Table 3-8 Rating Of Contactors, Breakers And Fuses - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

* Provides 100kAIC short circuit interrupt rating. Factory installed by default.
NUMBER
CB1
CB3
52C
52S
88RC
CB2
User supply (OPTION)
User supply (OPTION)
User supply (OPTION)
FCU, FCV, FCW
FCR, FCS, FCT
FPU, FPV FNU, FNV
FPR, FPS, FPT, FPW,
FNR, FNS, FNT, FNW
FUA, FUB, FUC
FSU, FSV, FSW
FZS1, 2, 3
FBS1, 2, 3
FZR1, 2, 3
FEA, FEB, FEC
24
Table 3–8 Rating of Contactors, Breakers and Fuses
APPLICATION
AC input contactor
STS contactor
Inverter output contactor
Bypass contactor
Control circuit contactor
Battery disconnect breaker
(Recommended)
AC input breaker
(Recommended)
AC bypass breaker
(Recommended)
AC output breaker
(Recommended)
DC fuse
DC fuse
DC fuse
Control power fuse
Bypass input fuse*
Bypass input ZNR fuse
Control power fuse
AC input ZNR fuse
Parallel control circuit fuse
G9000 Series UPS 300-750kVA Installation and Operation Manual – 61480-017
OUTPUT CAPACITY OF EQUIPMENT
300kVA
500kVA
300kW
500kW
452A
680A
260A
260A
452A
680A
452A
680A
20A
20A
800A
1400A
500A
800A
500A
800A
500A
800A
450A / 690V 630A / 690V
450A / 690V 630A / 690V
450A / 690V 630A / 690V
30A / 600V
30A / 600V
250A / 690V 315A / 690V
-
-
30A / 600V
30A / 600V
-
-
3A / 600V
3A / 600V
650kVA
750kVA
650kW
750kW
1005A
1005A
350A
350A
1005A
1005A
1005A
1005A
20A
20A
2000A
2000A
1200A
1200A
1000A
1200A
1000A
1200A
800A / 690V
800A / 690V
800A / 690V
800A / 690V
800A / 690V
800A / 690V
30A / 600V
30A / 600V
315A / 690V
315A / 690V
-
-
30A / 600V
30A / 600V
-
-
3A / 600V
3A / 600V