UNINTERRUPTIBLE POWER SYSTEM (UPS)
4200FA
INSTALLATION AND OPERATION MANUAL
Three-Phase 15/25/30/50 kVA UPS
Doc. Number: 53878-011
Date: May 2012

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba 4200FA

  • Page 1 UNINTERRUPTIBLE POWER SYSTEM (UPS) 4200FA INSTALLATION AND OPERATION MANUAL Three-Phase 15/25/30/50 kVA UPS Doc. Number: 53878-011 Date: May 2012...
  • Page 2 4200FA Installation and Operation Manual...
  • Page 3 4200FA THREE-PHASE 15/25/30/50 kVA UNINTERRUPTIBLE POWER SYSTEM USER’S MANUAL FOR all 15 – 50 kVA MODELS: TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Road Houston, TX 77041-9990 4200FA Installation and Operation Manual...
  • Page 4 4200FA Installation and Operation Manual...
  • Page 5: Important Notice

    UNINTERRUPTIBLE POWER SYSTEM If additional information or technical assistance is required call TOSHIBA Customer Support Center toll free at 1- 877-867-8773, or write to: Toshiba International Corporation, 13131 West Little York Road, Houston, TX 77041- 9990 Attn: UPS Product Manager.
  • Page 6: Purpose And Scope Of Manual

    TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual. Nor shall it be liable for incidental or consequential damages resulting from the use of information contained in this manual.
  • Page 7: Table Of Contents

    UPS Shutdown (via RS-232C) ....................32 Specifications ...................... 33 4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output - No Internal Batteries or Transformer 33 4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries ......34 4200FA 15/25 kVA w/Internal Transformer ...................
  • Page 8 Parts Replacement ........................69 External Dimensions / Shipping Dimensions / Weights ........70 External Dimensions – 15/25/30 kVA with Casters ............... 70 External Dimensions – 15/25/30 kVA without Casters..............71 External Dimensions – 50kVA with casters .................. 72 4200FA Installation and Operation Manual...
  • Page 9 External Dimensions – 50kVA without Casters ................73 Dimensions and Weights ......................74 Cabinet Color ..........................74 APPENDIX A – Seismic Anchorages ................75 APPENDIX B – Installation Planning Guides .............. 79 4200FA Installation and Operation Manual...
  • Page 10 (This Page Intentionally Left Blank) 4200FA Installation and Operation Manual...
  • Page 11: General Safety Instructions

    Explosion warning ─ The explosion warning symbol is an explosion image enclosed in a triangle. The Explosion warning symbol is used to indicate locations and conditions where molten exploding parts that may cause serious injury or death if the proper precautions are not observed. 4200FA Installation and Operation Manual...
  • Page 12: Equipment Warning Labels

    If the labels are damaged or if additional labels are required, contact your TOSHIBA representative for additional labels. The following are examples of the warning labels that may be found on the equipment. The labels are there to provide useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and equipment damage, or death if the instructions are not followed.
  • Page 13 While servicing, stand on some type of insulation, and be sure not to be grounded. Follow the safety instructions given in the equipment manual carefully and observe all danger, warning and caution notices. 40308 4200FA Installation and Operation Manual...
  • Page 14 NOTE: This Label for Battery Units Only 4200FA Installation and Operation Manual...
  • Page 15: Important Safety Instructions

    Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input. 3. Battery servicing should be performed by a qualified TOSHIBA Representative only. 4. Unauthorized personnel should not service batteries.
  • Page 16 UPS. The nominal battery voltage for all internal battery models is 288 VDC. The nominal battery voltage for all external battery models is 288 VDC. An Authorized TOSHIBA Representative who is knowledgeable of batteries and the required precautions should perform service on the batteries. Keep unauthorized personnel away from batteries.
  • Page 17 6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance. 4200FA Installation and Operation Manual...
  • Page 18: Instructions Importantes Concernant

    CONSERVER CES INSTRUCTIONS instructions importantes concernant la sécurté Un battery puet présenter un risque de choc électrique, de brûlure ATTENTION par transfert d’ énergie. L’élimination des batteries est règlementèe. Consultar les codes ATTENTION locaux à cet effet 4200FA Installation and Operation Manual...
  • Page 19: Product Description

    Product Description This manual covers all current variants of the 4200FA Series 15-50 kVA UPS. All variants of each capacity supply the same rated power and performance. The differences are listed below: • 4200FA Base Model – Basic version of 15-50kVA sizes, mounted on two C-channel skids, no integral maintenance bypass switch, no lockable On/Off switch, and no redundant dry contact terminal switch, and optional internal batteries.
  • Page 20: Product Unpacking / Inspection / Storage / Disposal

    UPS. See pg. 14. TOP HEAVY EQUIPMENT. IMPROPER LIFTING CAN RESULT IN INJURY OR DEATH. LIFT AND MOVE CAREFULLY AND ONLY WITH ADEQUATE DANGER EQUIPMENT AND TRAINED PERSONNEL. THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE. 4200FA Installation and Operation Manual...
  • Page 21: Unpack The Base And Seismic Model 15/25/30 Kva Ups (Without Casters)

    Unpack the Base and Seismic model 15/25/30 kVA UPS (without Casters) (4200FA Base, P/N C42F3FnnnXAXXN and C42F3FnnnXAXBN) (4200FA Seismic, P/N C42F3F250XAMX0S) Carefully inspect the UPS for shipping damage. Units shipped within North America and NAFTA are shrink-wrapped. Side view of 15/25/30kVA UPS 1.
  • Page 22: Unpack The Premium 50 Kva Ups (With Casters)

    See pg. 15. TOP HEAVY EQUIPMENT. IMPROPER LIFTING CAN RESULT IN INJURY OR DEATH. LIFT AND MOVE CAREFULLY AND ONLY WITH ADEQUATE EQUIPMENT AND TRAINED DANGER PERSONNEL. THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE. 4200FA Installation and Operation Manual...
  • Page 23: Unpack The Base And Seismic 50 Kva Ups (Without Casters)

    Unpack the Base and Seismic 50 kVA UPS (without Casters) 4200FA 50kVA Base (P/N T42F3F500XAXXN , T42F3F500XAXBN) 4200FA 50kVA Seismic (P/N T42F3F500XAMX0S) Upon receipt of the UPS, a careful inspection for shipping damage should be made. Units shipped within North America and NAFTA are shrink-wrapped; those outside North America are crated.
  • Page 24: Inspect Ups Equipment After Unpacking

    2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order specifications. Permanent Anchoring for Premium 15/25/30/50 kVA UPS (with Casters) Use the shipping rails for permanent anchoring of the castor-equipped 4200FA. 20” 36.3”...
  • Page 25: Permanent Anchoring For Base And Seismic Model 15/25/30/50 Kva Ups (Without Casters)

    38.3” 59.3” 30” 40” 13.5” Anchoring for 50 kVA 4200FA with Casters Permanent Anchoring for Base and Seismic model 15/25/30/50 kVA UPS (without Casters) 15/25/30 kVA Base/Seismic Anchoring Pattern 50 kVA Base/Seismic Anchoring Pattern (Middle top/bottom holes N/A for Base 50kVA) See Appendix A for fastener details.
  • Page 26: Storage Of Ups Equipment

    It is ILLEGAL to dump lead-acid batteries in landfills or dispose of ATTENTION improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call TOSHIBA toll-free at (877) 867-8773 for more information about recycling batteries. 4200FA Installation and Operation Manual...
  • Page 27: Installation Precautions

    3.0 Installation Precautions Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum amounts of unobstructed space around the unit are necessary for ventilation and maintenance access. The following section and Fig. 3.1 shows the minimum clearances required for proper UPS site installation.
  • Page 28: System Preparation (Pre-Power)

    LED’s have gone out before removing the front panel of the UPS after the UPS power has been turned off. Do not attempt to disassemble, modify, or repair the UPS. Call TOSHIBA Service for repair information.
  • Page 29: Ups Connections

    Input Terminals: 1 – 5 Output Terminals: 6 – 10 INPUT GROUND RESISTANCE LESS THAN 10 OHMS Optional Bypass Input: 3-phase, 3-Wire *208 V requires 3-phase, 4-Wire Wye * Customer-provided breaker for units with optional Bypass Input. 4200FA Installation and Operation Manual...
  • Page 30: Power Connections 15/25/30 Kva With Internal Transformer

    Input Terminals: 1 – 5 Output Terminals: 6 – 10 INPUT GROUND RESISTANCE LESS THAN 10 OHMS Optional Bypass Input: 3-Phase, 3-Wire *208 V requires 3-Phase, 4-Wire Wye * Customer-provided breaker for units with optional Bypass Input. 4200FA Installation and Operation Manual...
  • Page 31: Recommended Wire Size And Torque Requirements For 15/25/30Kva

    35 in-lbs. 8 – 1 51 in-lbs. 6 – 1 51 in-lbs. 600 V 10 – 1 35 in-lbs. 10 – 1 35 in-lbs. 10 – 1 35 in-lbs. *Maximum Wire Size is 1 AWG. 4200FA Installation and Operation Manual...
  • Page 32: Power Connection Cable Routing And Conduit Placement 15/25/30 Kva

    1) Input and Output conductors shall be installed in separate conduits, and installed in accordance with the latest edition of NEC and the Local Authority having jurisdiction. 2) Battery conductors shall be installed in a separate conduit and be of low resistance type. 4200FA Installation and Operation Manual...
  • Page 33: Control Circuit And External Battery Interface Connections 15/25/30 Kva

    (10) Remote Stop (Switch UPS to Static Bypass)* (11) Bypass (12) COMMON (13) EPO (24Vdc – 1A max.) (14) EPO (24Vdc – 1A max.) (15) – (24) Not Used *Must be programmed in via the front panel 4200FA Installation and Operation Manual...
  • Page 34: Recommended Wire Size And Torque Requirements

    CIRCUITS (3-6)* BATTERY 6 – 1 2 – 1 45 in-lbs. (+/-) *Indicates Class 1 wiring methods are to be used. Maximum Wire Size for Control Circuits is 12 AWG. Maximum for Battery is 1 AWG. 4200FA Installation and Operation Manual...
  • Page 35: Power Connections 50 Kva

    OUTPUT: 3-phase (4-wire) BATTERY 208 V requires 3-phase, 4-wire Optional: Bypass Input: 3-phase, 3-wire 208 V requires 3-phase, 50kVA with Back 4-wire Panel Removed (H1) (H2) (H3) Ground Lugs (2) Wire Capacity: #14 – 1/0 AWG 4200FA Installation and Operation Manual...
  • Page 36: Recommended Wire Size And Torque Requirements For 50Kva

    (USE MINIMUM 75 °C INSULATED COPPER WIRING) 50 kVA Input/ Output (GND) Tightening Torque 208-240 VAC 6 – 250 kcmil 200 in-lbs. 380-480 VAC 6 – 250 kcmil 200 in-lbs. 600 VAC 8 – 250 kcmil 200 in-lbs. 4200FA Installation and Operation Manual...
  • Page 37: Power Connection Cable Routing And Conduit Placement 50 Kva

    The following illustrates the proper cable routing that should be followed during the power connection process for the 50kVA. Note: Cabinet show with batteries, cabling is the same for units with internal batteries, internal transformers, and neither internal batteries nor transformers. 4200FA Installation and Operation Manual...
  • Page 38: Control Circuit And External Interface Connections 50 Kva

    (10) Remote Stop (Switch UPS to Static Bypass)* (11) Bypass (12) COMMON (13) EPO (24Vdc – 1A max.) (14) EPO (24Vdc – 1A max.) (15) – (18) Not Use *Must be programmed in via the front panel 4200FA Installation and Operation Manual...
  • Page 39: Recommended Wire Size And Torque Requirements

    TERMINAL TIGHTENING (TERMINAL #) AWG* TORQUE UPS CONTROL CIRCUITS 14-16 8 in-lbs. (1-24)* BATTERY CONTROL 14-16 8 in-lbs. CIRCUITS (3-6)* *Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG. 4200FA Installation and Operation Manual...
  • Page 40: Communication Interface

    1) Pin “switches” are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be connected to System Common). 2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps. 3) Pin number “3” is not used. 4200FA Installation and Operation Manual...
  • Page 41: Rs-232C

    RemotEye II Mounting Location – 15-30kVA RemotEye II Mounting Location – 50kVA This interface allows control of the UPS from a computer network running TOSHIBA RemotEyeII software. The computer and the UPS are connected through a serial RS-232C communication port.
  • Page 42: Ups Shutdown (Via Rs-232C)

    The UPS can be programmed to turn OFF up to 8 minutes after the 'shutdown' command is given. This command can be cancelled before the specified time has elapsed by following the directions listed on the RS-232C screen. 4200FA Installation and Operation Manual...
  • Page 43: Specifications

    5.0 Specifications 4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output - No Internal Batteries or Transformer C42F3F150XAXXN C42F3F250XAXXN Model Number C42F3F150XAMXN, -S C42F3F250XAMXN, -S C42F3F150FAMXN, -S C42F3F250FAMXN, -S 15 kVA 25 kVA Rated Output Capacity External Dimensions w/ casters: 20.0”...
  • Page 44: 4200Fa 15 / 25 Kva @ 208 Vac Input/ 208 Vac Output W/Internal Batteries

    4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries C42F3F150XAXBN C42F3F250XAXBN Model Number C42F3F150XAMBN C42F3F250XAMBN C42F3F150FAMBN C42F3F250FAMBN Rated Output Capacity 15 kVA 25 kVA External Dimensions w/ casters: 20.0” x 36.3” x 59.7”(50.8 cm x 92.2 cm x 151.6 cm) W x D x H (cm) w/o casters: 20.0”...
  • Page 45: 4200Fa 15/25 Kva W/Internal Transformer

    4200FA 15/25 kVA w/Internal Transformer Model Number C42#3*150#AMXN, -S C42#3*250#AMXN, -S # =(B: 208; H: 220; C: 240; N: 380–415 ∆-wye; P: 380–415 wye; D: 480; Input M: 600) VAC Output *=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600) VAC...
  • Page 46: 4200Fa 30 Kva @ 208 Vac Input/ 208 Vac Output - No Internal Batteries, No Internal

    4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output - No Internal Batteries, No Internal Transformer T42F3F300XAXXN Model Number T42F3F300XAMXN, -S T42F3F300FAMXN, -S Rated Output Capacity 30 kVA External Dimensions w/ casters: 20.0” x 36.3” x 59.7”(50.8 cm x 92.2 cm x 151.6 cm) W x D x H (cm) w/o casters: 20.0”...
  • Page 47: 4200Fa 30 Kva @ 208 Vac Input/ 208 Vac Output W/Internal Batteries

    4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries T42F3F300XAXBN Model Number T42F3F300XAMBN T42F3F300FAMBN Rated Output Capacity 30 kVA External Dimensions w/ casters: 20.0” x 36.3” x 59.7”(50.8 cm x 92.2 cm x 151.6 cm) W x D x H (cm) w/o casters: 20.0”...
  • Page 48: 4200Fa 30 Kva W/Internal Transformer

    4200FA 30 kVA w/Internal Transformer Model Number T42#3*300#AMXN, -S # =(B: 208; H: 220; C: 240; N: 380–415 ∆-wye; P: 380–415 wye; Input D: 480; M: 600) VAC *=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye:...
  • Page 49: 4200Fa 50Kva @ 208 Vac Input/ 208 Vac Output - No Internal Batteries, No Internal

    4200FA 50kVA @ 208 VAC Input/ 208 VAC Output - No Internal Batteries, No Internal Transformer T42F3F500XAXXN Model Number T42F3F500XAMXN, -S T42F3F500FAMXN, -S 50 kVA Rated Output Capacity External Dimensions w/ casters: 35.5” X 38.3” X 59.3” (90.1 cm x 97.2 cm x 150.6 cm) W x D x H (cm) w/o casters: 35.5”...
  • Page 50: 4200Fa 50Kva @ 208 Vac Input/ 208 Vac Output W/Internal Batteries

    4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries T42F3F500XAXBN Model Number T42F3F500XAMBN T42F3F500FAMBN Rated Output Capacity 50 kVA External Dimensions w/ casters: 35.5” X 38.3” X 59.3” (90.1 cm x 97.2 cm x 150.6 cm) W x D x H (cm) w/o casters: 35.5”...
  • Page 51: 4200Fa 50Kva W/Internal Transformer

    4 – Prolonged operation at this level requires derating of the maximum Operating Temperature to 90 °F ( 32 °C). 5 – SHORT TERM operation only (e.g. Brownouts). Operation at this level requires derating the maximum Operating Temperature to 95 °F ( 35 °C). 4200FA Installation and Operation Manual...
  • Page 52: 4200Fa Efficiencies And Thermal Losses At Various Loads

    0% Load 2,730 4,077 4,892 6,403 5.10.5 Eff. Vs. Load Table – 4200FA with Input and Output Transformers * 15 kVA w/ 2 Xfmr 25 kVA w/2 Xfmr 30 kVA w/2 Xfmr 50 kVA w/ 2 Xfmr 100% Load * 85.1%...
  • Page 53: Operating The Ups

    UPS is in the “Normal Operation Mode.” (Not available for LT units) Power Flow Bypass MCCB Output Input Isolating Converter Inverter Power XFMR Power Charger/ Chopper External Batteries Power flow in AC Input Mode 4200FA Installation and Operation Manual...
  • Page 54: Bypass Mode

    Bypass Mode for Optional Alternate Input Models Power Flow (Not available for LT units) Bypass Bypass Power MCCB Isolating Output Input Converter Inverter Power Power XFMR Charger/ Chopper External Batteries Power flow in Bypass mode for the Alternate Input Models 4200FA Installation and Operation Manual...
  • Page 55: Battery Backup Mode

    This minimum level is the rated minimum voltage (V min). (Not available for LT units) Bypass MCCB Output Isolating Converter Inverter Power XFMR Charger/ Chopper External Batteries Power flow in battery backup mode 4200FA Installation and Operation Manual...
  • Page 56: Battery Backup Time And Discharge Process

    Battery Backup Time and Discharge Process The UPS system, when used in conjunction with a TOSHIBA designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value.
  • Page 57: Battery Recharging

    50 kVA Model Internal Internal Internal Internal Battery Transformer Battery Transformer V float 324.0 VDC 324 VDC 324 VDC V min 216 VDC 216 VDC 216 VDC I charge 4.0 A 10.0 A 11.5 Amps 4200FA Installation and Operation Manual...
  • Page 58: Front Panel Layout (All Units)

    EPO switch. Use the Start-up Procedure for restarting the unit. (Not available for LT units) Power Flow Bypass TRIPPED MCCB Output Input Isolating Converter Inverter Power XFMR Power Charger/ Chopper External Batteries 4200FA Installation and Operation Manual...
  • Page 59: Audible Alarm Functions

    BATT lamp will flicker on and off slowly (1.2 second on and 1.2 second off). The BATT LED will go off if the battery voltage reaches the shutdown level during the battery-discharge mode. On when the UPS is experiencing a fault. 4200FA Installation and Operation Manual...
  • Page 60: Led (Light Emitting Diode) System Status

    Displayed during power failure if V (min.) is reached, an EPO is received, or after - OUTPUT SHUTDOWN - completion of Shutdown Sequence of the Inverter and Bypass is not available. - BATTERY BACKUP - Displayed during input power failure. 4200FA Installation and Operation Manual...
  • Page 61: Line-2 System Fault Messages

    (Normal) Displayed when key switch position is changed and * TRANSFER INHIBITED * frequency is not synchronized. (Abnormal) Displayed when a Fault or Faults have occurred. * ENTER FOR DETAILS * (Abnormal) 4200FA Installation and Operation Manual...
  • Page 62: Menu Tree

    2) Move the UPS MCCB (Circuit Breaker 1) power switch on the inner front panel to "on." The UPS battery charging circuit is now activated. The AC IN lamp will be "on." The LCD screen should display the following message: - UPS START UP - > PLEASE WAIT 4200FA Installation and Operation Manual...
  • Page 63: Start-Up Procedure

    With the key switch in the “STOP” position, both the AC IN and the BYP lamp will be "on" and the LCD screen should display the following message: - BYPASS OPERATION – OUTPUT VOLTAGE=208 V >CURRENT 100/80/90% DATE (DAY) TIME 4200FA Installation and Operation Manual...
  • Page 64: Shutdown Procedure

    OUTPUT VOLTAGE= 0 V CURRENT=LOW/LOW/LOW% When the EPO (Emergency Power Off) switch, located on the front panel (or from a remote located EPO switch) is pushed, the Circuit Breaker is tripped and power is removed from 4200FA Installation and Operation Manual...
  • Page 65: Maintenance Bypass Procedure

    3) Locate the maintenance bypass rotary cam switch (middle of inner front panel of the UPS); slowly rotate the cam switch clockwise to the “BYPASS MODE” position. (For the 25/50kVA 4200FA Base models, see Section 6.17 Note) 4) Turn off MCCB breaker labeled “MAIN POWER SWITCH."...
  • Page 66 5) Turn the “STOP/RUN” switch to the “RUN” position. 6) Verify that the Inverter indicator light on the front panel is lit. The unit is now back On-Line and supplying conditioned power to the load. 4200FA Installation and Operation Manual...
  • Page 67: Keypad Overview

    Reset – Press to reset UPS panel’s message-display area. Up Arrow – Press to forward through display data values or to forward through menus. Down Arrow – Press to reverse through display data values or to reverse through menus. 4200FA Installation and Operation Manual...
  • Page 68: Key Functions

    Ia = 100% CURRENT Ib = 100% Ic = 100% The Output Line Voltages (phase-neutral, and phase to phase), Frequencies / Sync Mode, Inverter Output Power, and Power factor can be monitored by pressing the "up/down" keys. 4200FA Installation and Operation Manual...
  • Page 69: Batt Key

    Press the F1+ ENTER keys at the same time to begin the battery test and to display the following screen while batteries are tested: - BATTERY TEST - BATTERY VOLTAGE=324V ## MINS ## SECS > PLEASE WAIT 4200FA Installation and Operation Manual...
  • Page 70: Buzz Stop Key

    - DISPLAY ERROR - MAIN COMM. ERROR PRESS & HOLD RESET KEY If the 'Reset' function is successful then the display will begin from the 'Start-up screen' and then change to the 'main monitor' screen. 4200FA Installation and Operation Manual...
  • Page 71: Menu Data Screens

    When setting this feature, press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the LCD-Idle Mode Select screen display: DISPLAY DURATION SET <3 MIN> 30 MIN >F1: DATA SET MODE >∆/∇:PRV/NEXT SCREEN 4200FA Installation and Operation Manual...
  • Page 72: Run Switch Select

    SER COM STATION ADDR STATION ADDRESS: >*F1: DATA SET MODE > ∆/∇: PRV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: SER COM STATION ADDR STATION ADDRESS: >∆/∇: CHANGE DATA >ENTER: ACCEPT CHANGE 4200FA Installation and Operation Manual...
  • Page 73: Output Voltage Adjustment

    Pressing the F1 key will have no effect on this display screen 6.20.7 Equalize Charge Mode Select Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option. DAMAGE to the battery system may occur if this option is used improperly.
  • Page 74: Reset To Default Settings

    If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the overload condition is still present, the following screen will be displayed: - BYPASS OPERATION - OUTPUT VOLTAGE=208 CURRENT= 114/116/114% * UPS OL: REDUCE LOAD * 4200FA Installation and Operation Manual...
  • Page 75: Backup History And Fault History

    # TIMES > F1: FOR DETAILS >∆/∇: TO SCROLL Press the F1 key to display the record relating to the first discharge event. BACKUP HISTORY ( 1) #MIN##SEC VB=324V BT *PF OL >∆/∇: EXIT F1: NEXT 4200FA Installation and Operation Manual...
  • Page 76 FAULT HISTORY ( #) Date Time fault code >∆/∇: EXIT F1: NEXT Press the ‘up’ or ‘down’ arrow keys to return to the Fault Count screen. TOTAL FAULT COUNT ## TIMES > F1: FOR DETAILS >∆/∇: TO SCROLL 4200FA Installation and Operation Manual...
  • Page 77: Ups Protection System

    If Bypass ok, transfer to bypass; if not, current-limit Battery Discharge after Fault No Output mode Audible Alarm Yes: See Audible Alarm Functions Visible Alarm Battery Lamp Flickers Relay Contact Low Battery Relay Bypass Relay closed Alarm closed Auto-Retransfer Yes, if bypass ok 4200FA Installation and Operation Manual...
  • Page 78: Start-Up / Scheduled Maintenance / Part Replacement

    Maintenance Bypass. Preventive Maintenance The 4200FA Uninterruptible Power Systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance. The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
  • Page 79: Parts Replacement

    C. Optionally test for the purpose of trending the battery over time. D. Re-torque all inter-battery connecting hardware (if applicable). 2) Aluminum electrolytic capacitors: Replace once every 5 years. 3) Fuses: Replace once every 7 years. 4) Cooling fan: Replace once every 3 years. 4200FA Installation and Operation Manual...
  • Page 80: External Dimensions / Shipping Dimensions / Weights

    9.0 External Dimensions / Shipping Dimensions / Weights External Dimensions – 15/25/30 kVA with Casters 36.3 in. (922 mm) 4200FA Installation and Operation Manual...
  • Page 81: External Dimensions - 15/25/30 Kva Without Casters

    External Dimensions – 15/25/30 kVA without Casters 4.1 in. (104 mm) Floor to Conduit knockout plate 4200FA Installation and Operation Manual...
  • Page 82: External Dimensions - 50Kva With Casters

    External Dimensions – 50kVA with casters 35.5 in. (901 mm) 59.3 in. (1506 mm) 4.5 in. (114 mm) Floor to Conduit 38.3 in. knockout plate (972 mm) 4200FA Installation and Operation Manual...
  • Page 83: External Dimensions - 50Kva Without Casters

    External Dimensions – 50kVA without Casters (LT version does not have the middle C-channel skid) 4.9 in. (125 mm) Floor to Conduit knockout plate 4200FA Installation and Operation Manual...
  • Page 84: Dimensions And Weights

    633 lb (287 kg) 739 lb (335 kg) 50 kVA 1221 lb (554 kg) 2548 lb (1156 kg) Cabinet Color All UPS cabinets are colored “White-Gray” Trimite C09079PA80123 Beige, Eggshell Texture (or Sherwin Williams HHT2-70055079 Beige Texture.) 4200FA Installation and Operation Manual...
  • Page 85: Appendix A - Seismic Anchorages

    APPENDIX A – Seismic Anchorages 4200FA Installation and Operation Manual...
  • Page 86 4200FA Installation and Operation Manual...
  • Page 87 4200FA Installation and Operation Manual...
  • Page 88 4200FA Installation and Operation Manual...
  • Page 89: Appendix B - Installation Planning Guides

    Professional Engineer within your local area for proper size selections. TOSHIBA INTERNATIONAL CORPORATION 13131 West Little York Road Houston, TX 77041 Telephone: 800.231.1412; 713.466.0277 Fax: 713.896.5212 Corporate Web Site: www.tic.toshiba.com Group Web Site: www.toshibaups.com 4200FA Installation and Operation Manual...
  • Page 90 60 A (1) x 6 / (1) x 4 90 A (1) x 3 / (1) x 1 110 A (1) x 2 / (1) x 1 175 A (1) x 2/0 / (1) 250 4200FA Installation and Operation Manual...
  • Page 91 60 A (1) x 6 / (1) x 4 90 A (1) x 3 / (1) x 1 110 A (1) x 2 (1) x 3/0 175 A (1) x 2/0 / (1) x 250 4200FA Installation and Operation Manual...
  • Page 92 30 A (1) x 8 / (1) x 8 50 A (1) x 8 / (1) x 4 60 A (1) x 6 / (1) x 3 100 A (1) x 3 / (1) x 2/0 4200FA Installation and Operation Manual...
  • Page 93 60 A (1) x 6 / (1) x 4 90 A (1) x 3 / (1) x 1 110 A (1) x 2 / (1) x 1 175 A (1) x 2/0 / (1) x 250 4200FA Installation and Operation Manual...
  • Page 94 25 A (1) x 10 / (1) x 8 40 A (1) x 8 / (1) x 6 45 A (1) x 8 / (1) x 4 75 A (1) x 4 / (1) x 2 4200FA Installation and Operation Manual...
  • Page 95 60 A (1) x 6 / (1) x 4 90 A (1) x 3 / (1) x 1 110 A (1) x 2 / (1) x 1 175 A (1) x 2/0 / (1) x 250 4200FA Installation and Operation Manual...
  • Page 98 INDUSTRIAL DIVISION 13131 West Little York Rd., Houston, TX 77041 Tel: 713/466-0277 Fax 713/466-8773 US 877/867-8773 Canada 800/872-2192 Mexico 01/800/527-1204 www.toshiba.com/ind Printed in the U.S.A.