4400 SPECIFICATIONS: 15–30kVA w/ External Battery Backup
Specification
Mechanical
Weight
lb/(kg)
2
with 1 Transformer
with 2 Transformers
Dimensions WxDxH (in/mm)
Shipping Weight
lb/(kg)
2
with 1 Transformer
with 2 Transformers
Shipping Dimensions WxDxH (in/
mm)
Clearance (in/mm)
Enclosure
Construction
Color
Emergency Power Off (EPO)
Control Panel
Monitoring
Operator Interface (Front Panel)
Dry Contacts Included
RS-232 Inrterface
Optional – Intelligent Monitoring
Optional – Remote Status Alarm
Panel (RSAP)
Additional Features
Optional Matching Battery Cabinets
Optional Matching MBS/PDU Cabinet
OTHER
Warranty (yr.)
Certifications
Minimum front clearance for unobstructed airflow is 20 inches. However, minimum front clearance when physically ac-
1 -
cessing the UPS must be at least the width of the front door of the UPS, or per NEC 110.34(A)(36 i n./900 mm) and local
requirements, whichever is greater.
2 - Approximate weights for dual-input units. Actual weights may vary depending on exact UPS configuration.
64
15kVA
930 lb (422 kg)
1170 lb (531 kg)
20.12 in x 37.4 in x 65.06 in (511 mm x 950 mm x 1653 mm)
1080 lb (490 kg)
1320 lb (599 kg)
46 in x 48 in x 90 in (1168 mm x 1219 mm x 2286 mm)
36 in (900 mm) Front
UL 1778, CUL, NEC (NFPS-70), CE, IBC, CBC, ANSI C62.41 (IEEE 587), Nema/PET-1993,
OSHA, ISO9000, ISO 14001:2004.
20kVA
935 lb (424 kg)
975 lb (510 kg)
1175 lb (533 kg)
1180 lb (535 kg)
1085 lb (492 kg)
1125 lb (510 kg)
1325 lb (601 kg)
1330 lb (603 kg)
/ 16 in (406 mm) Top / Zero clearance Sides/Back
1
NEMA 1
Welded Steel Chassis
Powder Coat, DuPont O'Brien Black
Yes
Touchscreen and LED
Touchscreen and LED
Yes
Yes
Yes – RemotEye 4
Yes
Yes
Yes
3 Years
4400 Series Installation and Operation Manual – 64527-008
25kVA
30kVA
985 lb (447 kg)
1185 lb (538 kg)
1135 lb (515 kg)
1335 lb (606 kg)