Table 3-7 Rating Of Contactors, Breakers, And Fuses; Table 3-8 Ac-Ac Efficiency Specifications - Toshiba G9400 Series Installation And Operation Manual

Table of Contents

Advertisement

DEVICE
NUMBER
CB1
CB2
CB3
52C
52S
88RC
User supply
User supply
User supply
FP, FC, FN
FBP, FBN
FBR1, FBR2, FBR3
FBR, FBS, FBT
FBO1, FBO2, FBO3
FOA, FOB, FOC
FIA, FIB
FUA, FUB, FUC
FSU, FSV, FSW
FCBV, FCBW
* Provides 100kAIC included from factory.
Rated Output Power
1200kVA / 1200kW
1600kVA / 1600kW
2000kVA / 2000kW
*Tentative values approximated from 2000kVA Testing
G9400 480V 1200-2000kVA Installation and Operation Manual 203078-001
Table 3–7 Rating of Contactors, Breakers, and Fuses
APPLICATION
AC input contactor
Battery contactor
STS contactor
Inverter output contactor
Bypass contactor
Control circuit contactor
Battery disconnect breaker
(Recommended)
AC input breaker
(Recommended)
Bypass input breaker
(Recommended)
DC fuse
DC fuse
Control power fuse
Control power fuse
Bypass input fuse*
Bypass input fuse*
Table 3–8 AC-AC Efficiency Specifications
30% Load
96.6%*
96.6%*
96.6%
OUTPUT CAPACITY OF EQUIPMENT
1200kVA
1200kW
704A
1992A
See Appendix A: Installation Planning Guide
See Appendix A: Installation Planning Guide
See Appendix A: Installation Planning Guide
2800A / 650V
50% Load
70% Load
97.0%*
97.0%*
97.0%*
97.0%*
97.0%
97.0%
1600kVA
2000kVA
1600kW
2000kW
520A
263A
(12kA for 3 sec)
520A
2843A
20A
315A / 690V
1250A / 690V
12A / 600V
12A / 600V
3600A / 550V
2000A / 500V
100% Load
96.9%*
96.9%*
96.9%