Standard Configuration Concept - ABB Relion Series Engineering Manual

Grid automation
Hide thumbs Also See for Relion Series:
Table of Contents

Advertisement

1MRS757810 C
2.2
REC615 and RER615
Engineering Manual
NCC-GW
HSI
(station-IED1)
(station-IED2)
bay
bay
IED 1
IED 2
GUID-414609A0-5B40-453F-83D4-4551B2894023 V1 EN
Figure 2:
Principle structure of a monitoring and control system for a substation
The monitoring and control system can be divided into three main parts.
Bay level devices
Station communication
Station level devices
All three parts require specific engineering and configuration.
A plant structure is used to identify each device in its location within the substation
organization. The plant structure is a logical image of the substation and the bays
within the substation. The organization structure for the devices may differ from the
structure of the primary equipment in the substation.
In PCM600 it is possible to set up a hierarchical structure of five levels for the device
identification.
Project
Substation = name of the substation
Voltage level = identifies to which grid type or part the device belongs in the
substation
Bay = bay within the voltage level
IED = the selection of the IED that is used in the bay; it is possible to insert several
IEDs within a bay, for example, one control device and two protection relays

Standard configuration concept

The product series covers protection relays developed for the protection of medium
voltage applications. Every product has predefined application-specific software
called standard configuration that contains protection, control, supervision and
measurement function blocks and default logical connections; for more information,
Relay engineering process
PCM600
(tool set)
Station bus
bay
bay
IED n-1
IED n
Section 2
Station level
Station
Communication
Bay level
IEC08000101.vsd
17