5 RAMO5 Motor starter
5.7 Configure special settings
5.7.2 Sensor inputs I1 and I2
Parameter
Designation
P3-06
DI1 Logic
P3-07
DI2 Logic
128
Sensor inputs I1 and I2 are laid out for rising-edge input signals (N/O, fail-
safe). Parameter P3-06 is set to the value 1 when delivered.
When using sensors (open) that switch to zero, parameter P3-07 must be set
to 1. The signal is then inverted.
I1, I2
->
I1, I2
->
Figure 88: Configuring the sensors inputs I1 and I2
Description
0 = close
1 = open
Note:
Change active only after POWER ON/OFF
0 = close
1 = open
Note:
Change active only after POWER ON/OFF
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
1
0
Unit
Min
Max
DS
–
0
1
0
–
0
1
0