The following sensors can be connected, for example:
optical (light barriers),
inductive (proximity switches),
mechanical (end switch).
The length of the sensor connection cables for inputs I1 and I2 is limited to
5 m. The sensors are supplied with 24 V DC from the RAMO5 and RASP5
rapid-link modules. The total current of all sensors is limited to 160 mA.
The sensor supply is short-circuit proof. In the event of an overload or short-
circuit, a group fault signal will be generated and the "Motor" LED will light
up FLT in red to indicate this. As soon as the fault is fixed, the error message
can be reset with the RESET command. In addition, the S1 bit will be set to
high during a short-circuit (peripheral fault). It will be set back to low automat-
ically once the short-circuit is eliminated.
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com