8.5
80-100kVA Anchorage - Standard
Install the anchor bolts per Section 8.3 in the pattern shown in Figure 8.6.
Secure the UPS Angle Bracket skids to the floor with the anchor bolts..
80 kVA FOOTPRINT - BOTTOM VIEW
2.5 in (64 mm)
27.1 in (689 mm)
2.0 in (51 mm)
Angle Bracket
Skids
FRONT
80kVA ANCHORAGE SPACING
Back
4 x 0.703 in Dia. (17.9 mm)
Front
27.1 in (689 mm)
FIGURE 8.6: ANCHORAGE HOLE LOCATIONS – 80KVA UNITS (STANDARD)
30
4400 Series Installation and Operation Manual – 64527-008