Mitsubishi Electric FR-E700 Series Instruction Manual page 344

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Misoperation prevention and parameter setting restriction
Parameter reading/writing restriction level (Pr. 296)
Level of reading/writing restriction by PU/NET mode operation command can be selected by Pr. 296.
PU Mode Operation Command
Pr. 296 Setting
Read
9999
0/100
1/101
2/102
3/103
4/104
5/105
6/106
Only parameters registered in the user group can be read/written.
99/199
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
Tab.6-52:
Level of password lock and reading/writing restriction
If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for
reading even when "✔" is indicated.
If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for
writing even when "✔" is indicated.
Parameter access from unit where parameter is written in PU operation mode (initially set to
operation panel, parameter unit) is restricted. (Refer to section 6.18.3 for PU mode operation
command source selection.)
This restricts parameter access from the command source that can write a parameter under
Network operation mode (initially RS-485 communication from PU connector or a communicati-
on option).
Read/write is enabled only in the simple mode parameters registered in the user group when
Pr. 160 "User group read selection" = "9999". Pr. 296 and Pr. 297 are always read/write enabled
whether registered to a user group or not.
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips (refer to
section 7.2).
6 - 200
RS-485 Communication
Write
Read
NET Mode Operation Command
Communication Option
Write
Read
Parameter
Write

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents