Parameter
6.10.3

Condition selection of function validity by second function selection signal

(RT, Pr. 155)

You can select the second function using the RT signal. For the RT signal, set "3" in any of Pr. 178 to
Pr. 184 "Input terminal function selection" to assign the function.
The second function has the following applications:
● Switching between normal use and emergency use.
● Switching between heavy load and light load.
● Changing of acceleration/deceleration time by broken line acceleration/deceleration.
● Switching of characteristic between main motor and sub motor.
Second functions selection
Following functions that can be set as second functions:
Function
Torque boost
Base frequency
Acceleration time
Deceleration time
Electronic thermal relay function
Stall prevention
Applied motor
Tab. 6-29: Functions that can be set as second functions
NOTES
When the RT signal is on, the above second function is selected at the same time.
Changing the terminal assignment using Pr. 178 to Pr. 184 "Input terminal function selection" may
affect the other functions. Make setting after confirming the function of each terminal.
FR-E700SC EC
Inverter
Start
High speed
Middle speed
Acceleration time
is reflected
Time
Function assignment of external terminals
Fig. 6-53:
Second functions connection diagram
Fig. 6-54:
Second acceleration/deceleration time example
Parameter Number as
1st Function
2nd Function
Pr. 0
Pr. 3
Pr. 7
Pr. 8
Pr. 44, Pr. 45
Pr. 9
Pr. 22
Pr. 71
I001145C
I001794E
Refer to
Page
Pr. 46
6-33
Pr. 47
6-54
Pr. 44
6-69
6-69
Pr. 51
6-80
Pr. 48
6-42
Pr. 450
6-85
6 - 119