5 RAMO5 Motor starter

5.4 Special technical data

5.4 Special technical data
Instance
Block diagram
Rated operational current (I
)
e
Adjustable motor protection
Assigned motor output at
400 V, 50 Hz
440 - 460 V, 60 Hz
Power side (primary side)
Number of phases
Rated voltage
Input current
Braking
Control voltage
(external brake)
Load current (external brake)
Heat dissipation at
rated current (I
)
e
Weight (without/with manual override
switch)
Reaction time
1)
Motor On (automatic)
1)
Motor Off (automatic)
Switch off the motor (quick stop)
Switch on Q1
Switch off Q1
Minimum pulse duration I1/I2
1) without bus runtime, depending on PLC
122
The following tables show the technical data of the RAMO5 Motor Control
Unit in the individual power classes with the allocated motor output.
The motor output allocation is based on the rated operational
current.
The motor output designates the respective active power
output to the drive shaft of a normal, four pole, internally or
externally ventilated three-phase asynchronous motor with
1500 min
Symbol
Unit
I
A
e
A
P
kW
P
HP
U
V
LN
I
A
LN
U
V
I
A
P
W
v
m
kg
t
ms
ON
t
ms
OFF
t
ms
Off
t
ms
ON
t
ms
OFF
t
ms
ON
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
-1
(at 50 Hz) and 1800 min
RAMO5-D...
Direct starter
L1 → U, L2 → V, L3 → W.
→ Page 123
6.6
0.3 - 6.6
0.18 - 3
0.25 - 4
3
380 V - 10 % - 480 V + 10 %, 45 - 66 Hz
0.3 - 6.6
RAMO5-xxx1...: 180 V DC
RAMO5-xxx2...: 230/277 V AC
RAMO5-xxx4...: 400/480 V AC
0.6 A, max. 6 A for 120 ms
max. 8 W, depending on motor current and brake
1.6/1.8
Motor 20-35, brake 20-35
Motor 20-35, brake 20-35
Motor 20-35, brake 20-35
2 - 20
2 - 20
5
-1
(at 60 Hz).
RAMO5-W...
Reversing starter
FWD: L1 → U, L2 → V, L3 → W
REV: L1 → W, L2 → V, L3 → U.
→ Page 124