Selection and protection of a motor
Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
Set Pr. 71 according to the motor used:
Motor
Mitsubishi standard motor,
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Other manufacturer's standard motor
Other manufacturer's constant-torque motor
Tab. 6-16: Motor selection
For other settings of Pr. 71, refer to section 6.8.2.
In the parameter setting mode, read the following parameters and set desired values.
Parameter
Tab. 6-17: Parameter setting ranges
NOTES
When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants are used.
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed as "2516", set 2642, i.e. 2516 × 1.05 = 2641.8, in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addition of a
given value to the displayed value has no significance.)
6 - 94
Name
Motor excitation
82
current
90
Motor constant R1
91
Motor constant R2
92
Motor constant L1
93
Motor constant L2
94
Motor constant X
859
Torque current
SF-JR
SF-JR 4P (1.5kW or less)
SF-HR
Others
SF-JRCA 4P
SF-HRCA 4P
Others (SF-JRC, etc.)
Setting Range
Setting Increments
0–**** , 9999
0–**** , 9999
0–**** , 9999
0–**** , 9999
0–**** , 9999
0–**** , 9999
0–**** , 9999
Parameter
Pr. 71
4
24
44
4
14
54
14
4
14
Initial Value
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999