Change The Acceleration/Deceleration Time (Pr. 7, Pr. 8) - Mitsubishi Electric FR-E700 Series Instruction Manual

Hide thumbs Also See for FR-E700 Series:
Table of Contents

Advertisement

Basic settings
5.1.5

Change the acceleration/deceleration time (Pr. 7, Pr. 8)

Set in Pr. 7 "Acceleration time" a larger value for a slower speed increase and a smaller value for a faster
speed increase.
Set in Pr. 8 "Deceleration time" a larger value for a slower speed decrease and a smaller value for a fast-
er speed decrease.
Pr.
Name
No.
7
Acceleration time
8
Deceleration time
Depends on the Pr. 21 "Acceleration/deceleration time increments" setting. The initial value for
the setting range is "0 to 3600s" and setting increments is "0.1s".
NOTE
Too short acceleration/deceleration times may lead to an inverter shutoff with error message
(E.THT, E.THM, E.OCT, E.OVT ...).
Example
Change the Pr. 7 "Acceleration time" setting from "5s" to "10s".
Pr. 20
FR-E700SC EC
Initial Value
≤ FR-E720S-110SC
≤ FR-E740-095SC
FR-E740-120SC and 170SC
FR-E740-230SC and 300SC
≤ FR-E720S-110SC
≤ FR-E740-095SC
FR-E740-120SC and 170SC
FR-E740-230SC and 300SC
Hz
0
Pr. 7
Setting
Range
5s
0–3600s/
10s
0–360s
15s
5s
0–3600s/
10s
0–360s
15s
Fig. 5-7:
Acceleration/deceleration time
t
Pr. 8
Simple mode parameter list
Description
Set the motor acceleration time.
Set the motor deceleration time.
I000006C
5 - 9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents