Main circuit connection

3.3
Main circuit connection
3.3.1

Specification of main circuit terminals

Terminal
R/L1,
S/L2,
T/L3
U, V, W
P/+
, PR
P/+
, N/–
P/+
, P1
Tab. 3-2:
When using single-phase power input, terminals are L1, N.
Indicated as "+" on the terminal block of the single-phase power input model.
Indicated as "–" on the terminal block of the single-phase power input model.
3 - 6
Name
Description
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-HC) or
power regeneration common converter (FR-CV).
Inverter output
Voltage ouput of the inverter
(3~, 0V–power supply voltage, 0.2–400Hz)
Brake resistor
Connect a brake resistor (FR-ABR) across terminals P/+ and PR.
connection
(The brake resistor can not be connected to the FR-E720S-008SC and 015SC.)
Brake unit connection
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV)
or high power factor converter (FR-HC).
DC reactor connection
Remove the jumper across terminals P/+ and P1 and connect a DC reactor.
PE
For earthing the inverter chassis. Must be earthed.
Specification of main circuit terminal
Wiring