Mitsubishi Electric FR-E700 Series Instruction Manual page 77

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Wiring
Note on selecting a suitable power supply ELCB
If your application requires by installation standards an RCD (residual current device) as up stream
protection please select according to DIN VDE 0100-530 as following:
Single phase inverter type A or B
Three phase inverter only type B
Additionally, when selecting a residual current device (RCD), leakage current caused by the mains fil-
ter, the length of the shielded motor cable and the carrier frequency must be taken into consideration.
When connecting AC current using switches without a step function, brief asymmetrical loads may re-
sult in unwanted triggering of the residual current device (RCD). It is recommendable here to use a
Type B residual current device (RCD) with delayed actuation or to switch on all three phases simulta-
neously using a main contactor.
Calculate the trip current sensitivity of the ELB as follows:
● Breaker designed for harmonic and surge suppression:
IΔn ≥ 10 × (Ig1 + Ign + Igi + lg2 + lgm)
● Standard breaker:
IΔn ≥ 10 × [Ig1 + Ign + Igi + 3 × (Ig2 + lgm)]
Ig1, Ig2: Leakage currents in wire path during commercial power supply operation
Ign:
Igm:
Igi:
Example of leakage current per 1km
during the commercial power supply
operation when the CV cable is routed
in metal conduit
(200V/60Hz)
Power supply size [mm²]
Fig. 3-37: Leakage currents
NOTE
For star connection, the amount of leakage current is 1/3.
FR-E700SC EC
Leakage current of inverter input side noise filter
Leakage current of motor during commercial power supply operation
Leakage current of inverter unit
Leakage current example of 3-phase
induction motor during the
commercial power supply operation
(200V/60Hz)
Motor capacity [kW]
Electromagnetic compatibility (EMC)
Example of leakage current per 1km
during the commercial power supply
operation when the CV cable is routed
in metal conduit
(Three-phase three-wire delta
connection 400V/60Hz)
Power supply size [mm²]
Leakage current example of 3-phase
induction motor during the
commercial power supply operation
(Totally-enclosed fan-cooled type
motor 400V/60Hz)
Motor capacity [kW]