External Breakers; Grounding Wire - Toshiba 4400 Series Installation And Operation Manual

Three phase - 15/20/25/30/50/80/100 kva
Hide thumbs

Advertisement

Table of Contents
9.5

External Breakers

The UPS is not equipped with isolation circuit breakers. Qualified personnel should provide the external breakers for the AC
input/output, bypass input and DC input.
Table 9.4 shows the minimum external breaker rating for each UPS. The bypass, input and output require 3-pole breakers.
Voltage
15kVA
208/120V
240V/90A
220/127V
240V/90A
240V
240V/80A
380/220V
480V/50A
400/227V
480V/50A
415/240V
480V/45A
480/277V
480V/40A
600V
600V/35A
Note: Above Amp trip ratings are sized for the worst case in the UPS System (Primpary Input Breaker) according to NEC
215.3 guidlines. For more exact recommendations, please refer to "Appendix C – Installation Planning Guide".
Voltage Capacity
(Min.)
500VDC
* For Battery Cabinet Systems not equipped with built-in over-current protection devices.
9.6

Grounding Wire

The earth grounding bus is located behind the dead front, close to the power lugs. See Section 8.5-8.7. Connect the
grounding wire to the earth ground bus.
The 15-50kVA UPS have a bus strip with 7 (seven) threaded holes for M4 bolts. Use a AWG 2 (or 38 mm
for the grounding wire. Connect the crimp terminal and ground bus together using a M4 bolt.
The 80-100kVA UPS has a ground bus with 10 (ten) M5x0.8 threaded holes, and 6 (six) 0.5118 in (13 mm) unthreaded
holes for 1/2 in bolts. Ground wire must have a crimp terminal with a corresponding diameter bolt hole. Connect the crimp
terminal and ground bus together using the appropriate diameter bolt.
4400 Series Installation and Operation Manual – 64527-008
TABLE 9.4: UPS MINIMUM BREAKER RATINGS
20kVA
25kVA
240V/125A
240V/150A
240V/125A
240V/150A
240V/100A
240V/125A
480V/70A
480V/80A
480V/60A
480V/70A
480V/60A
480V/70A
480V/50A
480V/60A
600V/40A
600V/50A
TABLE 9.5: DC (BATTERY) MINIMUM BREAKER RATINGS*
15kVA
20kVA
25kVA
100A
150A
WARNING
Be sure to ground the UPS as specified.
Using the UPS without a proper ground will deteriorate the insulation,
cause leakage of currents and electric shock. The resistance to
ground should be less than or equal to 10 ohms.
Capacity
30kVA
240V/175A
240V/250A
240V/150A
240V/250A
240V/150A
240V/225A
480V/90A
480V/150A
480V/90A
480V/150A
480V/80A
480V/125A
480V/70A
480V/110A
600V/55A
600V/85A
30kVA
50kVA
175A
200A
50kVA
80kVA
240V/400A
240V/400A
240V/350A
480V/225A
480V/200A
480V/200A
480V/175A
600V/150A
80kVA
350A
600A
100kVA
240V/500A
240V/450A
240V/400A
480V/300A
480V/250A
480V/250A
480V/200A
600V/175A
100kVA
700A
) or larger cable