Charger Connection Note; Enable Ups External Battery Parameters; Remote On/Off; Remote On/ Off (Figure 2) - Toshiba 1600XPi Series Installation And Operation Manual

8-22kva battery cabinet
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

4.3

Charger Connection Note

The Battery cabinet model BC-1825 requires a 240 Vac connection between the UPS and battery cabinet
for battery charging. This connection is made from CN14A of the battery cabinet to CN14 of the UPS (and
CN14A of battery cabinet 2 to CN24 of battery cabinet 1 if paralleling cabinets). NOTE: Without this
connection the battery cabinet will not be able to charge its batteries.
5

Enable UPS External Battery Parameters

Set the UPS external battery parameters 222 and 223 to enable battery string monitoring of the external
battery cabinet(s).
1. Power on the UPS and Battery Cabinet(s).
2. Follow the instructions in the 1600XPi manual, 60616, to log in as Administrator.
3. Press the SETTING tab, then press Batt on the touchscreen.
4. Use the <<, <, >, and >> buttons to navigate to the parameters 522, 523, and 525-527. Entering
parameters 528 and 529 is optional (See Table 1 below).
5. Touch the parameter on the touchscreen to select it for editing. See the UPS manual 60616. Set per the
following table.
Parameter
522 Enable BC1
523 Enable BC2
524 External BC Status
525 No Ex Batt(Series)
526 No Ex Batt(Paral)
527 Ex Batt Rated Ahr
1
528 Ex Batt C Rate
1
529 Ex Batt Ins Date
1 – Parameter is informational only. Value is not used in calculations
6. Model BC-1825 requires a 240 Vac connection between the UPS and battery cabinet for battery charging.
This connection is made from CN14A of the battery cabinet to CN14 of the UPS (and CN14A of battery
cabinet 2 to CN24 of battery cabinet 1 if paralleling cabinets). NOTE: Without this connection the
battery cabinet will not be able to charge its batteries.
6.0

Remote ON/OFF

6.1

Remote ON/ OFF (Figure 2)

The Battery Cabinet does not have an EPO. The EPO on the UPS connects to the battery cabinet through
the battery cabinet connection cable between CN14 and CN14A. No other battery cabinet connection is
needed.
6.2

EPO Operation

Pressing the EPO will cause the breaker on the battery cabinet and the UPS, to switch to the OFF position
simultaneously, disabling both the battery cabinet and the UPS.
1600XPi Series Battery Cabinet Installation and Operation Manual 64024-006

Table 4 1600XPi Parameter Settings for H3B-BC-1825

Description
Enable External Batt. Cabinet 1
Enable External Batt. Cabinet 2)
External Battery Cabinet Status
Number of External Batt. Packs in Series String
Number of External Batt. Strings in Parallel
External Battery Capacity in A-hr
External Battery Cabinet Charge/Discharge
Rate
External Battery Installation Date
(e.g YYYMMDD)
UPS
UPS +
1
Only
1 BC
Disable
Enable
Disable
Disable
0
1
0
24
0
3
0
9
0
2
N/A
YYYYMMDD
UPS +
1
2 BC
Enable
Enable
1
24
6
9
2
YYYYMMDD
11