Parameter Group 1 ("Basic") - Eaton RAMO5 Manual

For rapid link 5
Hide thumbs Also See for RAMO5:
Table of Contents

Advertisement

10.3.2 Parameter group 1 ("Basic")

Para-
Designation
meter
P1-08
Motor Nom Current
P1-13
DI Config Select
P1-14
Access Key
Table 28:
Parameter group 1 ("Basic")
Description
Motor rated current.
By setting the "Motor Nom Current" in the drive, the motor
overload protection is configured to match the motor
rating.
When the measured motor current exceeds "Motor Nom
Current", the decimal points on the display will flash to
indicate an overload condition.
If this condition persists, the drive will eventually trip,
displaying I. t -trP, preventing thermal overload of the
motor.
Configuration of digital inputs with a fix set of combina-
tions
Entry of the password to get access to the extended
parameter set.
The value to be put in is determined by the level to be
accessed.
Level 2 (Access to parameter groups 0 to 8): P1-14 = P2-32
(Default: 101)
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
10 Parameter list
10.3 Parameter groups for RAMO
Unit
Min
Max
Amps
0.3
6.6
1
4
0
65535
DS
6.6
1
0
165