10 Parameter list
10.3 Parameter groups for RAMO
10.3.3 Parameter group 2 ("Extended functions")
Para
Designation
meter
P2-24
Start Mode
P2-26
Auto Reset Delay
P2-27
Action@Thermistorfault Motor
P2-28
Service Interval Time
P2-29
Reset ServiceIndicator
P2-30
Parameter Set
P2-32
Access Key Level2
P2-33
Parameter Lock
166
Table 29:
Parameter group 2 ("Extended functions")
Description
Defines the behaviour of the drive relating to the enable
digital input and also configures the automatic restart
function.
0: Edge-r : Following power on or reset, the drive will not
start if a start signal (FWD/REV) is still present. To start a
rising edge is necessary.
1: Auto-0 : Following a power on or reset, the drive will
automatically start if digital input 1 is closed.
2, ..., 9: Auto-1 to 9 : Following a trip, the drive will make
up to 9 attempts to restart at intervals set in P2-26.
The drive must be powered down to reset the counter.
The number of restart attempts are counted, and if the
drive fails to start on the final attempt, the drive will trip,
and will require the user to manually reset the fault.
AutoResetDelay
Determines the time which will elapse between consecu-
tive drive reset attempts when Auto Reset is enabled in P2-
24.
Device reaction after occuring of "Thermistorfault Motor".
Possibilities device dependent
0: deactivated
1: activated
Service Interval Time
Defines the number of operating hours, after which the
service indicator is shown on the display.
With P2 -29 = 1 the counter is set to the value defined here.
The remaining time until the next service is indicated with
P0-22.
Reset Service Indicator
With P2-29 = 1 the counter for the remaining hours until
the next service is set to the value defined in P2-28.
Reset of P2-29 to 0 is done automatically.
Restores factory parameter settings.
Defines the password which is used to get access to
extended parameter set (Level 2).
Access via P1-14.
Determines whether to lock the parameters
0: OFF. All parameters can be accessed and changed
1: ON. Parameter values can be displayed, but cannot be
changed.
If a remote keypad is connected, parameters cannot be
accessed.
Rapid Link 5 · RAMO5 · RASP5 10/19 MN034004EN www.eaton.com
Unit
Min
Max
–
0
10
s
0.1
60
–
0
1
h
0
60000
–
0
1
–
0
1
–
0
65535
–
0
1
DS
0
0.5
1
0
0
0
101