IQ DP-4000 TD1 7548A The IQ DP-4000 is monitoring a constant power of 1 6,800 Watts. 5.15.3.3 Load Shed Settings, Parameter Selection The load shed feature activates the pulse initiator relay Watt-hours is selected as the parameter for the pulse when user-selected...
Page 42
IQ DP-4000 SECTION - TROUBLESHOOTING AND MAINTENANCE TD1 7548A REPLAC E M ENT LEVEL OF REPAIR To replace the IQ DP-4000: This manual is written assuming you will perform only Turn off control power at the main disconnect or unit-level troubleshooting. If you trace the cause of a isolation switch of the power supply.
Page 43
IQ DP-4000 SECTION 6 - TROU BLESHOOTING AND MAINTENANCE TD1 7548A 1 -800- Advanced Products Support Center {APSC) at 809-2772. Probable Cause(s) Solution Symptom Locate cause of deficiency in AC line All Operator Panel indicators are off. AC line voltage level is deficient. monitored.
Page 44
IQ DP-4000 SECTION 6 - TROU BLESHOOTING A N D MAINTENANCE TD1 7548A Symptom Probable Cause(s) Solution All Operator Panel LEDs are off. AC line being mon itored is below 96 VAC. Locate the cause of the deficiency in the monitored AC line.
Page 45
IQ DP-4000 SECTION 6 - TROUBLESHOOTING AND MAINTENANCE TD1 7548A 6.6 R ET U R N PROCEDURE The troubleshooting section is intended for service personnel to identify whether an observed problem is external or internal to the unit. For assistance with this determination, please contact...
Page 46
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TO 1 7548A = ON = OFF Switch Setti ngs Values PT Ratio...
Page 47
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values Select Ratio Setpoint No. 7 No. 6...
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TO 1 7548A = OFF = ON Switch Settings Values Switch Ratio No. 7 No. 2 No. 8 Switch...
Page 49
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A = OFF = ON Switch Settings Values No . 5 No. 3 No. 6...
Page 50
IQ DP-4000 TO 1 7548A APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES Switch Settings Values Select No. 8 Setpoint...
Page 51
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values Switch...
Page 52
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD 1 7548A = OFF = ON Switch Settings Values Select Ratio Switch Setpoint No. 1 No. 6...
Page 53
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD1 7548A = OFF = ON Switch Settings Values Switch No . 5 No. 2...
Page 54
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD 1 7548A = OFF = ON Switch Settings Values Switch No. 1 No. 6 No. 7...
Page 55
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A = OFF = ON Switch Settings Values No . 3 No . 6 No. 8 No. 1...
Page 56
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD 1 7548A = OFF = ON Switch Settings Values No . 4 No. 5...
Page 57
IQ DP-4000 TD1 7548A APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES Switch Settings Values Ratio No . 3 No. 8 No. 2...
Page 58
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES 1 7548A Switch Settings Values Select Setpoint No. 6 No. 8 Switch...
Page 59
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values No . 3 No. 8...
Page 61
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values Select Switch No. 8 No. 1 No. 2 No . 3 No . 4 No. 5 No. 6 No. 7 No. 8...
Page 62
IQ DP-4000 TD 1 7548A APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES Switch Setti ngs Values Select Sw itch Pr im ary Switch...
Page 63
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A = OFF = ON Switch Settings Values Select Sw itch Pr im ar y No. 6 No. 2 No. 3 No. 4 No. 5 No.
Page 64
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TO 1 7548A = OFF = ON Switch Settings Values Selec t Switch Primary No. 6 (CT:S) No. 8 No. 1 No. 2 No. 3 No. 4 No. 7 Switch...
Page 65
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A = OFF = ON Switch Settings Values Select Sw itch Pr im ary No. 6 No. 1 No. 2 No. 3 No. 4 No. 7 (CT:5) Switch...
Page 66
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD 1 7548A Switch Settings Values Select Switch Primary Switch These CT Primary values are repeated from previous pages. Either setting is acceptable.
Page 67
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values Select Sw itch Pri ma ry No. 8 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 (CT:S) Switch These CT Primary values are repeated from previous pages.
Page 68
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TO 1 7548A Switch Settings Values Select Sw itch Pri ma ry Switch...
Page 69
IQ DP-4000 TD1 7548A APPENDIX A - PT RATIO A N D CT P R I MARY SETPOINT VALUES Switch Settings Values Select Switch Primary No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No . 7 (CT:5) No.
Page 70
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD 1 7548A = OFF = ON Switch Settings Values Select SW 3 Switch Primary Switch...
Page 71
IQ DP-4000 TD1 7548A APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES = OFF = ON Switch Settings Values Select Sw itch Pri ma ry No. 6 No. 7 No. 8 No. 1 No. 2 No. 3 No.
Page 72
IQ DP-4000 APPENDIX A - PT RATIO AND CT PRIMARY SETPOINT VALUES TO 1 7548A Switch Settings Values Select SW 3 Switch Primary Switch...
Page 73
IQ DP-4000 APPENDIX A - PT RATIO A N D CT PRIMARY SETPOINT VALUES TD1 7548A Switch Settings Values Select Switch Prim ary Switch...
Page 74
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TD 1 7548A Master Setpoi nt Record Sheet Once you have determined the settings for your setpoint switches, record them in this table. Remove and store this table in several locations and keep it up-to-date when you change settings. No.
Page 75
IQ DP-4000 APPENDIX - SETPOINT RECORD SH EETS TD1 7548A I n the Setpoint Display rows, shade the cells of the numbers for which the LED's should l ight. This will allow you to easily verify the settings for each Select Switch. In the Setpoint Switch row, indicate beside each switch whether the switch is to the left (Off) or to the right (On).
Page 76
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TD 1 7548A Setpoint Display Setpoint Switch...
Page 77
IQ DP-4000 APPENDIX B SETPOINT RECORD S H E ETS TD1 7548A General System Setpoint Record Sheet Voltage Transformer Ratio System Configuration •= OFF = Not Applicable • = OFF = ON = Not Applicable = ON OFF = 3-Wire ON = 4-Wire See Appendix A Current Transformer Primary...
Page 78
IQ DP-4000 APPENDIX B SETPOINT R ECORD SHEETS TD 1 7548A Power Demand Window Reset Energy from Faceplate •= OFF l:l = ON •= OFF l:l = ON = Not Applicable = Not Applicable OFF = Disabled ON = Fixed ON = Enabled Power Demand Time Interval Energy Resolution...
Page 79
IQ DP-4000 TD1 7548A APPENDIX B SETPOINT RECORD SHEETS INCOM Programmable DP-4000/DP-2 Mode •= OFF = ON = Not Applicable •= OFF = ON = Not Applicable OFF = Disabled ON = Enabled ON = DP-4000 Mode...
Page 80
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TD 1 7548A Alarm 1 Setpoi nt Record Sheet Alarm 1 Mode 1 /Mode 2 Alarm 1 Activate on Undervoltage •= OFF = ON = Not Applicable •= OFF = ON = Not Applicable OFF = Mode 1 ON = Mode 2 ON = Enabled...
Page 81
IQ DP-4000 APPENDIX SETPOINT RECORD SHEETS TD1 7548A Alarm 1 Activate on Voltage Phase Reversal Alarm 1 Trip Delay = Not Applicable •= OFF = ON = Not Applicable •= OFF = ON OFF = Disabled See Table S.R ON = Enabled Alarm 1 Reset Delay •= OFF = ON...
Page 82
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TO 1 7548A Alarm 1 Undervoltage Detection Level Alarm 1 Reset Threshold •= OFF CJ = ON = Not Applicable •= OFF CJ = ON = Not Applicable See Table S.U See Table S.W Alarm 1 Voltage Phase Unbalance Detection Level •= OFF CJ = ON = Not Applicable...
Page 83
IQ DP-4000 TD1 7548A APPENDIX SETPOINT RECORD SHEETS Alarm 2 Setpoi nt Record Sheet Alarm 2 Mode 1/Mode 2 Alarm 2 Activate on Undervoltage = Not Applicable • = OFF CJ = ON = Not Applicable •= OFF CJ = ON OFF = Mode 1 OFF = Disabled ON = Mode 2...
Page 84
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TO 1 7548A Alarm 2 Activate on Voltage Phase Reversal Alarm 2 Trip Delay •= OFF = ON = Not Applicable •= OFF = ON OFF = Disabled See Table S.R ON = Enabled Alarm 2 Reset Delay •...
Page 85
IQ DP-4000 TD1 7548A APPENDIX B SETPOINT RECORD SHEETS Alarm 2 Undervoltage Detection Level Alarm 2 Reset Threshold •= OFF = ON = Not Applicable •= OFF = ON = Not Applicable See Table 5.U A larm 2 Voltage Phase U n balance Detection Level •= OFF = ON = Not Applicable...
Page 86
IQ DP-4000 APPENDIX SETPOINT RECORD SHEETS TO 1 7548A Optional 1/0 Setpoi nt Record Sheet Pulse Initiator Parameter Discrete Input Setup •= OFF r:J = ON = Not Applicable •= OFF r:J = ON = Not Applicable See Table 5.X ON = I nput is used as an External Reset Load Shed Range •= OFF r:J = ON...
Page 87
IQ DP-4000 APPENDIX B SETPOINT RECORD SHEETS TD1 7548A Load Shed Parameter Pulse I nitiator Rate = Not Applicable •= OFF = ON = Not Applicable •= OFF = ON See Table S.AA See Table 5.Z...