Parameter
Specify operation mode at power on (Pr. 340)
Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power on (reset) changes as de-
scribed below:
Pr. 340
0
(initial
value)
1
10
Tab. 6-60: Operation mode of the inverter at power on
The operation mode cannot be switched directly between the PU operation mode and network
operation mode.
Operation mode can be changed between the PU operation mode and network operation mode
with th PU/EXT key of the operation panel and X65 signal.
FR-E700SC EC
Operation Mode
Pr. 79
at Power on, Power Restoration, Reset
0
(initial
External operation mode
value)
1
PU operation mode
2
External operation moderieb
3 / 4
External/PU combined operation mode
6
External operation mode
X12 (MRS) signal ON: External operation mode
7
X12 (MRS) signal OFF: External operation
mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3 / 4
External/PU combined operation mode
6
NET operation mode
X12 (MRS) signal ON: NET operation mode
7
X12 (MRS) signal OFF: External operation
mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3 / 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode
Selection of operation mode and operation location
Operation Mode Switching
Can be switched to external, PU or NET opera-
tion mode
Fixed to PU operation mode
Can be switched to external or NET operation
mode
Switching to PU operation mode disabled
Operation mode switching disabled
Can be switched to external, PU or NET opera-
tion mode with operation continued
Can be switched to external, PU or NET opera-
tion mode
Fixed to external operation mode (Forcibly
switched to external operation mode.)
Same as when Pr. 340 = 0
Can be switched to PU or NET operation
mode
Same as when Pr. 340 = 0
Fixed to NET operation mode
Same as when Pr. 340 = 0
Can be switched to PU or NET operation mode
with operation continued
Same as when Pr. 340 = 0
6 - 217