External Breakers; Grounding Wire - Toshiba G8000 SERIES Installation And Operation Manual

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

11.4

External Breakers

The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the
external breakers for the AC input/output, bypass input and DC input.
See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.
Table 11.7 shows the G8000 UPS minimum external breaker rating for each capacity. The Bypass, AC
Input, and AC Output require 3-pole breakers.
C
apaCity
O
80 kVA
480 V/277 V
100 kVA
480 V/277 V
125 kVA
480 V/277 V
150 kVA
480 V/277 V
225 kVA
480 V/277 V
300 kVA
480 V/277 V
500 kVA
480 V/277 V
11.5

Grounding Wire

Be sure to ground the UPS as specified.
Using the UPS without a proper ground will deteriorate the insulation,
cause leakage of currents and electric shock.The resistance to ground
should be less than or equal to 10 ohms.
The 80/100/150/225kVA earth grounding bus' are located inside, at the bottom-front of the unit.
The 300 kVA earth grounding bus is located inside, at the top-left of the unit.
The 500 kVA earth grounding bus is located inside, at the bottom front of the units.
Use a AWG 2 (or 38 mm
opening at the bottom, or through a hole in the top conduit landing plate (if available). See Figure 11.12.
Connect either the top or bottom earth ground bus, but not both, to the grounding wire.
The ground wire must have a crimp terminal with a 1/2 in. (12 mm) diameter bolt hole. The ground bus has
33/64 in. (13 mm) bolt hole. The connect the crimp terminal and ground bus together using a 7/16 in. (10
mm) diameter bolt.
42
TABLE 11.7 UPS MINIMUM DEVICE RATINGS
R
i
B
ated
nput
ReakeR
R
utput
ating
480 V – 150 A
480 V – 200 A
480 V – 200 A
480 V – 300 A
480 V – 400 A
480 V – 600 A
480 V – 800 A
WARNING
) or larger cable for the grounding wire. Run the grounding wire through the
2
O
B
dC i
utput
ReakeR
R
B
ating
ReakeR
480 V – 125 A
500 VDC – 300A
480 V – 150 A
500 VDC – 350A
480 V – 200 A
500 VDC – 400A
480 V – 250 A
500 VDC – 600A
480 V – 350 A
500 VDC – 900A
480 V – 500 A
500 VDC – 1200A
480 V – 800 A
600 VDC – 1200A
G8000 Series Installation and Operation Manual
nput
R
ating