Standard Configuration A; Applications - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
3.3
3.3.1
REG615
Application Manual

Standard configuration A

Applications

The standard configuration with directional reactive power undervoltage and low-
voltage ride-through protection, voltage vector shift and frequency-based protection
is intended as interconnection protection for common point of coupling distributed
power generation into the utility network.
Standard configuration A is not designed for using all the available functionality
content in one relay at the same time. Directional earth-fault protection functions must
be added with the Application Configuration tool. To ensure the performance of the
relay, the user specific configuration load is verified with the Application
Configuration tool in PCM600.
The protection relay with a standard configuration is delivered from the factory with
default settings and parameters. The end user flexibility for incoming, outgoing and
internal signal designation within the protection relay enables this configuration to be
further adapted to different primary circuit layouts and the related functionality needs
by modifying the internal functionality using PCM600.
REG615 standard configurations
Section 3
37