9.7
Control Wiring
TB3 provides terminals for connecting the UPS to external control functions. The functions of the terminal pairs are given
below.
TB3
(NO - Normally Open)
Terminals
(NC - Normally Closed)
1 & 2
3 & 4
5 & 6
7 & 8
(Configurable NO or NC
9 & 10
11 & 12
13 & 14
15 & 16
17 & 18
19 & 20
* Dry contacts.
** Controller board is programmed to accept momentary signals only. Signal duration of 20 seconds or greater will trigger
the warning LBABNL (Local Button Abnormal)
TB3 Terminals
1 thru 20
54
TABLE 9.6: TB3 TERMINAL FUNCTIONS
Status*
**
Function
,
NO*
Bypass Status - Bypass / Gnd (Closed when UPS is in Bypass mode)
NO*
EPO Status (Closed when UPS is shut down)
NO*
Remote EPO (Closing external switch will shut down the UPS)
Default: NC*
Battery Breaker Open/Battery Overheat Sense (Batt Cab CB Aux
Switch)
from Display)
NO**
P24 A3 / Remote Run (Closing user-supplied external switch will
Transfer UPS from Bypass to Online)
NO**
P24 A3 / Remote Stop (Closing user-supplied external switch will
transfer the UPS from Online to Bypass)
NO**
P24 / Charge Stop (Closing user-supplied external switch will stop the
UPS Battery Charger circuit)
–
Shunt Trip (Places Battery Breaker shunt trip coil in parallel with UPS
MCCB, so EPO will open both UPS and BC circuit breakers simulta-
neously)
NO
(Not Assigned)
NO
(Not Assigned)
TABLE 9.7: TB3 TERMINAL FASTENING TORQUE
Wire Size
14 – 16 AWG
Fastener Torque
8 in-lb (0.9 N∙m)