Toshiba 1400 series; 1400 plus series ups (31 pages)
Summary of Contents for Toshiba 4200FA CT/XT
Page 1
TOSHIBA NINTERRUPTIBLE OWER YSTEM THREE-PHASE 15/25/30/50 kVA UPS 4200FA CT/XT User’s Manual Document Number: 53878-006 Date: September 2007...
Page 2
TOSHIBA 4200FA CT/XT THREE-PHASE 15/25/30/50 kVA UNINTERRUPTIBLE POWER SYSTEM CT-Internal Batteries XT- External Batteries or External Transformer USER’S MANUAL FOR MODELS C42F3F150X#MBN C42F3F150F#MBN C42#3#150##MXN C42F3F250X#MBN C42F3F250F#MBN C42#3#250##MXN T42F3F300X#MBN T42F3F300F#MBN T42#3#300##MXN T42F3F500XAMBN T42F3F500F#MBN T42#3#500##MXN TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Road...
UNINTERRUPTIBLE POWER SYSTEM If additional information or technical assistance is required call TOSHIBA Customer Support Center toll free at 1- 877-876-8773, or write to: Toshiba International Corporation, 13131 West Little York Road, Houston, TX 77041- 9990 Attn: UPS Product Manager.
IMPORTANT NOTICE... 2 TABLE OF CONTENTS... 3 Purpose and Scope of Manual ... 5 Contacting TOSHIBA Customer Support Center ... 5 GENERAL SAFETY INSTRUCTIONS... 6 EQUIPMENT WARNING LABELS ... 7 IMPORTANT SAFETY INSTRUCTIONS ... 10 Product Description... 14 Theory of Operation ... 14 Application and Use ...
TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual. Nor shall it be liable for incidental or consequential damages resulting from the use of information contained in this manual.
Explosion warning ─ The explosion warning symbol is an explosion image enclosed in a triangle. The Explosion warning symbol is used to indicate locations and conditions where molten exploding parts that may cause serious injury or death if the proper precautions are not observed. 4200FA CT/XT User’s Manual TOSHIBA...
If the labels are damaged or if additional labels are required, contact your TOSHIBA representative for additional labels. The following are examples of the warning labels that may be found on the equipment. The labels are there to provide useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and equipment damage, or death if the instructions are not followed.
Page 9
While servicing, stand on some type of insulation, and be sure not to be grounded. Follow the safety instructions given in the equipment manual carefully and observe all danger, warning and caution notices. 4200FA CT/XT User’s Manual TOSHIBA DANGER RISK OF ELECTRIC SHOCK Capacitors stay charged after power has been shut off.
Page 10
TOSHIBA NOTE: This Label for Battery Units Only 4200FA CT/XT User’s Manual...
Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input. 3. Battery servicing should be performed by a qualified TOSHIBA Representative only. 4. Unauthorized personnel should not service batteries.
Page 12
UPS. The nominal battery voltage for all internal battery models is 288 VDC. The nominal battery voltage for all external battery models is 288 VDC. An Authorized TOSHIBA Representative who is knowledgeable of batteries and the required precautions should perform service on the batteries. Keep unauthorized personnel away from batteries.
Page 13
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance. 4200FA CT/XT User’s Manual TOSHIBA...
Page 14
INSTRUCTIONS IMPORTANTES CONCERNANT CONSERVER CES INSTRUCTIONS ATTENTION ATTENTION 4200FA CT/XT User’s Manual TOSHIBA LA SÉCURITÉ Un battery puet présenter un risque de choc électrique, de brûlure par transfert d’ énergie. L’élimination des batteries est règlementèe. Consultar les codes locaux à cet effet...
Application and Use The TOSHIBA 4200FA On-Line, Uninterruptible Power Systems (UPS) provide continuous computer grade isolated AC power in a compact, efficient, high performance unit. The UPS assures safe, reliable operation of critical office equipment, ranging from personal computers to mini-computers to local area networks (LAN).
Attach the rails as shown in the front to the front of the pallet. DANGER 4200FA CT/XT User’s Manual TOSHIBA remove the screws that attach the shipping crate to the pallet. Remove the crate and foam packing material.
3. Place the tie brackets in the slots at the lower end of the ramps. SLOWLY roll the unit down th ramp. DANGER 4200FA CT/XT User’s Manual TOSHIBA Remove packing material. For international units, remove the screws that attach the shipping crate to the pallet.
It is ILLEGAL to dump lead-acid batteries in landfills or dispose of ATTENTION improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call TOSHIBA toll-free at (877) 867-8773 for more information about recycling batteries. 4200FA CT/XT User’s Manual...
If such interference occurs, the UPS should either be installed farther away from the affected equipment and/or powered from a different source than the affected equipment. 4200FA CT/XT User’s Manual TOSHIBA LEFT 6” (152mm) REAR 6” (152mm) RIGHT 6”...
CHARGE LED has gone out before removing the front panel of the UPS once the UPS power has been turned off. Do not attempt to disassemble, modify, or repair the UPS. Call TOSHIBA Service for repair information. Turn the power on only after attaching ALL the covers and DO NOT remove any covers of the UPS when the power is on.
3-phase, 3-Wire *208 V requires 3-phase, 4-Wire Wye 4200FA CT/XT User’s Manual TOSHIBA When the UPS is in the Inverter mode, turning the breaker to the OFF position will cause the unit to go into the battery backup mode. The Do not EPO (Emergency Power OFF) the UPS and then reset the breaker until the UPS has been fully discharged.
UPS) to the terminal block of the 15/25/30 kVA UPS Models TO BATTERY SYSTEM GND Optional Bypass Input: 3-Phase, 3-Wire *208 V requires 3-Phase, 4-Wire Wye 4200FA CT/XT User’s Manual TOSHIBA CUSTOMER-PROVIDED AC DISTRIBUTION PANEL INPUT GROUND RESISTANCE LESS THAN 10 OHMS...
208 V 220 V 240 V 380 V 400 V 415 V 480 V 600 V Maximum Wire Size is 2 AWG. 4200FA CT/XT User’s Manual TOSHIBA 25 kVA Torque Torque 51 in-lbs. 51 in-lbs. 51 in-lbs. 51 in-lbs. 51 in-lbs.
1) Input and Output conductors shall be installed in separate conduits, and installed in accordance with the latest edition of NEC and the Local Authority having jurisdiction. 2) Battery conductors shall be installed in a separate conduit and be of low resistance type. 4200FA CT/XT User’s Manual TOSHIBA OUTPUT CONDUIT...
CIRCUITS (3-6)* BATTERY (+/-) *Indicates Class 1 wiring methods are to be used. Maximum Wire Size for Control Circuits is 12 AWG. Maximum for Battery is 2 AWG. 4200FA CT/XT User’s Manual TOSHIBA Battery Connection (+) Positive Negative 15/25/30 kVA...
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 50 kVA UPS Model (H1) (H2) (H3) (N) INPUT: 3-phase, 3-wire 208 V requires 3-phase, 4-wire 4200FA CT/XT User’s Manual TOSHIBA (L1) (L2) (L3) OUTPUT: 3-phase (4-wire) (H1)
415 V 480 V 600 V Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM. 4200FA CT/XT User’s Manual TOSHIBA Minimum Wire Size and Torque Requirements UPS Input and Output Terminals 50 kVA NEUTRAL...
Power Connection Cable Routing and Conduit Placement 50 kVA The following illustrates the proper cable routing that should be followed during the power connection process for the 50kVA. Removable cover for conduit access 4200FA CT/XT User’s Manual TOSHIBA Bottom Conduit Entry...
1) Pin “switches” are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be connected to System Common). 2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps. 3) Pin number “3” is not used. 4200FA CT/XT User’s Manual TOSHIBA 5 System Common DB9 Male Connector Outline...
The RS-232C serial communication interface is available through a DB9 female connector located on the inside of the UPS. This interface allows control of the UPS from a computer network running TOSHIBA RemotEyeII™ software. The computer and the UPS serial RS-232C communication port. The available data from the UPS, via the RS-232C...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User’s Manual TOSHIBA...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User’s Manual TOSHIBA...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User’s Manual TOSHIBA...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User’s Manual TOSHIBA Input # =(B: 208;...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). (****) Prolonged operation at this level requires some derating of the output capacity. 4200FA CT/XT User’s Manual TOSHIBA T42F3F500XAMBN...
24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). (****) Prolonged operation at this level requires some derating of the output capacity. 4200FA CT/XT User’s Manual TOSHIBA Input # =(B: 208;...
The batteries are maintained in a constantly charged state when the UPS is in the “Normal Operation Mode.” Power Flow Input Isolating Power XFMR 4200FA CT/XT User’s Manual TOSHIBA Bypass MCCB Converter Charger/ Chopper...
Bypass Mode for Optional Alternate Input Models Power Flow Bypass Power Input Isolating Power XFMR Power flow in Bypass mode for the Alternate Input Models 4200FA CT/XT User’s Manual TOSHIBA Bypass MCCB Converter Charger/ Chopper External Batteries Power flow in Bypass mode...
When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (V min). MCCB Isolating XFMR 4200FA CT/XT User’s Manual TOSHIBA Bypass Converter Inverter...
Battery Backup Time and Discharge Process The UPS system, when used in conjunction with a TOSHIBA designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value.
'EMERGENCY OFF' screen. The following figure shows the UPS condition after application of the EPO switch. Use the Start-up Procedure for restarting the unit. Power Flow Input Isolating Power XFMR 4200FA CT/XT User’s Manual TOSHIBA Emergency Emergency Power Off switch power off switch (see Section 6.9) (see Section 6.6)
BATT lamp will flicker on and off slowly (1.2 second on and 1.2 second off). The BATT LED will go off if the battery voltage reaches the shutdown level during the battery-discharge mode. On when the UPS is experiencing a fault. 4200FA CT/XT User’s Manual TOSHIBA Audible pattern .5 S .5 S...
- BYPASS OPERATION - - UPS ON-LINE - - BATTERY DISCHARGE - - OUTPUT SHUTDOWN - - BATTERY BACKUP - 4200FA CT/XT User’s Manual TOSHIBA ON/OFF STATUS (After EPO received (Emergency Power Off )) LINE-1 MESSAGES Displayed when UPS is in the start-up condition or display board is resetting.
2) Allow 24-72 hours for the batteries to charge and then move the Circuit Breaker to "off." 3) Repeat Initial Battery Charge procedure. (A failure indicates battery replacement may be necessary). 4200FA CT/XT User’s Manual TOSHIBA - UPS START UP - > PLEASE WAIT...
If a fault occurs during start-up, the red FAULT lamp will be "on" and the LCD screen will display a FAULT(s) DETECTED at start-up message such as the following: Refer to the "Line-2 System Fault Messages" section for details. 4200FA CT/XT User’s Manual TOSHIBA - UPS START UP - >...
Failure to adhere to the following instructions could result in damage to your WARNING equipment and/or you risk removal of power to any equipment attached to the UPS. 4200FA CT/XT User’s Manual TOSHIBA BYPASS OPERATION OUTPUT VOLTAGE=208 >CURRENT 100/100/100%...
Page 50
5) Rotate the “STOP/RUN” switch to the “RUN” position. 6) Verify that the Inverter indicator light on the front panel is lit. The unit is now back On-Line and supplying conditioned power to the load. 4200FA CT/XT User’s Manual TOSHIBA...
Press to reset UPS panel’s message-display area. RESET Press to forward through display data values or to forward through menus. Press to reverse through display data values or to reverse through menus. 4200FA CT/XT User’s Manual TOSHIBA BATT BATT TEST...
The Output Line Voltages (phase-neutral, and phase to phase), Frequencies / Sync Mode, Inverter Output Power, and Power factor can be monitored by pressing the "up/down" keys. 4200FA CT/XT User’s Manual TOSHIBA - UPS ON-LINE - OUTPUT VOLTAGE= 208 V...
The following system message is displayed: Press the F1+ ENTER keys at the same time to begin the battery test and to display the following screen while batteries are tested: 4200FA CT/XT User’s Manual TOSHIBA - UPS ON-LINE - BATTERY VOLTAGE=324V CHARGE CURR.=0%...
15 seconds, a fatal time-out occurs and the following system message displays: If the 'Reset' function is successful then the display will begin from the 'Start-up screen' and then change to the 'main monitor' screen. 4200FA CT/XT User’s Manual TOSHIBA - UPS ON-LINE -...
When setting this feature, press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the LCD-Idle Mode Select screen display: Press the F1 key to display the LCD-Idle mode setting adjustment screen: 4200FA CT/XT User’s Manual TOSHIBA CALENDER / CLOCK DATE (DAY) TIME >*F1: DATA SET MODE...
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the “Serial Comm Station Address” setting screen display: Press the F1 key to display the following active adjustment screen: 4200FA CT/XT User’s Manual TOSHIBA DISPLAY DURATION SET <3 MIN>...
Pressing the F1 key will have no effect on this display screen 6.19.7 Equalize Charge Mode Select Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option. DAMAGE to the battery system may occur if this option is used improperly.
If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the overload condition is still present, the following screen will be displayed: 4200FA CT/XT User’s Manual TOSHIBA MENU DATA RESET DATA INITIALIZATION >F1: TO ACCESS RESET...
Pressing the MONI and F1 keys simultaneously, for a few seconds will cause the Battery Discharge Count screen to be displayed. Press the F1 key to display the record relating to the first discharge event. 4200FA CT/XT User’s Manual TOSHIBA - BYPASS OPERATION -...
Page 60
Press the F1 key to display the record relating to the first fault. Press the F1 key again to display the record relating to each subsequent fault. Press the ‘up’ or ‘down’ arrow keys to return to the Fault Count screen. 4200FA CT/XT User’s Manual TOSHIBA BACKUP HISTORY ( #)
Maintenance Bypass. Preventive Maintenance The TOSHIBA 4200FA Uninterruptible Power Systems have been designed to provide no years of trouble-free operation requiring a minimum of preventive maintenance. The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
C. Optionally test for the purpose of trending the battery over time. D. Re-torque all inter-battery connecting hardware (if applicable). 2) Aluminum electrolytic capacitors: Replace once every 5 years. 3) Fuses: Replace once every 7 years. 4) Cooling fan: Replace once every 3 years. 4200FA CT/XT User’s Manual TOSHIBA...
50 kVA with internal battery 50 kVA with no internal transformer or battery 50 kVA with 1 internal transformer 50 kVA with 2 internal transformers 4200FA CT/XT User’s Manual TOSHIBA Shipping Dimensions, Standard Inches (cm) 42.8 (109) 49.0 (125) 64.6 (164) 67.6 (172)
Page 68
INDUSTRIAL DIVISION 13131 West Little York Rd., Houston, TX 77041 Tel: 713/466-0277 Fax 713/466-8773 US 877/867-8773 Canada 800/872-2192 Mexico 01/800/527-1204 www.toshiba.com/ind Printed in the U.S.A.